Plan Review Details - Permit 18070149
Plan Review Stops For Permit 18070149
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 15:39 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 15:39 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 15:26 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 15:26 Sent To I
Notes
2018-07-30 15:24:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN REVIEW STAFF WAS ADVISED THAT THIS WAS A
 MULTI-MILLION DOLLAR JOB. VALUE FOR WORK STATED ON
 PERMIT APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. DETAIL HOW THIS COST WILL BE SPLIT
 BETWEEN THE RESPECTIVE PERMITS. FBC 109.3
 2. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET G3.02
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By pleduc Date 2019-01-22 Time   Rev Time 0.00
Received By pleduc Date 2019-01-22 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By pleduc Date 2018-07-19 Time   Rev Time 0.00
Received By pleduc Date 2018-07-06 Time 14:22 Sent To  
Notes
2018-07-19 13:52:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET G 3 02 - THERE IS AN INDICATION OF COMPLIANCE
 WITH THE 5TH EDITION FOR THE FLORIDA FIRE PREVENTION
 CODE.
  
 THE CURRENT EDITION IS THE 6TH EDITION.
  
 PLEASE REVIEW, CORRECT, OR JUSTIFY AND ENSURE
 COMPLIANCE.
  
  
  
 2) SGEET G 3 02 - THE IS A REFERENCEUNDER THE LIFE
 SAFETY TABULAR BOX INDICATING WORK ON THE 4TH FLOOR
 COMMAND CENTER.
  
 THIS PLAN DOES NOT APPEAR TO ADDRESS THAT AREA AND IS
 CONFUSING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 3) SHEET FA 1 01 - UNDER THE GENRAL SECTION THERE IS A
 REFERNCE TO THE 2011 EDITION OF THE NEC.
  
 THE CURRENT EDITION OF THE NFPA 70?, NATIONAL
 ELECTRICAL CODE?, 2014 EDITION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) FA 1 02 - UNDER PHASE VI THERE IS AN INDICATION OF
 APPLYING FIRE CAULK PER THE MANUFACTURES REQUIREMENTS.
 THIS IS AGENRAL STATEMENT THAT MAY NOT BE APPLICABLE.
  
 LIST FIRE RATED ASSEMBLIES SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL.
  
 PROVIDE DETAILS OF LISTED FIRE RATED ASSEMBLIES FOR THE
 OPENINGS OR PROVIDE AN APPLICABLE NOTE TO PROVIDE
 LISTED ASSEMBLIES FOR REVIEW AND APPROVAL PRIOR TO ANY
 INSPECTION.
  
  
  
 5) SHEET FA 2 01 - STAFF BREAKROOM A1A19, DOES NOT
 INDICATE A NOTIFICATION DEVICE.
  
 SHOULD THE EXISTING CONDITION NOT HAVE A DEVICE, ONE IS
 REQUIRED IN THE SPACE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 6) SHEET FA 2 01 - WOMENS RESTROOM A1A10 & MENS
 RESTROOM A1A12, INDICATE ONLY 75CD WITH NO DEVICE
  
 PLEASE REVIEW AND INDICATE WHAT DEVICE IS LOCATED IN
 THESE AREAS.
  
  
  
 7) ALL FA SHEETS - THERE ARE ADDRESSABLE INDICATORS ON
 ANY DEVICE ON ANY SHEET DRAWINGS.
  
 ALL DEVICES SHALL BE ADDRESSABLE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 8) FA 3 02 - THE FIRE ALARM RISER DOES NOT HAVE ANY
 ADDRESSABLE INDICATORS ON ANY DEVICE.
  
 ALL DEVICES SHALL BE ADDRESSABLE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-08 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-05 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By ccole Date 2019-01-28 Time 13:21 Rev Time 0.00
Received By ccole Date 2019-01-28 Time 13:21 Sent To  
Notes
2019-01-28 13:21:52 
 MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 10:47 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 10:47 Sent To  
Notes
2018-07-26 10:49:30 
 MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  
  
 CCOLE- 7/25/2018

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 14:59 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 14:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 15:26 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 15:25 Sent To  
Notes
2018-07-30 15:26:33ALL SIGNATURES WITH THIS SUBMISSION HAVE BEEN
 CONFIRMED, ANY NEW SHEETS SUBMITTTED WILL NEED TO BE
 CHECKED.