| Plan Review Stops For Permit 18070202 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-09 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-09 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2018-10-09 16:49:32 | SIGNED SEALED GENERATOR PAD PLAN TO BE SUBMITTED PRIOR | | | TO THE FINAL ELECTRICAL INSPECTION JLEAHY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-26 |
Time |
06:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-26 |
Time |
06:39 |
Sent To |
I |
|
| Notes |
| 2018-09-26 06:41:50 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING (COMMENTS FROM 1ST REVIEW WERE NOT | | | ADDRESSED) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. FAC | | | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. ENGINEERING PLAS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED | | | IN ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-19 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-19 |
Time |
15:39 |
Sent To |
I |
|
| Notes |
| 2018-07-19 15:44:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. FAC | | | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. ENGINEERING PLAS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED | | | IN ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-09 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-09 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2018-10-09 16:48:17 | GAS PERMIT 18070203 HAS BEEN SEPARATED FROM THIS PERMIT | | | SO THEY CAN DO THE SERVICE CHANGE | | | | | | GAS PERMIT IS NOW A STAND ALONE PERMIT. | | | | | | SIGNED SEALED GENERATOR PAD PLAN TO BE SUBMITTED PRIOR | | | TO THE FINAL ELECTRICAL INSPECTION.. JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-09-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-09-21 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-09-21 |
Time |
06:30 |
Sent To |
G |
|
| Notes |
| 2018-09-21 06:33:58 | SAME VIOLATIONS AS PREVIOUS REVIEW: | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON | | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | | | | 2. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1 | | | | | | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS NOT A "SIZING REPORT". NEC 220; FBC RE E3602.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-17 |
Time |
05:57 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-17 |
Time |
05:42 |
Sent To |
G |
|
| Notes |
| 2018-07-17 05:57:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON | | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | | | | 2. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-09 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-09 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2018-10-09 16:50:32 | GAS PERMIT 18070203 HAS BEEN SEPARATED FROM THIS PERMIT | | | SO THE SERVICE CHANGE COULD BE DONE JLEAHY..... |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-09-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-09-21 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-09-21 |
Time |
17:38 |
Sent To |
|
|
| Notes |
| 2018-09-21 17:40:04 | 09/21/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE SECOND REQUEST, THE CITY RECORDS SHOW AN | | | EXISTING GAS SYSTEM FOR THIS ADDRESS. THE EXISTING GAS | | | DRAWING ON RECORD SHOWS A DEVELOPED LENGTH OF 60 FEET | | | TO THE FARTHEST GAS OUTLET. THE SUBMITTED GAS PLAN | | | SHOWS 15 FEET AS THE FARTHEST DISTANCE, PLEASE CLARIFY. | | | SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP | | | REGULATORS TO THE FARTHEST OUTLET. THIS DISTANCE SHALL | | | BE USED IN THE SIZING OF THE LOW-PRESSURE SYSTEM. | | | | | | 2. THE SECOND REQUEST, SUBMIT PAGES 40 & 41 OF THE GAS | | | REGULATOR SPECS. THESE ARE THE INSTALLATION | | | INSTRUCTIONS FOR THE REGULATORS. | | | | | | 3. THE SECOND REQUEST, THERE ARE TWO DIFFERENT SIZING | | | TABLES FOR THE PE PIPE: ONE FROM NFPA 54 AND ONE FROM | | | 2017 FBC-FUEL GAS. WHICH ONE IS BEING USED? REMOVE THE | | | TABLE NOT BEING USED. | | | | | | 4. THE SECOND REQUEST, THE LOCATION OF THE GENERATOR | | | EXHAUST SHALL COMPLY WITH THE MANUFACTURER'S | | | INSTALLATION MANUAL OR IF NOT SPECIFIED IN THE MANUAL, | | | A MINIMUM OF 10 FEET FROM ANY BUILDING OPENINGS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-19 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-19 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2018-07-19 13:21:18 | | | | 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS | | | ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A | | | DEVELOPED LENGTH OF 60 FEET TO THE FARTHEST GAS OUTLET. | | | THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE FARTHEST | | | DISTANCE. CLARIFY. | | | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE | | | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE | | | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, | | | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE | | | EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS | | | SHOWN AS 407,000 BTU'S. | | | 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE | | | ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2 | | | PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW | | | THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE | | | FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE | | | SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM. | | | 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP | | | REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE | | | USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM. | | | 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS. | | | THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE | | | REGULATORS. | | | 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE | | | PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS. | | | WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING | | | USED. | | | 7) THE LOCATION OF THE GENERATOR EXHAUST EXHAUST SHALL | | | COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL OR | | | IF NOT SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET | | | FROM ANY BUILDING OPENINGS. | | | | | | NOTE: FOR FUTURE GAS SUBMITTALS, ENSURE THERE ARE TWO | | | COPIES OF EACH PAGE OF THE SPECIFICATIONS IN THE | | | SUBMITTAL AND DIVIDED INTO TWO SEPARATE PACKETS. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-09 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-03 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2018-10-05 09:26:02 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-26 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-19 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2018-09-20 11:23:42 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-19 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-05 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2018-07-06 13:54:15 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-11 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-11 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|