Plan Review Details - Permit 18070401
Plan Review Stops For Permit 18070401
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By skennedy Date 2018-08-06 Time 10:21 Rev Time 0.00
Received By skennedy Date 2018-08-06 Time 10:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-18 Cont ID  
Sent By rmcdouga Date 2018-07-18 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2018-07-18 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By skennedy Date 2018-08-06 Time 10:21 Rev Time 0.00
Received By skennedy Date 2018-08-06 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By fgiaquin Date 2018-08-02 Time 06:59 Rev Time 0.00
Received By fgiaquin Date 2018-08-02 Time 06:23 Sent To  
Notes
2018-08-02 06:59:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLAN IS
 BARELY LEGIBLE AND HAS NO LEGEND FOR SYMBOLS. "R" WITH
 A BOX AROUND IT IS NOT THE SYMBOL FOR A RECEPTACLE. "R"
 TYPICALLY MEANS "RELOCATE" PLEASE REVIEW THE FOLLOWING
 SECTIONS FROM THE WEST PALM BEACH AMENDMENTS TO THE
 FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. NO KITCHEN COUNTERTOP RECEPTACLES ON PLAN AS PER
 210.52C1 NEC. PLEASE PROVIDE CORRECTION.
  
 3. ISLAND COUNTERTOP APPEARS TO HAVE MORE THAN A 6"
 OVERHANG. THE PROPOSED RECEPTACLES ON THE ISLAND DO NOT
 MEET THE REQUIREMENTS OF 210.52C2 AND 210.52C5
 EXCEPTION #5 NEC. PLEASE PROVIDE CORRECTION.
  
 4. PLAN SHOWS NO APPLIANCE RECEPTACLES FOR THE FRIDGE,
 MICROWAVE, DISHWASHER, DISPOSAL, OR RANGE AS PER
 210.50C NEC PLEASE PROVIDE CORRECTION.
  
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
  
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 INFORMATIONAL NOTE: PER THE WPB AMENDMENTS TO THE FBC,
 PLAN (BOTH COPIES) ARE REQUIRED TO BEAR THE NAME AND BE
 SIGNED (EVERY PAGE) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN AND HAVE THE ADDRESS OF THE PROJECT ON THEM. WPB
 FBC 107.1, 107.2; FS 471, 481
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-06 Cont ID  
Sent By skennedy Date 2018-08-06 Time 10:21 Rev Time 0.00
Received By skennedy Date 2018-07-10 Time 11:19 Sent To  
Notes
2018-07-12 11:19:11R07

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-06 Cont ID  
Sent By skennedy Date 2018-08-06 Time 10:20 Rev Time 0.00
Received By skennedy Date 2018-08-06 Time 09:05 Sent To  
Notes
***NONE***