Plan Review Details - Permit 18070202
Plan Review Stops For Permit 18070202
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 16:48 Rev Time 0.00
Received By jleahy Date 2018-10-09 Time 16:48 Sent To  
Notes
2018-10-09 16:49:32SIGNED SEALED GENERATOR PAD PLAN TO BE SUBMITTED PRIOR
 TO THE FINAL ELECTRICAL INSPECTION JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 06:40 Rev Time 0.00
Received By rmcdouga Date 2018-09-26 Time 06:39 Sent To I
Notes
2018-09-26 06:41:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING (COMMENTS FROM 1ST REVIEW WERE NOT
 ADDRESSED)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. FAC
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLAS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED
 IN ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2018-07-19 Time 15:39 Sent To I
Notes
2018-07-19 15:44:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE. FAC
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLAS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED
 IN ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 16:46 Rev Time 0.00
Received By jleahy Date 2018-10-09 Time 16:46 Sent To  
Notes
2018-10-09 16:48:17GAS PERMIT 18070203 HAS BEEN SEPARATED FROM THIS PERMIT
 SO THEY CAN DO THE SERVICE CHANGE
  
 GAS PERMIT IS NOW A STAND ALONE PERMIT.
  
 SIGNED SEALED GENERATOR PAD PLAN TO BE SUBMITTED PRIOR
 TO THE FINAL ELECTRICAL INSPECTION.. JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-21 Cont ID  
Sent By fgiaquin Date 2018-09-21 Time 06:34 Rev Time 0.00
Received By fgiaquin Date 2018-09-21 Time 06:30 Sent To G
Notes
2018-09-21 06:33:58SAME VIOLATIONS AS PREVIOUS REVIEW:
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 2. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1
  
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS NOT A "SIZING REPORT". NEC 220; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By fgiaquin Date 2018-07-17 Time 05:57 Rev Time 0.00
Received By fgiaquin Date 2018-07-17 Time 05:42 Sent To G
Notes
2018-07-17 05:57:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 2. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 16:49 Rev Time 0.00
Received By jleahy Date 2018-10-09 Time 16:49 Sent To  
Notes
2018-10-09 16:50:32GAS PERMIT 18070203 HAS BEEN SEPARATED FROM THIS PERMIT
 SO THE SERVICE CHANGE COULD BE DONE JLEAHY.....

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-09-21 Cont ID  
Sent By lcrespo Date 2018-09-21 Time 17:38 Rev Time 0.00
Received By lcrespo Date 2018-09-21 Time 17:38 Sent To  
Notes
2018-09-21 17:40:0409/21/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SECOND REQUEST, THE CITY RECORDS SHOW AN
 EXISTING GAS SYSTEM FOR THIS ADDRESS. THE EXISTING GAS
 DRAWING ON RECORD SHOWS A DEVELOPED LENGTH OF 60 FEET
 TO THE FARTHEST GAS OUTLET. THE SUBMITTED GAS PLAN
 SHOWS 15 FEET AS THE FARTHEST DISTANCE, PLEASE CLARIFY.
 SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP
 REGULATORS TO THE FARTHEST OUTLET. THIS DISTANCE SHALL
 BE USED IN THE SIZING OF THE LOW-PRESSURE SYSTEM.
  
 2. THE SECOND REQUEST, SUBMIT PAGES 40 & 41 OF THE GAS
 REGULATOR SPECS. THESE ARE THE INSTALLATION
 INSTRUCTIONS FOR THE REGULATORS.
  
 3. THE SECOND REQUEST, THERE ARE TWO DIFFERENT SIZING
 TABLES FOR THE PE PIPE: ONE FROM NFPA 54 AND ONE FROM
 2017 FBC-FUEL GAS. WHICH ONE IS BEING USED? REMOVE THE
 TABLE NOT BEING USED.
  
 4. THE SECOND REQUEST, THE LOCATION OF THE GENERATOR
 EXHAUST SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR IF NOT SPECIFIED IN THE MANUAL,
 A MINIMUM OF 10 FEET FROM ANY BUILDING OPENINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By tklarge Date 2018-07-19 Time 13:33 Rev Time 0.00
Received By tklarge Date 2018-07-19 Time 10:14 Sent To  
Notes
2018-07-19 13:21:18 
 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS
 ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A
 DEVELOPED LENGTH OF 60 FEET TO THE FARTHEST GAS OUTLET.
 THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE FARTHEST
 DISTANCE. CLARIFY.
 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE
 EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS
 SHOWN AS 407,000 BTU'S.
 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE
 ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2
 PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW
 THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE
 FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE
 SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM.
 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP
 REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE
 USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM.
 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS.
 THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE
 REGULATORS.
 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE
 PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS.
 WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING
 USED.
 7) THE LOCATION OF THE GENERATOR EXHAUST EXHAUST SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL OR
 IF NOT SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET
 FROM ANY BUILDING OPENINGS.
  
 NOTE: FOR FUTURE GAS SUBMITTALS, ENSURE THERE ARE TWO
 COPIES OF EACH PAGE OF THE SPECIFICATIONS IN THE
 SUBMITTAL AND DIVIDED INTO TWO SEPARATE PACKETS. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-09 Cont ID  
Sent By jleahy Date 2018-10-09 Time 16:50 Rev Time 0.00
Received By jleahy Date 2018-10-03 Time 09:25 Sent To  
Notes
2018-10-05 09:26:02RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 06:42 Rev Time 0.00
Received By rmcdouga Date 2018-09-19 Time 11:23 Sent To  
Notes
2018-09-20 11:23:42RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2018-07-05 Time 13:51 Sent To  
Notes
2018-07-06 13:54:15ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By mcruz Date 2018-07-11 Time 14:42 Rev Time 0.00
Received By mcruz Date 2018-07-11 Time 14:41 Sent To  
Notes
***NONE***