Plan Review Details - Permit 18070206
Plan Review Stops For Permit 18070206
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2018-08-21 Time 16:37 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-08-17 Cont ID  
Sent By rmcdouga Date 2018-08-17 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2018-08-17 Time 16:16 Sent To I
Notes
2018-08-17 16:25:35PLAN REVIEW COMMENTS
 (COMMENTS FROM FIRST & SECOND REVIEWS WERE NOT
 ADDRESSED.)
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003
 PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW
 GENERATOR IS NOT LISTED ON THE GENERATOR PAD
 ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD
 DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL
 INSTALL. FBCR-G 2404.6
  
 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR
 THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER
 THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF
 UPDATED GENERATOR PAD DRAWINGS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-31 Time 15:18 Sent To I
Notes
2018-07-31 15:46:43PLAN REVIEW COMMENTS
 (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.)
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003
 PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW
 GENERATOR IS NOT LISTED ON THE GENERATOR PAD
 ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD
 DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL
 INSTALL. FBCR-G 2404.6
  
 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR
 THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER
 THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF
 UPDATED GENERATOR PAD DRAWINGS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2018-07-19 Time 11:27 Sent To I
Notes
2018-07-19 11:45:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003
 PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW
 GENERATOR IS NOT LISTED ON THE GENERATOR PAD
 ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD
 DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL
 INSTALL. FBCR-G 2404.6
  
 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR
 THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER
 THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF
 UPDATED GENERATOR PAD DRAWINGS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-27 Cont ID  
Sent By fgiaquin Date 2018-07-27 Time 06:37 Rev Time 0.00
Received By fgiaquin Date 2018-07-27 Time 06:32 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By fgiaquin Date 2018-07-17 Time 06:12 Rev Time 0.00
Received By fgiaquin Date 2018-07-17 Time 06:11 Sent To G
Notes
2018-07-17 06:12:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 2. ADDRESS MUST BE ON PLANS FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-16 Cont ID  
Sent By lcrespo Date 2018-08-16 Time 07:12 Rev Time 0.00
Received By lcrespo Date 2018-08-16 Time 07:11 Sent To  
Notes
2018-08-16 07:13:2608/16/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By tklarge Date 2018-07-27 Time 10:25 Rev Time 0.00
Received By tklarge Date 2018-07-27 Time 09:53 Sent To  
Notes
2018-07-27 10:24:36NOTE: IT DOES NOT APPEAR THAT ANY OF THE PREVIOUS GAS
 PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
  
 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS
 ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A
 DEVELOPED LENGTH OF 145 FEET TO THE FARTHEST GAS
 OUTLET. THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE
 FARTHEST DISTANCE. CLARIFY.
 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE
 EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS
 SHOWN AS 487,000 BTU'S.
 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE
 ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2
 PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW
 THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE
 FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE
 SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM.
 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP
 REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE
 USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM.
 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS.
 THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE
 REGULATORS.
 6) THE LOCATION OF THE GENERATOR EXHAUST SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION MANUAL OR IF NOT
 SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET FROM ANY
 BUILDING OPENINGS.
 7) IS THE GAS METER FOR THE GENERATOR GOING TO BE A NEW
 METER JUST FOR THE GENERATOR? CLARIFY ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By tklarge Date 2018-07-19 Time 09:58 Rev Time 0.00
Received By tklarge Date 2018-07-19 Time 06:40 Sent To  
Notes
2018-07-19 06:46:411) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS
 ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A
 DEVELOPED LENGTH OF 145 FEET TO THE FARTHEST GAS
 OUTLET. THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE
 FARTHEST DISTANCE. CLARIFY.
 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE
 EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS
 SHOWN AS 487,000 BTU'S.
 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE
 ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2
 PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW
 THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE
 FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE
 SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM.
 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP
 REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE
 USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM.
 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS.
 THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE
 REGULATORS.
 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE
 PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS.
 WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING
 USED.
 7) THE LOCATION OF THE GENERATOR EXHAUST SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION MANUAL OR IF NOT
 SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET FROM ANY
 BUILDING OPENINGS.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 15:31 Sent To  
Notes
2018-08-21 15:32:04RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-17 Cont ID  
Sent By rmcdouga Date 2018-08-17 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2018-08-08 Time 15:09 Sent To  
Notes
2018-08-09 15:09:52RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 14:29 Sent To  
Notes
2018-07-26 14:30:09RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2018-07-05 Time 13:50 Sent To  
Notes
2018-07-06 13:50:23ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By mcruz Date 2018-07-11 Time 15:04 Rev Time 0.00
Received By mcruz Date 2018-07-11 Time 14:53 Sent To  
Notes
2018-07-11 15:05:15ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 3.5' FROM SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]