Plan Review Details - Permit 18070299
Plan Review Stops For Permit 18070299
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 13:43 Rev Time 0.00
Received By shill Date 2018-08-12 Time 13:43 Sent To  
Notes
2018-08-12 13:45:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PLEASE CLARIFY SCOPE. A TEMPORARY
 CONSTRUCTION TRAILER IS EXEMPT FROM FLORIDA BUILDING
 CODE, BUT A TEMPORARY OFFICE TRAILER IS NOT.
  
 NO PLANS SUBMITTED; A SITE PLAN WAS SUBMITTED BUT DOES
 NOT SHOW DISTANCE TO PROPERTY LINES, ACCESSIBLE ROUTE,
 ETC. WHICH WOULD BE REQUIRED FOR A STRUCTURE SUBJECT TO
 REQUIREMENTS OF FBC.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By fgiaquin Date 2018-07-16 Time 06:43 Rev Time 0.00
Received By fgiaquin Date 2018-07-16 Time 06:28 Sent To  
Notes
2018-07-16 06:31:50ROUTED BACK TO BIN B03
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PANEL SCHEDULE, WIRE
 SIZE, CONDUIT SIZE, OCP? FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
  
 2. WILL TRAILER HAVE TEMPORARY ELECTRICAL SERVICE OR
 GENERATOR POWERED?
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By scaldero Date 2018-07-12 Time 11:09 Rev Time 0.00
Received By scaldero Date 2018-07-12 Time 10:59 Sent To E
Notes
2018-07-12 11:09:29PERMIT # 18070299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER NFPA 241 ? STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET.
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET.
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET.
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET.
  
 2) PLAN DOES NOT SHOW THE DISTANCE FROM THE TRAILER TO
 THE EXISTING DREYFOOS HALL BUILDING. BUT THE FEW
 DETAILS PROVIDED APPEAR TO INDICATE THAT THE REQUIRED
 SEPARATION IS NOT BEING MET.
 PLEASE RE-SUBMIT AND INCLUDE THE RELEVANT DETAILS
 SHOWING COMPLIANCE WITH THE ABOVE REQUIREMENTS.
  
 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL, EXIT STAIR DETAILS, INCLUDING HANDRAILS, ETC.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 13:45 Rev Time 0.00
Received By shill Date 2018-07-09 Time 13:51 Sent To  
Notes
2018-07-11 13:55:06B03

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By ES Date 2018-07-24 Time 16:03 Rev Time 0.50
Received By eschneid Date 2018-07-24 Time 16:03 Sent To  
Notes
2018-07-24 16:18:32FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE PERMIT CALLS THIS OUT AS AN OFFICE TRAILER. WAS
 THIS INTENDED TO BE THE CONSTRUCTION TRAILER? AN OFFICE
 TRAILER IS NOT PERMITTED TO BE A TEMPORARY STRUCTURE
 UNLESS IT IS A CONSTRUCTION TRAILER.
  
 2) PROVIDE A PLAN, WITH DIMENSIONS OF THE ACTUAL
 TRAILER THAT IS BEING PROPOSED.
  
 3) PROVIDE THE SCALED DRAWING, WITH DIMENSIONS, OF THE
 TRAILER ON THE SITE PLAN AND THE SCALED DIMENSIONS OF
 THE TRAILER TO THE PROPERTY LINES AND THE EXISTING
 BUILDING.
  
 4) WILL THE CONSTRUCTION TRAILER REQUIRE ADA ACCESS.
 THIS NEEDS TO BE SHOWN ON THE SITE PLAN.
  
 5) TEMPORARY CONSTRUCTION TRAILERS REQUIRE ONE PARKING
 SPACE PER 300 SQUARE FEET OF STRUCTURE. PLEASE SHOW THE
 PARKING SPACE(S) IN COMPLIANCE WITH CITY CODE
 REQUIREMENTS ON THE SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]