Plan Review Details - Permit 18070150
Plan Review Stops For Permit 18070150
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 15:48 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 15:48 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 16:01 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 16:01 Sent To  
Notes
2018-07-30 16:00:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN REVIEW STAFF WAS ADVISED THAT THIS WAS A
 MULTI-MILLION DOLLAR JOB. VALUE FOR WORK STATED ON
 PERMIT APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. DETAIL HOW THIS COST WILL BE SPLIT
 BETWEEN THE RESPECTIVE PERMITS. FBC 109.3
 2. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET G1.02
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By pleduc Date 2019-01-22 Time   Rev Time 0.00
Received By pleduc Date 2019-01-22 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By pleduc Date 2018-08-07 Time   Rev Time 0.00
Received By pleduc Date 2018-07-06 Time 14:23 Sent To I
Notes
2018-08-07 12:50:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 1 02 - THERE IS A NOTE BOX INDICATING THE
 WORK IS ON THE 4TH FL COMMAND CENTER.
  
 FOR CLARIFICATION PURPOSES PLEASE INDICATE WHY THE ONLY
 THE COMMAND CENTER IS INCLUDED.
  
  
  
 2) SHEET G 1 02 - THERE IS AN INDICATION IN A NOTE BOX
 THAT THE WORK ON THE 4TH FL COMMAND CENTER SHALL COMPLY
 WITH THE 5TH ED OF THE FFPC.
  
 THE CURRENT ED OF THE FFPC IS THE 6TH.
  
 PLEASE REVIEW AND CORECT OR JUSTIFY WHY THE 5TH ED IS
 INDICATED AND ALOS WHY THE NOT THE ENTIRE PROJECT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-28 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-08 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-07 Cont ID  
Sent By cpuell Date 2018-08-07 Time 13:33 Rev Time 0.00
Received By cpuell Date 2018-07-05 Time 16:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By ccole Date 2019-01-28 Time 13:27 Rev Time 0.00
Received By ccole Date 2019-01-28 Time 13:27 Sent To  
Notes
2019-01-28 13:28:07MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 09:30 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 09:30 Sent To  
Notes
2018-07-26 10:02:53MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  
 CCOLE- 7/25/2018
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 15:43 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 15:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 16:01 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 16:01 Sent To  
Notes
2018-07-30 16:01:38ALL SIGNATURES WITH THIS SUBMISSION HAVE BEEN
 CONFIRMED, ANY NEW SHEETS SUBMITTTED WILL NEED TO BE
 CHECKED.