| 2018-07-19 13:52:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET G 3 02 - THERE IS AN INDICATION OF COMPLIANCE |
| | WITH THE 5TH EDITION FOR THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | THE CURRENT EDITION IS THE 6TH EDITION. |
| | |
| | PLEASE REVIEW, CORRECT, OR JUSTIFY AND ENSURE |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 2) SGEET G 3 02 - THE IS A REFERENCEUNDER THE LIFE |
| | SAFETY TABULAR BOX INDICATING WORK ON THE 4TH FLOOR |
| | COMMAND CENTER. |
| | |
| | THIS PLAN DOES NOT APPEAR TO ADDRESS THAT AREA AND IS |
| | CONFUSING. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 3) SHEET FA 1 01 - UNDER THE GENRAL SECTION THERE IS A |
| | REFERNCE TO THE 2011 EDITION OF THE NEC. |
| | |
| | THE CURRENT EDITION OF THE NFPA 70?, NATIONAL |
| | ELECTRICAL CODE?, 2014 EDITION. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 4) FA 1 02 - UNDER PHASE VI THERE IS AN INDICATION OF |
| | APPLYING FIRE CAULK PER THE MANUFACTURES REQUIREMENTS. |
| | THIS IS AGENRAL STATEMENT THAT MAY NOT BE APPLICABLE. |
| | |
| | LIST FIRE RATED ASSEMBLIES SHALL BE SUBMITTED FOR |
| | REVIEW AND APPROVAL. |
| | |
| | PROVIDE DETAILS OF LISTED FIRE RATED ASSEMBLIES FOR THE |
| | OPENINGS OR PROVIDE AN APPLICABLE NOTE TO PROVIDE |
| | LISTED ASSEMBLIES FOR REVIEW AND APPROVAL PRIOR TO ANY |
| | INSPECTION. |
| | |
| | |
| | |
| | 5) SHEET FA 2 01 - STAFF BREAKROOM A1A19, DOES NOT |
| | INDICATE A NOTIFICATION DEVICE. |
| | |
| | SHOULD THE EXISTING CONDITION NOT HAVE A DEVICE, ONE IS |
| | REQUIRED IN THE SPACE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 6) SHEET FA 2 01 - WOMENS RESTROOM A1A10 & MENS |
| | RESTROOM A1A12, INDICATE ONLY 75CD WITH NO DEVICE |
| | |
| | PLEASE REVIEW AND INDICATE WHAT DEVICE IS LOCATED IN |
| | THESE AREAS. |
| | |
| | |
| | |
| | 7) ALL FA SHEETS - THERE ARE ADDRESSABLE INDICATORS ON |
| | ANY DEVICE ON ANY SHEET DRAWINGS. |
| | |
| | ALL DEVICES SHALL BE ADDRESSABLE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 8) FA 3 02 - THE FIRE ALARM RISER DOES NOT HAVE ANY |
| | ADDRESSABLE INDICATORS ON ANY DEVICE. |
| | |
| | ALL DEVICES SHALL BE ADDRESSABLE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |