Plan Review Details - Permit 18070249
Plan Review Stops For Permit 18070249
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-11-02 Cont ID  
Sent By tklarge Date 2018-11-02 Time 10:59 Rev Time 0.00
Received By tklarge Date 2018-11-02 Time 10:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By tklarge Date 2018-07-24 Time 09:46 Rev Time 0.00
Received By tklarge Date 2018-07-24 Time 09:46 Sent To  
Notes
2018-07-24 09:47:011) THE EXISTING GAS DRAWING SHOWS A 1 INCH LINE FOR THE
 FUTURE GENERATOR AND THE THE DRAWING SUBMITTED BY
 STATIC ELECTRIC SHOWS A 3/4 INCH LINE. CLARIFY.
 2) THE GAS LINE AT THE OUTLET OF THE GAS METER SHALL BE
 1 1/4 INCH SCH. 40 PIPE BASED ON GAS SIZING TABLE 402.4
 (5) AT 2 PSI AND A TOTAL DEVELOPED LENGTH OF 175 FEET
 TO THE FARTHEST REGULATOR.
 3) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE REGULATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-02 Cont ID  
Sent By tklarge Date 2018-11-02 Time 11:00 Rev Time 0.00
Received By tklarge Date 2018-11-02 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-24 Cont ID  
Sent By tklarge Date 2018-07-24 Time 09:47 Rev Time 0.00
Received By tklarge Date 2018-07-24 Time 09:47 Sent To  
Notes
***NONE***