Plan Review Details - Permit 18070030
Plan Review Stops For Permit 18070030
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-03-28 Cont ID  
Sent By pvalenti Date 2019-03-28 Time 16:15 Rev Time 0.00
Received By pvalenti Date 2019-03-28 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-27 Cont ID  
Sent By pvalenti Date 2019-03-27 Time 08:53 Rev Time 0.00
Received By pvalenti Date 2019-03-27 Time 08:53 Sent To  
Notes
2019-03-27 09:06:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISOS AS NOTED BELOW IN ITEMIZED LIST:
  
 1. APPROVED.
  
 2.A. APPROVED WITH PROVISO: REVISE PLANS TO CORRECT
 OCCUPANCY CAPACITY AS PER FBC B TABLE 1004.1.2. FOR 2ND
 LEVEL STORAGE ROOMS AND 1ST FLOOR ROOM. (NOTE: PLUMBING
 REVIEWER ACCEPTED NUMBER OF FIXTURES PER OCCUPANCY
 LOAD).
 C. APPROVED WITH PROVISO: PROVIDE LETTER STATING THAT
 ADJACENT BUILDING IS COMPLYING WITH REQUIREMENT FOR
 REMOVAL OF WINDOW. EXTERIOR STAIR AT WEST WALL NEEDS TO
 BE 10? FROM ADJACENT BUILDING WINDOW.
  
 3. THROUGH 6. APPROVED
  
 7. APPROVED WITH PROVISO: SEPARATE SPRINKLER PERMIT
 REQUIRED, LEVEL 2 APPEARS TO BE OK. LEVEL 1 EXCEEDS THE
 ALLOWABLE QUANTITY (120 GALLONS) OF 1B, SO THIS CHANGES
 FROM F1 TO H3.
  
 8. THROUGH 14. APPROVED
  
 15.(1) APPROVED WITH PROVISO: ARCHITECT NEEDS TO
 PROVIDE NEW DETAIL FOR COUNTER TOP IN ACCORDANCE WITH
 ACCESSIBILITY REQUIREMENTS. 1ST LEVEL CABINET BASE
 DETAIL SHOWS TOP OF COUNTER AT 34?. THIS SHOULD BE NO
 HIGHER THAN 30? AND NEEDS LEG ROOM FOR WHEEL CHAIR
 FRONT APPROACH.
 (2) THROUGH (4) APPROVED
  
 16. APPROVED WITH PROVISO: A CLARIFICATION OF VALUATION
 BREAK DOWN IS REQUIRED FROM CONTRACTOR.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-11-13 Cont ID  
Sent By rmcdouga Date 2018-11-13 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2018-11-08 Time 17:53 Sent To  
Notes
2018-11-13 10:13:433RD REVIEW FBC-2017 BUILDING
 PERMIT #18070030
 415 SOUTHERN BLVD.
 TYPE OF CONSTRUCTION: II B
 OCCUPANCY TYPE: F-1
 SPRINKLERED BLDG: NO
 LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF
 OCCUPANCY
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) PARTIALLY COMPLIED. SEE NEW COMMENTS REGARDING LIFE
 SAFETY PLANS.
 A) WHEN DETERMINING OCCUPANT LOADS PER FBC 1004.1, THE
 DECIMALS OF A NUMBER ARE TO BE ROUNDED UP TO THE NEXT
 HIGHER WHOLE NUMBER. NEW COMMENTS:THE OCCUPANT LOAD OF
 3.2 FOR THE SECOND FLOOR OFFICE #202 WILL BE 4
 OCCUPANTS, NOT 3. ON THE FIRST FLOOR THE 3.1 OCCUPANT
 LOAD OF ROOM #102 WILL BE 4 OCCUPANTS AND THE 3.27
 OCCUPANTS OF ROOM #1 WILL ALSO BE 4 OCCUPANTS.
 B) COMPLIES.
 C) THE EXTERIOR EXIT STAIR IS REQUIRED BY FBC 1027.5 TO
 HAVE A MINIMUM FIRE SEPARATION DISTANCE OF 10 FEET
 MEASURED AT RIGHT ANGLES FROM THE EXTERIOR EDGE OF THE
 STAIRWAY. THIS STAIRWAY DOES NOT HAVE 10 FEET TO THE
 PROPERTY LINE OR TO THE BUILDING ON THE ADJACENT LOT.
 NEW COMMENTS: THE BUILDING OFFICIAL HAS DETERMINED THAT
 THE EXTERIOR EXIT STAIR WILL BE ALLOWED TO REMAIN AS
 EXISTING, AS LONG AS, THE WALL OF THE ADJACENT BUILDING
 IS CMU AND THE 4 X 4 WINDOW IN THE WALL IS NOT WITHIN
 10 FEET OF THE EXIT STAIRS.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) ADDRESSED.
  
