Plan Review Details - Permit 18070236
Plan Review Stops For Permit 18070236
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 06:15 Rev Time 0.00
Received By shill Date 2018-08-10 Time 06:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By shill Date 2018-07-20 Time 07:58 Rev Time 0.00
Received By shill Date 2018-07-09 Time 16:00 Sent To  
Notes
2018-07-20 08:03:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, PROVIDE THE MEAN ROOF HEIGHT. PROPOSED
 DESIGN PRESSURES WERE NOT PROVIDED. THIS IS REQUIRED IF
 YOU WANT FOR THE BUILDING DIVISION TO DETERMINE DESIGN
 PRESSURES.
  
 2. REVISE APPLICATION TO INCLUDE ROOF DECK TYPE AND
 INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED, FBC B
 1609.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-10 Cont ID  
Sent By shill Date 2018-08-10 Time 06:15 Rev Time 0.00
Received By shill Date 2018-08-01 Time 11:10 Sent To  
Notes
2018-08-02 11:10:14RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-20 Cont ID  
Sent By shill Date 2018-07-20 Time 08:05 Rev Time 0.00
Received By shill Date 2018-07-06 Time 11:07 Sent To  
Notes
2018-07-09 11:07:46CTHROOP