Plan Review Details - Permit 18070188
Plan Review Stops For Permit 18070188
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-08-14 Cont ID  
Sent By RRossano Date 2018-08-14 Time   Rev Time 1.00
Received By rrossano Date 2018-08-13 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By mgonzale Date 2018-07-20 Time   Rev Time 1.00
Received By mgonzale Date 2018-07-20 Time   Sent To I
Notes
2018-07-20 17:25:05NO COMMENTS - ADDRESS FIRE DEPARTMENT COMMENTS.
  
 MANNY GONZALEZ
 PROJECT COORDINATOR
 (561) 494-1085

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-08-10 Time 00:00 Rev Time 0.00
Received By bwoods Date 2018-08-10 Time 00:00 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By bwoods Date 2018-07-12 Time 00:00 Rev Time 0.00
Received By bwoods Date 2018-07-12 Time 00:00 Sent To M
Notes
2018-07-12 14:00:531. NEED MORE DEFINED PLANS SPECIFED FROM POINT OF
 SERVICE OF PLANS FOR THAT PERMIT
 2. DETAIL DRAWINGS OF HYDRANTS AND PIVS
 3. DETAIL OF ADDRESS OF BUILDING TO MATCH PERMIT
 4. NEEDS MANUFACTURAL SPECIFICATIONS ON PIPING AND
 FITTINGS
 5. PROVIDE CONTRACTOR LICENSE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-14 Cont ID  
Sent By cpuell Date 2018-08-14 Time 15:46 Rev Time 0.00
Received By cpuell Date 2018-07-26 Time 11:21 Sent To  
Notes
2018-07-27 11:21:26RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-23 Cont ID  
Sent By cpuell Date 2018-07-23 Time 11:09 Rev Time 0.00
Received By cpuell Date 2018-07-05 Time 14:23 Sent To  
Notes
2018-07-06 14:23:54ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-13 Cont ID  
Sent By ccole Date 2018-08-13 Time 09:37 Rev Time 0.00
Received By ccole Date 2018-08-13 Time 09:37 Sent To ENG
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By ccole Date 2018-07-19 Time 11:05 Rev Time 0.00
Received By ccole Date 2018-07-19 Time 11:05 Sent To ENG
Notes
2018-07-19 11:05:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070188
 7/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A PLAN THAT HAS THE ADDRESS OF THE
 BUILDING, AND SITE SPECIFIC DETAILS FOR INSTALLATION OF
 THE FIRE LINE.
  
 2) PROVIDE A SUBMITTAL PACKAGE FOR THE FIRE LINE
 MATERIALS THAT INCLUDES, BUT IS NOT LIMITED TO,
 MANUFACTURER'S SPECIFICATIONS FOR THE UNDERGROUND
 PIPING, PIPE FITTINGS, AND JOINT RESTRAINT SYSTEMS
 INCLUDING MATERIAL DATA SHEETS INDICATING TORGUE WRENCH
 SETTINGS,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  