Plan Review Details - Permit 18070237
Plan Review Stops For Permit 18070237
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By shill Date 2018-07-23 Time 10:00 Rev Time 0.00
Received By shill Date 2018-07-23 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By jleahy Date 2018-07-31 Time 12:33 Rev Time 0.00
Received By jleahy Date 2018-07-31 Time 12:33 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By jpearson Date 2018-07-24 Time 09:27 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 17:11 Sent To  
Notes
2018-07-24 09:26:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET CS IS
 NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 (ALSO SEE CURRENT CODES ABOVE)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. SPECIFYING THAT THE CONTRACTOR IS REQUIRED
 TO CONFIRM THE LOAD IS NOT SATISFACTORY. NEC 215.2,
 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 14:33 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 14:27 Sent To I
Notes
2018-07-31 14:32:57PERMIT # 18070237
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO, AS THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED IN THE RESUBMITTAL:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) CS: OCCUPANT LOAD IS LISTED AS "EXISTING/UNCHANGED".
 PLEASE PROVIDE THE OCCUPANT LOAD, AS THE EXISTING
 OCCUPANT LOAD IS UNKNOWN.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By scaldero Date 2018-07-12 Time 11:28 Rev Time 0.00
Received By scaldero Date 2018-07-12 Time 11:13 Sent To  
Notes
2018-07-12 11:28:41PERMIT # 18070237
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SHEETS CS, A1.2, AND E2.0: SEATING LAYOUT CONFLICTS
 ON THESE SHEETS.
 SHEET CS: 2 ROWS OF 2-TOP TABLES/CHAIRS AND ACCESSIBLE
 SEATING ON 1 END OF ROW OF BOOTHS.
 SHEET A1.2: 1 ROW OF 2-TOP TABLES/CHAIRS AND ACCESSIBLE
 SEATING ON 1 END OF ROW OF BOOTHS.
 SHEET E2.0: 1 ROW OF T-TOP TABLES/CHAIRS AND ACCESSIBLE
 SEATING ON BOTH ENDS OF ROW OF BOOTS.
 PLEASE REVIEW AND PROVIDE ACCURATE SEATING ARRANGEMENT
 ON ALL SHEETS.
  
 3) CS: OCCUPANT LOAD IS LISTED AS "EXISTING/UNCHANGED".
 PLEASE PROVIDE THE OCCUPANT LOAD, AS THE EXISTING
 OCCUPANT LOAD IS UNKNOWN.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-01 Cont ID  
Sent By cpuell Date 2018-08-01 Time 07:21 Rev Time 0.00
Received By cpuell Date 2018-07-27 Time 06:12 Sent To  
Notes
2018-07-31 14:18:027/30 TO FIRE BOX
  
  
2018-07-30 17:12:367/30 TO JP DESK
  
  
2018-07-30 06:12:33SENT EMAIL TO APPLICANT, DOES NOT APPEAR THAT FIRE
 COMMENTS WERE ADDRESSED (ONLY ELECTRICAL); ELECTRICAL
 SHEETS NOT SIGNED & SEALED
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 10:49 Rev Time 0.00
Received By tklarge Date 2018-07-09 Time 14:31 Sent To  
Notes
2018-07-11 14:31:45B20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-07-23 Cont ID  
Sent By ccole Date 2018-07-23 Time 16:35 Rev Time 0.00
Received By ccole Date 2018-07-23 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 10:48 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 10:48 Sent To I
Notes
2018-07-25 10:49:31EQUIPMENT SHOWN AS EXISTING TO REMAIN. PLUMBING PERMIT
 NOT REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By shill Date 2018-08-01 Time 14:26 Rev Time 0.00
Received By shill Date 2018-08-01 Time 14:26 Sent To  
Notes
2018-08-01 14:26:43RECEIVED 1 SET S&S ELECTRICAL SHEETS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By shill Date 2018-07-31 Time 14:14 Rev Time 0.00
Received By shill Date 2018-07-31 Time 14:14 Sent To  
Notes
2018-07-31 14:15:15NEED SIGNED AND SEALED ELECTRICAL SHEETS; APPLICANT TO
 PROVIDE PRIOR TO ISSUANCE
  