Plan Review Details - Permit 18070221
Plan Review Stops For Permit 18070221
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-06 Cont ID  
Sent By lcrespo Date 2018-08-06 Time 06:42 Rev Time 0.00
Received By lcrespo Date 2018-08-03 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-02 Cont ID  
Sent By tklarge Date 2018-08-02 Time 06:58 Rev Time 0.00
Received By tklarge Date 2018-07-31 Time 14:09 Sent To  
Notes
2018-08-01 14:09:13RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 08:23 Rev Time 0.00
Received By tklarge Date 2018-07-20 Time 14:40 Sent To  
Notes
2018-07-23 14:40:14RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-13 Cont ID  
Sent By lcrespo Date 2018-07-13 Time 07:20 Rev Time 0.00
Received By lcrespo Date 2018-07-13 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-08-06 Cont ID  
Sent By lcrespo Date 2018-08-06 Time 06:42 Rev Time 0.00
Received By lcrespo Date 2018-08-03 Time 17:13 Sent To  
Notes
2018-08-06 06:43:1108/03/18 APPROVED BY PLUMBING AND SENT TO UTILITIES,
 LAC

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-08-02 Cont ID  
Sent By tklarge Date 2018-08-02 Time 06:57 Rev Time 0.00
Received By tklarge Date 2018-08-02 Time 06:31 Sent To I
Notes
2018-08-02 06:57:031) THE SITE PLAN YOU HAVE SUBMITTED NOTES A PVB
 BACKFLOW DEVICE ON THE DOMESTIC WATER, IRRIGATION AND
 POOL AUTOFILL BUT YOU HAVE SUBMITTED SPECS FOR AN RPZ
 AND A PVB DEVICE. THE SITE PLAN NEEDS TO BE CORRECTED
 TO SHOW THE CORRECT DEVICES AND THEIR LOCATION.
 2) THE 720A PVB DEVICE IS NOT A LEAD FREE DEVICE AND
 CANNOT BE INSTALLED ON THE AUTOFILL. THE WILKINS 420XL
 IS A LEAD FREE DEVICE AND IS APPROVED FOR THIS TYPE OF
 INSTALLATION OR CONSIDER THE USE OF ANOTHER LEAD FREE
 DEVICE. THE UNIT CURRENTLY INSTALLED ON THE POOL
 AUTOFILL MUST BE REPLACED. 2017 FBC-PLUMBING
 SEC.605.2.1.
 3) SUBMIT TWO COPIES OF THE 975XL2 DEVICE AND TWO
 COPIES OF THE DEVICE TO BE USED FOR THE POOL AUTOFILL
 AND TWO COPIES OF THE DEVICE TO BE USED FOR THE
 IRRIGATION SYSTEM. ALL DEVICES SHALL BE LEAD FREE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 08:23 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 07:37 Sent To I
Notes
2018-07-26 08:01:081) THE SUBMITTED DOCUMENTS FOR THE RPZ DOES NOT STATE
 THAT THE DEVICE IS ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL'S
 LIST OF APPROVED DEVICES. YOU NEED TO SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS, NOT THE INSTALLATION
 INSTRUCTIONS. CITY OF WPB CROSS CONNECTION CONTROL
 MANUAL REQS.
 2) THE DESCRIPTION OF THE WORK ON THE PERMIT
 APPLICATION IS VAGUE. INDICATE ON THE PERMIT
 APPLICATION HOW MANY BACKFLOW DEVICES ARE BEING
 INSTALLED AND WHAT THEY ARE BEING INSTALLED ON (
 IRRIGATION, AUTOFILL FOR POOL, DOMESTIC SYSTEM?). WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE MANFACTURER'S SPECIFICATIONS FOR THE ANTI-SIPHON
 PRESSURE VACUUM BREAKER CANNOT BE USED FOR BACKPRESSURE
 BACKFLOW PER THE MANUFACTURER'S SPECIFICATIONS AND THE
 SPECIFICATIONS DO NOT STATE THAT THE DEVICE IS LEAD
 FREE. SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS
 FOR THE CORRECT DEVICE TO BE USED FOR THE SPECIFIC
 APPLICATION. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT TWO COPIES OF A HAND DRAWN SITE PLAN SHOWIN
 THE LOCATION OF EACH DEVICE AND THE TYPE OF SYSTEM ON
 WHICH IT IS INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-13 Cont ID  
Sent By lcrespo Date 2018-07-13 Time 07:18 Rev Time 0.00
Received By lcrespo Date 2018-07-13 Time 07:18 Sent To  
Notes
2018-07-13 07:19:5707/13/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN
 ECTION-CONTROL-MANUAL FOR MORE INFORMATION. ALL
 BACKFLOW DEVICES MUST BE LEAD FREE. LEAD FREE (LF)
 SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED ON
 THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 2. PLEASE PROVIDE IN THE APPLICATION WHERE THIS DEVICE
 IS BEING USED AT AND FOR WHAT REASON. A SITE PLAN
 DEPICTING THE GENERAL LOCATION OF THE PROPOSED BACKFLOW
 PREVENTION DEVICE, THIS CAN BE DONE BY GOING TO THE
 PROPERTY APPRAISER WEBSITE AND PRINT OUT A STRUCTURAL
 LAYOUT OF THE BUILDING AND HAND DRAW THE METER LOCATION
 WITH THE BACKFLOW.
  
 3. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 AS LEAD FREE.
  
 4. UNDER NOTICE IT STATES; VACUUM BREAKERS ARE NOT
 DESIGNED, TESTED OR APPROVED TO PROTECT AGAINST
 BACKPRESSURE BACKFLOW OR WATER HAMMER SHOCK. FOR
 PROTECTION AGAINST BACKPRESSURE BACKFLOW, INSTALL WATTS
 909/009 REDUCED PRESSURE ZONE BACKFLOW PREVENTER. FOR
 PROTECTION AGAINST WATER HAMMER SHOCK INSTALL A WATTS
 SERIES 15 WATER HAMMER ARRESTOR UTILIZING GOOD PLUMBING
 PRACTICE IF THIS IS THE CASE THIS PARTICULAR MODEL WILL
 NOT BE APPROVED.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  