Plan Review Details - Permit 18070228
Plan Review Stops For Permit 18070228
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 16:00 Rev Time 0.00
Received By dbattles Date 2018-10-25 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-04 Cont ID  
Sent By dbattles Date 2018-10-04 Time 09:12 Rev Time 0.00
Received By dbattles Date 2018-10-04 Time 09:12 Sent To  
Notes
2018-10-04 09:12:17****CORRECTIONS****
 W.P.B. PERMIT: 18070228-2
 REVISION 2ND REVIEW: OCTOBER 4, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR THE
 CHANGE OF ROOFING OFF MASTER SUITE.
 1-2. [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING
 AS STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 PLEASE PROVIDE THE MAXIMUM DESIGN PRESSURE, CHOOSE THE
 SYSTEM TO BE INSTALLED AND PROVIDE ENHANCED NAILING IF
 APPLICABLE TO THE SYSTEM BEING INSTALLED.
  
 2. OK
  
 3. OK
  
 NOTE:
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 16:21 Rev Time 0.00
Received By dbattles Date 2018-08-08 Time 15:13 Sent To  
Notes
2018-08-08 16:21:34****CORRECTIONS****
 W.P.B. PERMIT: 18070228
 REVIEWED: AUGUST 8, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR THE
 CHANGE OF ROOFING OFF MASTER SUITE.
  
 2. PROVIDE ROOF DRAINAGE CALCULATION AND SCUPPER DETAIL
 TO MEET [FBC R903.4]ROOF DRAINAGE AND SCUPPERS.
  
 3. PLEASE PROVIDE DESCRIPTION OF CHANGES IN THE
 REVISION.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By jpearson Date 2018-10-25 Time 11:27 Rev Time 0.00
Received By jpearson Date 2018-10-25 Time 11:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 15:33 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 15:33 Sent To  
Notes
2018-09-22 15:33:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEEDER F1 TO FPL IS NOT RATED FOR 600 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
 2. FEEDER F2A IS NOT RATED FOR 600 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
 3. FEEDER F2B IS NOT RATED FOR 600 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 10:19 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 06:50 Sent To  
Notes
2018-07-30 10:19:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO REVISIONS ARE INDICATED ON PLAN. PROVIDE
 NARRATIVE OF REVISIONS AND CLOUD THESE CHANGES ON PLAN.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 18:11 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 18:11 Sent To  
Notes
2018-08-22 18:12:10GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-25 Cont ID  
Sent By dbattles Date 2018-10-25 Time 16:00 Rev Time 0.00
Received By dbattles Date 2018-10-16 Time 11:36 Sent To  
Notes
2018-10-18 11:36:56RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-04 Cont ID  
Sent By hmoser Date 2018-10-04 Time 15:19 Rev Time 0.00
Received By hmoser Date 2018-09-11 Time 11:09 Sent To  
Notes
2018-09-13 11:10:05R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 18:12 Rev Time 0.00
Received By lcrespo Date 2018-07-06 Time 10:41 Sent To  
Notes
2018-07-11 10:41:48R17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By hmoser Date 2018-10-04 Time 15:17 Rev Time 0.00
Received By hmoser Date 2018-10-04 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By hmoser Date 2018-07-30 Time 11:44 Rev Time 0.00
Received By hmoser Date 2018-07-30 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-02 Cont ID  
Sent By lcrespo Date 2018-10-02 Time 09:34 Rev Time 0.00
Received By jesmith Date 2018-10-02 Time 09:06 Sent To  
Notes
2018-10-02 09:11:072ND REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
  
 1. THE VALVES FOR THE STACKABLE WASHING MACHINE(S)
 SHALL BE ACCESSIBLE. FBC RES P2903.9.3
 A. PLEASE REVIEW RED LINED NOTES MADE ON SHEET P-2 REV
 1 FOR CLARIFICATION.
 2. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. FBC RES P2903.5
 A. PLEASE REVIEW RED LINED NOTES MADE ON SHEET P-1 REV
 1 FOR CLARIFICATION.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-22 Cont ID  
Sent By tklarge Date 2018-08-22 Time 18:12 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 18:12 Sent To  
Notes
2018-08-22 18:13:0608/22/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By pgreilic Date 2018-09-20 Time   Rev Time 0.00
Received By pgreilic Date 2018-09-18 Time 11:10 Sent To  
Notes
2018-09-20 12:07:01PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2018-08-22 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-22 Time 15:34 Sent To  
Notes
2018-08-22 15:34:421.) PROVIDE A SURVEY OR SITE PLAN CLEARLY INDICATING
 THE AREA OF THE STRUCTURE, AND LABEL SETBACKS
 ACCORDINGLY
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]