Plan Review Details - Permit 18070148
Plan Review Stops For Permit 18070148
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 15:52 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 14:47 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 14:38 Sent To I
Notes
2018-07-30 14:47:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS THIS PLAN IS A SUBMISSION FOR THE FIRE ALARM
 SYSTEM, THE PLAN SUBMITTED SHOULD CONTAIN JUST THE FIRE
 ALARM SYSTEM AND ANY ELECTRICAL TO FEED THAT SYSTEM.
 REMOVE ALL LIGHTING, POWER, AND LOW VOLTAGE SYSTEMS NOT
 PART OF FIRE ALARM INSTALLATION. WPB FBC 107.2.1
 2. PLAN REVIEW STAFF WAS ADVISED THAT THIS WAS A
 MULTI-MILLION DOLLAR JOB. VALUE FOR WORK STATED ON
 PERMIT APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. DETAIL HOW THIS COST WILL BE SPLIT
 BETWEEN THE RESPECTIVE PERMITS. FBC 109.3
 3. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET G2.01
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By pleduc Date 2019-01-22 Time   Rev Time 0.00
Received By pleduc Date 2019-01-22 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-18 Cont ID  
Sent By pleduc Date 2018-07-18 Time   Rev Time 0.00
Received By pleduc Date 2018-07-06 Time 14:20 Sent To  
Notes
2018-07-18 15:44:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET GEN 2.1 - THERE IS AN INDICATION IN THE DATA
 TABULAR BOX OF FFPC 5TH EDITION.
  
 THE CURENT EDITION OF THE FFPC IS THE 6TH EDITION.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE AND/OR JUSTIFY
 WITH SPECIFIC DETAIL.
  
  
  
 2) SHEET LS 100 - THE CORRIDOR/SPACE BETWEEN THE PUBLIC
 LOBBY AND ELEVATOR LOBBY IS INDICATED AS BEING
 NARROWED; HOWEVER, THERE ARE NO DIMENSIONS INDICATED.
  
 WHAT IS THE REQUIRED DIMENSION FOR THE EXIT PATHWAY AND
 PROVIDE THAT DIMENSION TO THIS AREA.
  
  
  
  
 3) SHEET FP 1.04.1 - STATEMENT # 3 INDICATES STATE FIRE
 MARSHAL APPROVAL PRIOR TO ANY INSTALLATION.
  
 IS THIS A STRICT CONDITION TO BE BE ENFORCED?
  
 HAS APPROVAL BEEN GRANTED? PROVIDE APPLICABLE DETAILS.
  
  
  
  
 4) SHEET FP 1.04.1 - PROVIDE A NOTE INDICATING THAT THE
 FIRE SPRINKLER SHALL REMAIN FULLY OPERATIONAL DURING
 ALL CONSTRUCTION.
  
  
  
  
 5) SHEET FAC 1.04.1 - PROVIDE A NOTE INDICATING THAT
 THE FIRE ALARM SHALL REMAIN FULLY OPERATIONAL DURING
 ALL CONSTRUCTION.
  
  
  
  
 6) SHEET FAC 1.01 - THERE IS AN INDICATION IN THE
 GENERAL SECTION OF NOTE # 1 STATING COMPLIANCE WITH NEC
 2011.
  
 PER THE FLORIDA FIRE PREVENTION CODE 6TH EDITION,
 COMPLIANCE SHALL BE WITH NFPA 70?, NATIONAL ELECTRICAL
 CODE?, 2014 EDITION.
  
 PLEASE CORRECT OR JUSTIFY.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-28 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-08 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-05 Time 16:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By ccole Date 2019-01-28 Time 12:55 Rev Time 0.00
Received By ccole Date 2019-01-28 Time 12:18 Sent To  
Notes
2019-01-28 12:55:59MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  
 CCOLE- 7/25/2018
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 11:07 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 11:07 Sent To  
Notes
2018-07-26 11:07:41MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  
 CCOLE- 7/25/2018
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By jpearson Date 2019-01-24 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-01-24 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 14:42 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 14:42 Sent To  
Notes
2018-07-30 14:43:09ALL SIGNATURES WITH THIS SUBMISSION HAVE BEEN
 CONFIRMED, ANY NEW SHEETS SUBMITTTED WILL NEED TO BE
 CHECKED.