Plan Review Details - Permit 18070063
Plan Review Stops For Permit 18070063
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By jgomez Date 2018-07-31 Time 14:46 Rev Time 0.00
Received By jgomez Date 2018-07-31 Time 11:37 Sent To  
Notes
2018-07-31 13:05:14 
 ****PROVISOS REMAINDER:
  
  
 REVISION #18040403 PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE BEAD BOARD SOFFIT SPECIFIED ON
 PLANS/SECTIONS.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL BUILDING REVIEW PROVISO:
 1- PROVIDE MANUFACTURER'S DETAILS & SPECS FOR FACTORY
 BUILT FIREPLACE & CLAY FLUE SPECIFIED ON FLOOR PLANS
 AND SHEET A.13. SHOW COMPLIANCE WITH UL 127.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 07:42 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 07:42 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 16:45 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 14:49 Sent To  
Notes
2018-07-26 15:21:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR HER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 12:37 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 12:37 Sent To  
Notes
2018-08-15 12:38:11GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-16 Time 15:36 Sent To  
Notes
2018-08-17 15:36:46RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 13:48 Rev Time 0.00
Received By lcrespo Date 2018-07-02 Time 15:11 Sent To  
Notes
2018-08-15 08:22:348/15 TO LC DESK
  
2018-07-03 15:11:26R03

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-15 Cont ID  
Sent By tklarge Date 2018-08-15 Time 13:46 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 13:46 Sent To  
Notes
2018-08-15 13:49:3508/15/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2018-07-06 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-06 Time 14:47 Sent To  
Notes
2018-07-26 14:57:10PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]