| Plan Review Stops For Permit 18070148 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-24 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-24 |
Time |
15:52 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-30 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-30 |
Time |
14:38 |
Sent To |
I |
|
| Notes |
| 2018-07-30 14:47:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. AS THIS PLAN IS A SUBMISSION FOR THE FIRE ALARM | | | SYSTEM, THE PLAN SUBMITTED SHOULD CONTAIN JUST THE FIRE | | | ALARM SYSTEM AND ANY ELECTRICAL TO FEED THAT SYSTEM. | | | REMOVE ALL LIGHTING, POWER, AND LOW VOLTAGE SYSTEMS NOT | | | PART OF FIRE ALARM INSTALLATION. WPB FBC 107.2.1 | | | 2. PLAN REVIEW STAFF WAS ADVISED THAT THIS WAS A | | | MULTI-MILLION DOLLAR JOB. VALUE FOR WORK STATED ON | | | PERMIT APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED | | | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL | | | MATERIALS AND LABOR. DETAIL HOW THIS COST WILL BE SPLIT | | | BETWEEN THE RESPECTIVE PERMITS. FBC 109.3 | | | 3. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET G2.01 | | | IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC | | | PREFACE (ALSO SEE CURRENT CODES ABOVE) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-01-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-01-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-01-22 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-07-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-06 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2018-07-18 15:44:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET GEN 2.1 - THERE IS AN INDICATION IN THE DATA | | | TABULAR BOX OF FFPC 5TH EDITION. | | | | | | THE CURENT EDITION OF THE FFPC IS THE 6TH EDITION. | | | | | | PLEASE CORRECT AND ENSURE COMPLIANCE AND/OR JUSTIFY | | | WITH SPECIFIC DETAIL. | | | | | | | | | | | | 2) SHEET LS 100 - THE CORRIDOR/SPACE BETWEEN THE PUBLIC | | | LOBBY AND ELEVATOR LOBBY IS INDICATED AS BEING | | | NARROWED; HOWEVER, THERE ARE NO DIMENSIONS INDICATED. | | | | | | WHAT IS THE REQUIRED DIMENSION FOR THE EXIT PATHWAY AND | | | PROVIDE THAT DIMENSION TO THIS AREA. | | | | | | | | | | | | | | | 3) SHEET FP 1.04.1 - STATEMENT # 3 INDICATES STATE FIRE | | | MARSHAL APPROVAL PRIOR TO ANY INSTALLATION. | | | | | | IS THIS A STRICT CONDITION TO BE BE ENFORCED? | | | | | | HAS APPROVAL BEEN GRANTED? PROVIDE APPLICABLE DETAILS. | | | | | | | | | | | | | | | 4) SHEET FP 1.04.1 - PROVIDE A NOTE INDICATING THAT THE | | | FIRE SPRINKLER SHALL REMAIN FULLY OPERATIONAL DURING | | | ALL CONSTRUCTION. | | | | | | | | | | | | | | | 5) SHEET FAC 1.04.1 - PROVIDE A NOTE INDICATING THAT | | | THE FIRE ALARM SHALL REMAIN FULLY OPERATIONAL DURING | | | ALL CONSTRUCTION. | | | | | | | | | | | | | | | 6) SHEET FAC 1.01 - THERE IS AN INDICATION IN THE | | | GENERAL SECTION OF NOTE # 1 STATING COMPLIANCE WITH NEC | | | 2011. | | | | | | PER THE FLORIDA FIRE PREVENTION CODE 6TH EDITION, | | | COMPLIANCE SHALL BE WITH NFPA 70?, NATIONAL ELECTRICAL | | | CODE?, 2014 EDITION. | | | | | | PLEASE CORRECT OR JUSTIFY. | | | | | | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-01-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-08 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-07-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-07-05 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-28 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-28 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2019-01-28 12:55:59 | MECHANICAL PROVISOS: | | | | | | A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL | | | PERMIT. | | | | | | B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION | | | SYSTEMS CONTROL. | | | | | | 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A. | | | | | | 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED: | | | | | | A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE | | | A CAPACITY GREATER THAN 2000 CFMS. | | | | | | B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS | | | SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY | | | GREATER THAN 2000 CFMS. | | | | | | C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES | | | THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS, | | | AT EACH STORY. | | | | | | D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL | | | LISTING AND MANUFACTURER'S SPECIFICATIONS. | | | | | | CCOLE- 7/25/2018 | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-26 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-26 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2018-07-26 11:07:41 | MECHANICAL PROVISOS: | | | | | | A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL | | | PERMIT. | | | | | | B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION | | | SYSTEMS CONTROL. | | | | | | 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A. | | | | | | 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED: | | | | | | A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE | | | A CAPACITY GREATER THAN 2000 CFMS. | | | | | | B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS | | | SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY | | | GREATER THAN 2000 CFMS. | | | | | | C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES | | | THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS, | | | AT EACH STORY. | | | | | | D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL | | | LISTING AND MANUFACTURER'S SPECIFICATIONS. | | | | | | CCOLE- 7/25/2018 | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-24 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-24 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-30 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-30 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2018-07-30 14:43:09 | ALL SIGNATURES WITH THIS SUBMISSION HAVE BEEN | | | CONFIRMED, ANY NEW SHEETS SUBMITTTED WILL NEED TO BE | | | CHECKED. |
|
|