Plan Review Details - Permit 18070084
Plan Review Stops For Permit 18070084
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 11:26 Rev Time 0.00
Received By shill Date 2019-05-13 Time 11:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By shill Date 2019-05-02 Time 14:03 Rev Time 0.00
Received By shill Date 2019-05-02 Time 12:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 17:41 Rev Time 0.00
Received By shill Date 2018-12-08 Time 17:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:44 Rev Time 0.00
Received By shill Date 2018-09-22 Time 17:44 Sent To  
Notes
2018-09-22 17:50:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FLORIDA BUILDING CODE, BUILDING
  
 1. GOVERNING CODE FOR THIS PROJECT IS FBC 2010, REVISE
 S1 AND ANY OTHER AFFECTED PAGES.
  
 2. I WAS UNABLE TO FIND FAIR HOUSING INFORMATION (FBC
 ACCESSIBILITY, FAIR HOUSING). REVISE PLAN TO SPECIFY IF
 BATHROOMS ARE SPECIFICATION A OR B, AND REVISE PLAN TO
 SHOW CLEARANCE REQUIRED BETWEEN COUNTERTOP AND
 CABINETS/APPLIANCES (40" MINIMUM, SEE REQUIREMENT 7).
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By jpearson Date 2019-05-02 Time 10:15 Rev Time 0.00
Received By jpearson Date 2019-05-02 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-13 Cont ID  
Sent By jpearson Date 2018-11-13 Time 12:32 Rev Time 0.00
Received By jpearson Date 2018-11-13 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 08:18 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 08:17 Sent To  
Notes
2018-09-17 08:17:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 3. NOTE 3 INDICATES THERE ARE OUTLETS ON BUNK BED.
 PROVIDE SPEC SHEET TO CONFIRM LISTING. NEC 110.3
 4. NOTE 5 INDICATES A REGULAR RECEPTACLE OUTLET
 INSTALLED IN MEDICINE CABINET., AND NOTE 6 INDICATES
 RECEPTACLE OUTLETS INSIDE VANITY DRAWERS. ALL
 RECEPTACLE OUTLETS INSTALLED IN A BATHROOM REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 5. PLAN SHOWS LED LIGHTING WITHIN THE STORAGE SPACE OF
 THE CLOSET. PROVIDE LISTING OF PRODUCT TO CONFIRM IT IS
 LISTED FOR THIS USE. NEC 410.16, 110.3
 6. PROVIDE SPEC SHEET FOR TOWEL HEATER. NEC 110.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-09 Cont ID  
Sent By pleduc Date 2019-04-09 Time   Rev Time 0.00
Received By pleduc Date 2019-04-09 Time 09:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time   Rev Time 0.00
Received By pleduc Date 2018-10-24 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-07 Cont ID  
Sent By pleduc Date 2018-08-07 Time   Rev Time 0.00
Received By pleduc Date 2018-08-07 Time 13:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-04-04 Cont ID  
Sent By tklarge Date 2020-04-04 Time 10:15 Rev Time 0.00
Received By tklarge Date 2020-04-04 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:39 Rev Time 0.00
Received By shill Date 2019-05-15 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-05-06 Time   Rev Time 0.00
Received By cpuell Date 2019-04-08 Time 14:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-13 Cont ID  
Sent By gjohnson Date 2018-12-13 Time 13:34 Rev Time 0.00
Received By gjohnson Date 2018-10-22 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By gjohnson Date 2018-09-25 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2018-08-04 Time 13:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-06 Cont ID  
Sent By ccole Date 2019-05-01 Time 08:24 Rev Time 0.00
Received By ccole Date 2019-05-01 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-21 Cont ID  
Sent By ccole Date 2018-11-21 Time 10:51 Rev Time 0.00
Received By ccole Date 2018-11-21 Time 09:05 Sent To  
Notes
2018-11-21 11:24:572ND REVIEW FBC-2010 FLORIDA BUILDING CODES- MECHANICAL
 PERMIT #18070084
 11/21/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION CODE
 FBC FG- FLORIDA FUEL GAS CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO COMMENT #4 FROM THE 1ST REVIEW AND COMPLY-
 4) M-1.0: SMOKE DETECTORS ARE REQUIRED IN BOTH THE
 SUPPLY AND RETURN AIR SYSTEMS OF THE HEAT PUMPS IN
 ACCORDANCE WITH SECTION 606.2.2 FBC M. SMOKE DETECTORS
 MISSING FOR THE HP-C SYSTEM
  
 2) SHEET M-1.0: PLEASE LABEL THE DRYER EXHAUST CHASE
 AND CLARIFY WHY THERE ARE TWO DRYER EXHAUST DUCTS
 CONNECTING TO IT. THERE WERE SPECS FOR AN ELECTRIC AND
 A GAS DRYER SUBMITTED WITH THE CORRECTED PLANS. IF
 USING BOTH DRYERS PLEASE NOTE THAT ON THE PLAN AND
 PROVIDE COMBUSTION AIR CALCULATIIONS FOR THE GAS DRYER-
 SECTION 304 FBC-10 FUEL GAS.
  
