Plan Review Details - Permit 18070206
| Plan Review Stops For Permit 18070206 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-21 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-21 |
Time |
16:37 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-17 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-17 |
Time |
16:16 |
Sent To |
I |
|
| Notes |
| 2018-08-17 16:25:35 | PLAN REVIEW COMMENTS | | | (COMMENTS FROM FIRST & SECOND REVIEWS WERE NOT | | | ADDRESSED.) | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003 | | | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH | | | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | | ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW | | | GENERATOR IS NOT LISTED ON THE GENERATOR PAD | | | ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD | | | DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL | | | INSTALL. FBCR-G 2404.6 | | | | | | 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR | | | THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER | | | THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF | | | UPDATED GENERATOR PAD DRAWINGS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-31 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-31 |
Time |
15:18 |
Sent To |
I |
|
| Notes |
| 2018-07-31 15:46:43 | PLAN REVIEW COMMENTS | | | (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.) | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003 | | | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH | | | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | | ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW | | | GENERATOR IS NOT LISTED ON THE GENERATOR PAD | | | ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD | | | DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL | | | INSTALL. FBCR-G 2404.6 | | | | | | 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR | | | THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER | | | THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF | | | UPDATED GENERATOR PAD DRAWINGS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-19 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-19 |
Time |
11:27 |
Sent To |
I |
|
| Notes |
| 2018-07-19 11:45:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003 | | | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH | | | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE | | | PROVISIONS OF SECTION 471.025, F.S., AND RULE | | | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED | | | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL | | | ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW | | | GENERATOR IS NOT LISTED ON THE GENERATOR PAD | | | ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD | | | DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL | | | INSTALL. FBCR-G 2404.6 | | | | | | 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR | | | THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER | | | THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF | | | UPDATED GENERATOR PAD DRAWINGS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-27 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-27 |
Time |
06:32 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-17 |
Time |
06:12 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-17 |
Time |
06:11 |
Sent To |
G |
|
| Notes |
| 2018-07-17 06:12:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON | | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | | | | 2. ADDRESS MUST BE ON PLANS FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-08-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-16 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-08-16 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2018-08-16 07:13:26 | 08/16/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-27 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-27 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2018-07-27 10:24:36 | NOTE: IT DOES NOT APPEAR THAT ANY OF THE PREVIOUS GAS | | | PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS | | | ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A | | | DEVELOPED LENGTH OF 145 FEET TO THE FARTHEST GAS | | | OUTLET. THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE | | | FARTHEST DISTANCE. CLARIFY. | | | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE | | | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE | | | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, | | | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE | | | EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS | | | SHOWN AS 487,000 BTU'S. | | | 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE | | | ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2 | | | PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW | | | THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE | | | FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE | | | SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM. | | | 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP | | | REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE | | | USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM. | | | 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS. | | | THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE | | | REGULATORS. | | | 6) THE LOCATION OF THE GENERATOR EXHAUST SHALL COMPLY | | | WITH THE MANUFACTURER'S INSTALLATION MANUAL OR IF NOT | | | SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET FROM ANY | | | BUILDING OPENINGS. | | | 7) IS THE GAS METER FOR THE GENERATOR GOING TO BE A NEW | | | METER JUST FOR THE GENERATOR? CLARIFY ON THE PLANS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-19 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-19 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2018-07-19 06:46:41 | 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS | | | ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A | | | DEVELOPED LENGTH OF 145 FEET TO THE FARTHEST GAS | | | OUTLET. THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE | | | FARTHEST DISTANCE. CLARIFY. | | | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE | | | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE | | | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, | | | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE | | | EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS | | | SHOWN AS 487,000 BTU'S. | | | 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE | | | ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2 | | | PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW | | | THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE | | | FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE | | | SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM. | | | 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP | | | REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE | | | USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM. | | | 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS. | | | THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE | | | REGULATORS. | | | 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE | | | PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS. | | | WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING | | | USED. | | | 7) THE LOCATION OF THE GENERATOR EXHAUST SHALL COMPLY | | | WITH THE MANUFACTURER'S INSTALLATION MANUAL OR IF NOT | | | SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET FROM ANY | | | BUILDING OPENINGS. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-21 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-20 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2018-08-21 15:32:04 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-17 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-08 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2018-08-09 15:09:52 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-31 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-25 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2018-07-26 14:30:09 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-19 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-05 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2018-07-06 13:50:23 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-11 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-11 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2018-07-11 15:05:15 | ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST | | | 3.5' FROM SIDE PROPERTY LINE. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|
|