Plan Review Details - Permit 18070252
| Plan Review Stops For Permit 18070252 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2018-08-25 14:17:04 | PER JL/JP, NO SD REQUIRED IN FPL VAULT (INFO ONLY, NO | | | ACTION REQUIRED) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-10 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-10 |
Time |
18:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-08-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-08-03 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-07-30 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2018-08-03 10:44:50 | PERMIT # 18070252 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED PROVISO: | | | | | | 1) SHEET A7.0.1 - DOOR NOTE #7: AUTOMATIC DOOR | | | UNLOCKING DEVICE TO BE TESTED IN THE FIELD. STAIRS AND | | | EGRESS COMPONENTS SHALL CONFORM TO THE LIFE SAFETY | | | REQUIREMENTS OF CHAPTER 7 OF NFPA 101 FLORIDA 2015 | | | EDITION. | | | | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-09-11 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-07-17 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-14 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-10 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2018-08-14 11:49:42 | MECHANICAL PROVISOS | | | 8/14/18 | | | | | | 1) COMMISSIONING OF THE COMMON AC SYSTEMS AND | | | ELECTRICAL LIGHTING CONTROLS IS REQUIRED. FINAL REPORT | | | SHALL BE PROVIDED TO THE OWNERSHIP OF THE BUILDING AND | | | THE BUILDING DEPARTMENT PRIOR TO RECEIVING CERTIFICATE | | | OF OCCUPANCY. | | | | | | 2) ) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR | | | THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING | | | APPROVAL BY THE ENGINEER OF RECORD: | | | | | | A) SMOKE CONTROL FANS. | | | B) FIRE AND FIRE/SMOKE DAMPERS. | | | C) BAROMETRIC DAMPERS | | | D) DUCT SMOKE DETECTORS | | | E) AC ROOF AND DUCT STANDS, WALL BRACKETS | | | F) EXHAUST AND OUTSIDE AIR LOUVERS | | | G) C02 AND N02 SENSORS | | | H) PIPING INSULATIONS | | | I) ACCESS PANELS | | | J) GENERATOR | | | K) COMMERCIAL CLOTHES DRYERS | | | L) COOKING APPLIANCES | | | M) DUCT FIRE WRAPPING | | | N) FIRESTOPPING AND FIRE CAULKING | | | O) MANUFACTURER'S SPECIFICATIONS AND WIND LOAD | | | ENGINEERING FOR THE EXTERIOR BARBECUE. | | | P) STRUCTURAL DETAILS FOR ATTACHING THE AC UNITS AND | | | INLINE FAN SUPPORTS TO THE SLAB. | | | Q) WIND LOAD ENGINEERING FOR ALL ROOF TOP MOUNTED | | | MECHANICAL EQUIPMENT- OAU'S, FANS AND FAN CURBS, AC | | | STANDS, SUPPORTS ETC. | | | | | | 3) SMOKE CONTROL SYSTEM TESTING PRIOR TO C/O | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-08-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-22 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-22 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2018-08-14 11:57:52 | MECH SHEETS GOOD | | | CCOLE- 8/14/18 | | 2018-08-10 17:14:17 | ELECTRICAL SHEETS OK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-09-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2018-09-06 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2018-09-06 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2018-09-06 17:01:15 | PROVISO: RETAIL RAMP AND STAIR ON OLIVE AVENUE ARE NOT | | | ALLOWED TO ENCROACH INTO THE ROW AND SHALL BE ADJUSTED | | | TO BE TOTALLY INSIDE THE PROPERTY LINE. |
|
|
|