 3) M-1.0: PROVIDE CONSTRUCTION DETAILS FOR THE PLENUM
 RATED CHASES- SEE KEYNOTES #5 & 6.
  
 4) REFER TO COMMENT #5 FROM THE 1ST REVIEW AND COMPLY-
 5) SUBMIT CUT SHEETS AND PROVIDE EQUIPMENT SCHEDULES ON
 THE PLANS FOR THE KITCHEN COOKING APPLIANCES- SECTION
 623 FBC FG,.
  
 5) REFER TO COMMENT #10 FROM THE 1ST REVIEW AND COMPLY-
 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 MINI-SPLIT AIR HANDLER AT THE BAR- SECTION 307 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By ccole Date 2018-09-17 Time 13:53 Rev Time 0.00
Received By ccole Date 2018-09-17 Time 12:18 Sent To  
Notes
2018-09-17 14:02:311ST REVIEW FBC-2010 FLORIDA BUILDING CODES- MECHANICAL
 PERMIT #18070084
 9/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION CODE
 FBC FG- FLORIDA FUEL GAS CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMCHECK COMPLIANCE CERTIFICATE LISTS COOLING
 AND HEATING CAPACITIES AND EFFICENCY RATINGS FOR THE AC
 SYSTEMS THAT DO NOT MATCH THE DATA SHOWN IN THE AC
 EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB. PLEASE NOTE
 THE PLANS ARE BEING REVIEWED UNDER THE 2010 CODES,
 HOWEVER THE COMCHECK SUBMITTAL IS THE 2017 VERSION.
  
 2) SUBMIT AC CALCULATIONS FOR THE NEW MINI SPLIT
 SYSTEM- 503.2.1 FBC- EC., AND PROVIDE COMPLIANCE DATA
 FOR THE SYSTEM IN THE REVISED COMCHECK CERTIFICATE.
  
 3) SHEET M-1.0: VERIFY THAT THE DRYER AND KITCHEN
 EXHAUST DUCTS ARE NOT RUNNING THROUGH THE ABOVE-
 CEILING PLENUM- SECTIONS 504.4 & 601.5 FBC M.
  
 4) M-1.0: SMOKE DETECTORS ARE REQUIRED IN BOTH THE
 SUPPLY AND RETURN AIR SYSTEMS OF THE HEAT PUMPS IN
 ACCORDANCE WITH SECTION 606.2.2 FBC M.
  
 5) SUBMIT CUT SHEETS AND PROVIDE EQUIPMENT SCHEDULES ON
 THE PLANS FOR THE KITCHEN COOKING APPLIANCES- SECTION
 623 FBC FG,.
  
 6) SUBMIT CUT SHEETS FOR THE KITCHEN EXHAUST HOOD AND
 EXHAUST DUCT. INDICATE HOW MAKEUP AIR IS BEING PROVIDED
 FOR THE EXHAUST AND PROVIDE EXHAUST AND AIR BALANCE
 CALCULATIONS- SECTIONS 505, 506, 507, & 508 FBC M.
 PLEASE NOTE THAT A FIRE SUPPRESSION SYSTEM MAY BE
 REQUIRED PER SECTION 509.1 FBC M.
  
 7) SUBMIT CUT SHEETS FOR THE DRYERS AND INDICATE HOW
 MAKE UP AIR IS BEING PROVIDED- SECTION 504.5 FBC M.
  
 8) M-1.0 & M-2.10: PROVIDE A DETAIL SHOWING HOW THE
 FIRE DAMPERS WILL BE INSTALLED IN THE DUCTS CONNECTING
 TO THE RISERS. PLEASE SUBMIT SPECS FOR THE DAMPERS WITH
 AN APPROVAL STAMP BY THE EOR.
  
 9) M-1.0: THE TOILET EXHAUST RISER BY POWDER RM 118 IS
 MISLABELED AS KER-2.
  