 6) COMPLIED.
  
 7) PARTIALLY COMPLIED. SPECIFY THE ITEMS AND QUANTITY
 OF THEM THAT WILL BE STORED ON THE SECOND FLOOR IN ROOM
 #204. NEW COMMENT: THE RESPONSE LETTER STATES THAT RUM
 WILL BE STORED WITHIN THE BUILDING ON LEVEL TWO AND/OR
 AS NEEDED ON LEVEL ONE. SINCE THERE WERE NO MSDS (
 MATERIAL SAFETY DATA SHEETS) SUBMITTED FOR THE RUM, I
 WAS ABLE TO OBTAIN SOME INFORMATION ON RUM FROM THE
 INTERNET. THE FLASH POINT FOR 80 % ETHANOL IS 20.0
 DEGREES CELCIUS (68 DEGREES F) AND THE BOILING POINT IS
 78.5 DEGREES CELCIUS (173.3 DEGREES F). THIS MAKES RUM
 A CLASS IB FLAMABLE LIQUID. BASED ON FBC TABLE 307.1(1)
 A MAXIMUM OF 120 GALLONS OF RUM CAN BE STORED PER
 CONTROL AREA ON SITE WITHOUT BEING CONSIDERED AN H-3
 OCCUPANCY. FOOTNOTE B FOR THIS TABLE STATES THAT THE
 AGGREGRATE QUANITY IN USE AND STORAGE SHALL NOT EXCEED
 THE QUANITY LISTED FOR STORAGE. FOOTNOTE C ALLOWS THE
 QUANTITY OF ALCOHOLIC BEVERAGES IN RETAIL AND WHOLESALE
 SALE OCCUPANCIES TO NOT BE LIMITED, PROVIDED THE
 LIQUIDS ARE PACKAGED IN INDIVIDUAL CONTAINERS NOT
 EXCEEDING 1.3 GALLONS. THE BUILDING OFFICIAL WILL ALLOW
 THE UNLIMITED STORAGE OF THE RUM IN INDIVIDUAL
 CONTAINERS NOT EXCEEDING 1.3 GALLONS. WHEN THE
 MATERIALS IN THE RUM PRODUCTION PROCESS REACH THE POINT
 IT BECOMES A FLAMABLE LIQUID THEN NO MORE THAN 120
 GALLONS PER CONTROL AREA IS ALLOWED WITHOUT BEING
 CONSIDERED A HAZARDOUS OCCUPANCY (H-3). FBC 307.1 THE
 RUM DISTILLERY PROCESS OUTLINE THAT WAS SUBMITTED DOES
 NOT STATE THE AMOUNT OF RUM ( CLASS IB FLAMABLE LIQUID)
 THAT WILL BE IN THE PROCESS. THE PLANS SHOW A 1000
 GALLON AND A 600 GALLON SPIRIT SAFE. SO IT WOULD APPEAR
 THAT THERE WILL BE AT LEAST 1600 GALLONS OF RUM IN THE
 SPIRT SAFES. THIS EXCEEDS THE 120 GALLONS ALLOWED BY
 FBC TABLE 307.1(1) AND WILL REQUIRE THIS AREA TO BE H-3
 RATHER THAN F-1. PLEASE ADVISE AS TO HOW THIS WILL BE
 ADDRESSED.
  
 8) ADDRESSED.
  
 9) COMPLIED.
  
 10) ADDRESSED.
  
 11) ADDRESSED.
  
 12) ADDRESSED.
  
 13) ADDRESSED.
  
 14) ADDRESSED.
  
