Plan Review Details - Permit 18070248
Plan Review Stops For Permit 18070248
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-01 Cont ID  
Sent By rmcdouga Date 2018-10-01 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2018-10-01 Time 07:40 Sent To P
Notes
2018-10-01 07:42:02AE FLOOD ZONE, THE GENERATOR IS TO BE AT OR ABOVE THE
 FLOOR ELEVATION OF THE DWELLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-16 Cont ID  
Sent By rmcdouga Date 2018-07-16 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 13:27 Sent To P
Notes
2018-07-16 13:33:57AE FLOOD ZONE, THE GENERATOR IS TO BE AT OR ABOVE THE
 FLOOR ELEVATION OF THE DWELLING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-28 Cont ID  
Sent By jleahy Date 2018-09-28 Time 17:17 Rev Time 0.00
Received By jleahy Date 2018-09-28 Time 17:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By jleahy Date 2018-07-19 Time 17:49 Rev Time 0.00
Received By jleahy Date 2018-07-19 Time 17:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-11-01 Cont ID  
Sent By tklarge Date 2018-11-01 Time 13:24 Rev Time 0.00
Received By tklarge Date 2018-11-01 Time 11:56 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-10-03 Cont ID  
Sent By tklarge Date 2018-10-03 Time 06:18 Rev Time 0.00
Received By tklarge Date 2018-10-03 Time 05:12 Sent To I
Notes
2018-10-03 05:54:521) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE GENERATOR IN RELATION TO BUILDING OPENINGS,
 DISTANCE FROM THE STRUCTURE, ETC. 2017 FBC 107.2.1.
 2) THE 3/4 INCH PE TO THE EXISTING GAS LOADS IS
 UNDERSIZED.THE ORIGINAL PLAN ON FILE WITH THE CITY
 SHOWS THE LINE FROM THE OUTLET OF THE GAS METER GOING
 INTO A TEE AND THE TOTAL LOAD BEING DISTRIBUTED BETWEEN
 2 - 3/4 INCH PE LINES WHICH MEETS CODE. ONE 3/4 INCH PE
 LINE SERVING THE EXISTING BTU LOAD OF 1,697,000 WILL
 NOT WORK PER TABLE 402..2 (22) OF THE FUEL GAS CODE.IF
 ONE LINE IS TO SUPPLY THE EXISTING BTU LOAD, IT SHALL
 BE 1 1/4 INCH PE.
 3) YOU HAVE SUBMITTED COPIESS OF AN EXISTING CITY
 DRAWING TO WHICH YOU HAVE ADDED THE GENERATOR ONTO THE
 DRWAING. THESE DOCUMENTS ARE FOR REFERENCE ONLY AND
 CANNOT BE USED TO ADD APPLIANCES/ EQUIPMENT AND BE
 SUBMITTED FOR PERMIT. REMOVE THESE DRAWINGS FROM THE
 PERMIT PACKAGE. 2017 FBC SEC.107.2.1.
 4) THERE ARE COPIES OF 2 DIFFERENT GAS DRAWINGS IN THIS
 SUBMITTAL. REMOVE ALL OLD GAS DRAWINGS AND COMBINE THE
 DOCUMENTS INTO TWO FULL, COMPLETE SETS OF PLANS FOR
 REVIEW. 2017 FBC SEC. 107.2.1.
 5) THE GENERATOR SHALL BE A MINIMUM OF 10 FEET FROM ANY
 BUILDING OPENING INCLUDING SOFFIT VENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By tklarge Date 2018-07-24 Time 09:44 Rev Time 0.00
Received By tklarge Date 2018-07-24 Time 09:24 Sent To I
Notes
2018-07-24 09:44:461) THE EXISTING GAS DRAWING SHOWS A 1 INCH LINE FOR THE
 FUTURE GENERATOR AND THE THE DRAWING SUBMITTED BY
 STATIC ELECTRIC SHOWS A 3/4 INCH LINE. CLARIFY.
 2) THE GAS LINE AT THE OUTLET OF THE GAS METER SHALL BE
 1 1/4 INCH SCH. 40 PIPE BASED ON GAS SIZING TABLE 402.4
 (5) AT 2 PSI AND A TOTAL DEVELOPED LENGTH OF 175 FEET
 TO THE FARTHEST REGULATOR.
 3) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE REGULATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-01 Cont ID  
Sent By tklarge Date 2018-11-01 Time 13:24 Rev Time 0.00
Received By tklarge Date 2018-10-16 Time 13:53 Sent To  
Notes
2018-10-17 13:53:09RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-03 Cont ID  
Sent By tklarge Date 2018-10-03 Time 06:18 Rev Time 0.00
Received By tklarge Date 2018-09-21 Time 16:04 Sent To  
Notes
2018-09-24 16:04:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-24 Cont ID  
Sent By tklarge Date 2018-07-24 Time 09:45 Rev Time 0.00
Received By tklarge Date 2018-07-06 Time 13:06 Sent To  
Notes
2018-07-09 13:06:34ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-26 Cont ID  
Sent By mcruz Date 2018-10-26 Time 11:58 Rev Time 0.00
Received By mcruz Date 2018-10-26 Time 11:57 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-28 Cont ID  
Sent By mcruz Date 2018-09-28 Time 11:29 Rev Time 0.00
Received By mcruz Date 2018-09-28 Time 11:29 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By mcruz Date 2018-07-12 Time 15:46 Rev Time 0.00
Received By mcruz Date 2018-07-12 Time 15:41 Sent To  
Notes
2018-07-12 15:46:51ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) THE LOCATION OF THE PROPOSED GENERATOR DOES NOT MEET
 SETBACK REQUIREMENTS. THE GENERATOR SHOULD BE AT LEAST
 11' FROM THE WEST PROPERTY LINE.
  
 NOTE: PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]