 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 MINI-SPLIT AIR HANDLER AT THE BAR- SECTION 307 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 09:44 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-13 Cont ID  
Sent By gjohnson Date 2018-12-13 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2018-12-13 Time 13:33 Sent To  
Notes
2018-12-13 13:33:102ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS PLEASE
 PROVIDE DETAILS WITH HEIGHT AND LOCATION DIMENSIONS.
 PER FHA REQUIREMENT #6
  
 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR THE KEMPER SYSTEM USED IN THE SHOWER PANS.
 PER WPB AMEND TO FBC 107.2.1
  
 3. FLOOR DRAINS AND OR HUB DRAINS SHALL BE INSTALLED
 ACCESSIBLE LOCATION THE WALL CHASE THAT IT IS SHOWN IN
 IS A CODE VIOLATION. PER FBC PL 412.2
  
 4. THE STEAM GENERATOR SHALL BE INSTALLED ACCESSIBLE
 LOCATION THE WALL CHASE THAT IT IS SHOWN IN IS A CODE
 VIOLATION. PER FBC PL 502.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By gjohnson Date 2018-09-25 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2018-09-25 Time 16:11 Sent To  
Notes
2018-09-25 16:11:511ST REVIEW:
 FBC PLUMBING 2010
  
 PLUMBING COMMENTS:
  
 1. SEE BUILDINGS COMMENTS. SHOW COMPLIANCE WITH FHA
  
 2. PROVIDE SANITARY ISOMETRIC FOR BATHROOM #1, POWDER
 ROOM AND KITCHEN. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 3. THE STAND ALONE TUB VALVE ON THE MASTER TUB SHALL
 HAVE A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS
 TO ASSE 1070 OR CSA B125.3 PER FBC PL 424.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:39 Rev Time 0.00
Received By shill Date 2019-05-16 Time 07:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 11:27 Rev Time 0.00
Received By shill Date 2019-05-13 Time 11:27 Sent To  
Notes
2019-05-13 11:28:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE COMMENT FROM PREVIOUS REVIEWS:
  
 1. THE LOAD CALCS ARE NOT DIGITALLY SIGNED; IT APPEARS
 TO BE A DIGITALLY SIGNED DOCUMENT WHICH WAS PRINTED AND
 SCANNED. PROVIDE THE ORIGINAL, FS471.
  
 2. STRUCTURAL PAGE RECEIVED VIA EMAIL AND IS OK
 (PROVISO FOR FUTURE PLANS TO INCLUDE SEAL IMAGE AND
 LANGUAGE REQUIRED BY FAC61G15-23.004).
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-05-02 Cont ID  
Sent By shill Date 2019-05-02 Time 14:23 Rev Time 0.00
Received By shill Date 2019-05-02 Time 14:03 Sent To  
Notes
2019-05-02 14:16:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE COMMENT FROM FIRST REVIEW:
  
 1. THE LOAD CALCS ARE NOT DIGITALLY SIGNED; IT APPEARS
 TO BE A DIGITALLY SIGNED DOCUMENT WHICH WAS PRINTED AND
 SCANNED. PROVIDE THE ORIGINAL, FS471.
  
 2. PLAN PAGES CHECKED ARE OK WITH THE EXCEPTION OF 030
 S_1; THE ENGINEER'S PAGE LACKS A SEAL AND THE LANGUAGE
 REQUIRED BY FAC61G15-23.004. TITLE BLOCK FOR THE
 ENGINEER IS NOT CLEAR; IF ENGINEER IS PRACTICING
 ENGINEERING THROUGH C.A.D. INTERNATIONAL, THE
 CERTIFICATE OF AUTHORIZATION SHOULD BE INCLUDED IN THE
 TITLE BLOCK.
  
 TO RESOLVE:
  
 IF MECHANICAL PASSES REVIEW, PLEASE SEND THE LOAD CALCS
 DIGITALLY SIGNED TO ME VIA EMAIL. IF MECHANICAL DOES
 NOT PASS, PLEASE UPLOAD THE DIGITALLY SIGNED DOCUMENTS.
  
 FOR THE STRUCTURAL PAGE (MASOOD HAJALI), PLEASE HAVE
 HIM CONTACT ME TO CLARIFY. I HAVE ALSO CONTACTED HIM
 DIRECTLY VIA EMAIL.
  
  
  
  
  
2019-05-02 10:15:08ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-11-13 Cont ID  
Sent By jpearson Date 2018-11-13 Time 10:52 Rev Time 0.00
Received By jpearson Date 2018-11-13 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 17:36 Rev Time 0.00
Received By shill Date 2018-09-22 Time 17:36 Sent To  
Notes
2018-09-22 17:39:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN PAGES ARE OK, BUT NEW PAGES SUBMITTED 2ND
 REVIEW CYCLE REQUIRE VERIFICATION.
  
 2. THE LOAD CALCS ARE NOT DIGITALLY SIGNED; IT APPEARS
 TO BE A DIGITALLY SIGNED DOCUMENT WHICH WAS PRINTED AND
 SCANNED. PROVIDE THE ORIGINAL, FS471.
  
  
  