 15) 2017 FBC- ACCESSIBILITY - ADA
 201.1 SCOPE.
 THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE
 SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO
 PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO
 RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2),
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL
 NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE
 BUILDINGS AND FACILITIES, PLACES OF PUBLIC
 ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS
 CODE SHALL COMPLY WITH THIS CODE.
 THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND
 NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM
 RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED
 BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR
 FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508,
 F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 BUILDINGS AND FACILITIES WHERE THE ORIGINAL
 CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS
 CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW.
  
 15-1) CLARIFY. THE LETTER FROM THE OWNER MENTIONS
 CUSTOMERS, WHICH WOULD BE THE PUBLIC. (IF ACCESS TO THE
 PRIVATE RECEPTION TASTING AREA IS ALLOWED FOR PERSONS
 OTHER THAN THE EMPLOYEES, THEN THE ADA REQUIREMENTS
 APPLY. THE FBC ACCESSIBILTY ALSO APPLIES TO PRIVATE
 BUILDINGS, CLUBS, ETC. IT APPEARS THAT YOUR DESIGN DOES
 COMPLY WITH THE EXCEPTION OF VERTICAL ACCESSIBILTY.)
 THE PLANS SHOW A RECEPTION/TASTING AREA THAT APPARENTLY
 WILL BE OPEN TO THE PUBLIC. SPECIFY WHICH AREAS WILL BE
 OPEN TO THE PUBLIC FOR TOURS, ETC. FBC 107.2.1
  
 15-2) NOT COMPLIANT. (THE RESPONSE TO THIS COMMENT
 STATES THAT THE SECOND FLOOR IS PRIMARILY STORAGE WITH
 ONE OFFICE WHICH HAS AN OCCUPANCY OF 3 PERSONS. THE
 PLANS STILL SHOW TWO OFFICES AND AN OCCUPANCY OF 4
 PERSONS IN EACH FOR A TOTAL OF 8. THE CALCULATED
 OCCUPANT LOAD FOR EACH SPACE IS REQUIRED TO BE ROUNDED
 UP THE NEXT HIGHER WHOLE NUMBER. THE MECHANICAL ROOM
 206 SHOULD NOT HAVE AN OCCUPANT LOAD. THE OCCUPANT LOAD
 FOR THE STORAGE AREA (3 PERSONS) DOES NOT COUNT TOWARD
 ACCESSIBILITY. 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE PITS AND PLATFORMS.
 (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES
 AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS.
 (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER
 LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SECTIONS 221 AND 802 ARE MET.
 (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF
 CHAPTER 10 ARE MET.
 (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9.
 (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION
 203.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
 ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE
 APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR
 WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS
 REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL
 CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE
 THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED
 TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE
 AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS,
 EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM
 THESE REQUIREMENTS AND MUST BE ACCESSIBLE.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 15-3) COMPLIED.
  
 15-4) PARTIAL COMPLIANCE. (BATHROOM MUST BE ON AN
 ACCESSIBLE ROUTE). NEW COMMENT: IF THE SECOND FLOOR IS
 REQUIRED TO HAVE VERTICAL ACCESSIBILITY, THEN THE
 BATHROOM ON THE SECOND LEVEL WILL HAVE TO COMPLY.
 WHERE TOILET FACILITIES AND BATHING FACILITIES ARE
 PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED IN
 FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT
 TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET
 FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON
 A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN
 ACCESSIBLE ENTRANCE.
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 16) PLEASE CLARIFY THE INTENT OF THE GENERAL
 CONTRACTOR'S PRICING THAT WAS SUBMITTED. IS THE
 $90,250.00 MEANT TO BE ADDED TO THE $320,000.00 PERMIT
 VALUE? THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW
 FOR THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By rmcdouga Date 2018-09-27 Time 19:34 Rev Time 0.00
Received By rmcdouga Date 2018-09-24 Time 08:24 Sent To  
Notes
2018-09-27 09:14:432ND REVIEW FBC-2017 BUILDING
 PERMIT #18070030
 415 SOUTHERN BLVD.
 TYPE OF CONSTRUCTION: II B
 OCCUPANCY TYPE: F-1
 SPRINKLERED BLDG: NO
 LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF
 OCCUPANCY
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED. SEE NEW COMMENTS REGARDING LIFE SAFETY
 PLANS.
 A) WHEN DETERMINING OCCUPANT LOADS PER FBC 1004.1, THE
 DECIMALS OF A NUMBER ARE TO BE ROUNDED UP TO THE NEXT
 HIGHER WHOLE NUMBER.
 B) SHOW THAT THE TWO EXIT ACCESS STAIRWAYS FROM THE
 SECOND FLOOR COMPLY WITH FBC1007.1 FOR THE REQUIRED
 SEPARATION DISTANCE OF ONE-HALF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 THEM.
 C) THE EXTERIOR EXIT STAIR IS REQUIRED BY FBC 1027.5 TO
 HAVE A MINIMUM FIRE SEPARATION DISTANCE OF 10 FEET
 MEASURED AT RIGHT ANGLES FROM THE EXTERIOR EDGE OF THE
 STAIRWAY. THIS STAIRWAY DOES NOT HAVE 10 FEET TO THE
 PROPERTY LINE OR TO THE BUILDING ON THE ADJACENT LOT.
  
 3) NOT COMPLIANT. (DESIGNER NEEDS TO REFERENCE 2017 FBC
 EXISTING BUILDING AND CHANGE OF OCCUPANCY ON THE
 PLANS.) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE
 ARCHITECT SHALL INDICATE THE CLASSIFICATION OF WORK AS
 OUTLINED IN CHAPTER 5 FBC EXISTING BUILDING. THIS
 APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN
 SECTION 202 FBC EX. PLEASE SEE SECTION 506 AND CHAPTER
 10 FOR ALL REQUIREMENTS.
  
 4) NOT COMPLIANT. (DESIGNER NEEDS TO SPECIFY ON THE
 PLANS THAT THIS BUILDING IS A NONSEPARATED MIXED USE
 OCCUPANCY, F-1, B AND S-1.) SEE FBC 508.3 THE BUILDING
 IS FUNCTIONING AS A MULTI-USE OCCUPANCY. INDICATE IF
 THE BUILDING IS DESIGNED FOR MIXED USE (NON-SEPARATED)
 OR SEPARATED USE PER SECTION 6.1.14.3 OF NFPA 101
 FLORIDA EDITION 2015. FOR NON-SEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING.
  
 5) ADDRESSED.
  
 6) COMPLIED.
  
 7) SEE FIRE COMMENTS. NEW COMMENT: SPECIFY THE ITEMS
 AND QUANTITY OF THEM THAT WILL BE STORED ON THE SECOND
 FLOOR IN ROOM #204. SPECIFY THE REQUIRED UNIFORMLY
 DISTRIBUTED LIVE LOAD FOR THIS STORAGE AREA AND THE
 EXISTING FLOOR LIVE LOAD FOR THIS AREA. FBC 1607.1
  
 8) ADDRESSED.
  
 9) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION
 DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER
 ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 10) ADDRESSED.
  
 11) ADDRESSED.
  
 12) ADDRESSED.
  
 13) ADDRESSED.
  
 14) ADDRESSED.
  
 15) 2017 FBC- ACCESSIBILITY - ADA
 201.1 SCOPE.
 THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE
 SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO
 PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO
 RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2),
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL
 NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE
 BUILDINGS AND FACILITIES, PLACES OF PUBLIC
 ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS
 CODE SHALL COMPLY WITH THIS CODE.
 THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND
 NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM
 RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED
 BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR
 FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508,
 F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 BUILDINGS AND FACILITIES WHERE THE ORIGINAL
 CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS
 CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW.
  
 15-1) CLARIFY. (IF ACCESS TO THE PRIVATE RECEPTION
 TASTING AREA IS ALLOWED FOR PERSONS OTHER THAN THE
 EMPLOYEES, THEN THE ADA REQUIREMENTS APPLY. THE FBC
 ACCESSIBILTY ALSO APPLIES TO PRIVATE BUILDINGS, CLUBS,
 ETC. IT APPEARS THAT YOUR DESIGN DOES COMPLY WITH THE
 EXCEPTION OF VERTICAL ACCESSIBILTY.) THE PLANS SHOW A
 RECEPTION/TASTING AREA THAT APPARENTLY WILL BE OPEN TO
 THE PUBLIC. SPECIFY WHICH AREAS WILL BE OPEN TO THE
 PUBLIC FOR TOURS, ETC. FBC 107.2.1
  
 15-2) NOT COMPLIANT. ( THE RESPONSE TO THIS COMMENT
 STATES THAT THE SECOND FLOOR IS PRIMARILY STORAGE WITH
 ONE OFFICE WHICH HAS AN OCCUPANCY OF 3 PERSONS. THE
 PLANS SHOW TWO OFFICES AND AN OCCUPANCY OF 4 PERSONS IN
 EACH FOR A TOTAL OF 8. THE CALCULATED OCCUPANT LOAD FOR
 EACH SPACE IS REQUIRED TO BE ROUNDED UP THE NEXT HIGHER
 WHOLE NUMBER. THE MECHANICAL ROOM 206 SHOULD NOT HAVE
 AN OCCUPANT LOAD.) THE OCCUPANT LOAD FOR THE STORAGE
 AREA (3 PERSONS) DOES NOT COUNT TOWARD ACCESSIBILITY. )
 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE PITS AND PLATFORMS.
 (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES
 AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS.
 (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER
 LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SECTIONS 221 AND 802 ARE MET.
 (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF
 CHAPTER 10 ARE MET.
 (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9.
 (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION
 203.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
 ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE
 APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR
 WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS
 REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL
 CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE
 THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED
 TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE
 AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS,
 EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM
 THESE REQUIREMENTS AND MUST BE ACCESSIBLE.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 15-3) NOT RESOLVED. PROVIDE AN ACCESSIBLE ROUTE TO AND
 THROUGH THE PUBLIC AREAS. FBC-A 206.1 GENERAL.
 ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH
 206 AND SHALL COMPLY WITH CHAPTER 4.
  
 15-4) PARTICAL COMPLIANCE. ( BATHROOM MUST BE ON AN
 ACCESSIBLE ROUTE.) PROVIDE AN ACCESSIBLE BATHROOM.
 FBC-A 213 TOILET FACILITIES AND BATHING FACILITIES
 213.1 GENERAL.
 WHERE TOILET FACILITIES AND BATHING FACILITIES ARE
 PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED IN
 FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT
 TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET
 FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON
 A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN
 ACCESSIBLE ENTRANCE.
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 16) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR
 THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By rmcdouga Date 2018-08-02 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2018-08-01 Time 13:12 Sent To  
Notes
2018-08-01 19:02:331ST REVIEW FBC-2017 BUILDING
 PERMIT #18070030
 415 SOUTHERN BLVD.
 TYPE OF CONSTRUCTION: ?
 OCCUPANCY TYPE: ?
 SPRINKLERED BLDG: NO
 LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF
 OCCUPANCY
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) A LIFE SAFETY PLAN (SHEET A250) IS IDENTIFIED ON THE
 SHEET INDEX, HOWEVER IT WAS NOT PROVIDED WITH THIS
 SUBMISSION. PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING
 TYPE OF CONSTRUCTION AND ALL OCCUPANCY TYPES, OCCUPANT
 LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL, FIRE
 SPRINKLER CLASSIFICATION, LOCATION OF FIRE SEPARATIONS
 AND HOURLY FIRE-RATINGS, FIRESTOPPING FOR PIPES,
 CONDUITS, AND DUCTWORK, EGRESS PATHS AND TRAVEL
 DISTANCES, ETC.- SECTION 107.2.1 WPB AMENDMENTS
  
 3) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT
 SHALL INDICATE THE CLASSIFICATION OF WORK AS OUTLINED
 IN CHAPTER 5 FBC EXISTING BUILDING. THIS APPEARS TO BE
 A CHANGE OF OCCUPANCY AS DEFINED IN SECTION 202 FBC EX.
 PLEASE SEE SECTION 506 AND CHAPTER 10 FOR ALL
 REQUIREMENTS.
  
 4) THE BUILDING IS FUNCTIONING AS A MULTI-USE
 OCCUPANCY. INDICATE IF THE BUILDING IS DESIGNED FOR
 MIXED USE (NON-SEPARATED) OR SEPARATED USE PER SECTION
 6.1.14.3 OF NFPA 101 FLORIDA EDITION 2015. FOR
 NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT
 FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY
 SHALL APPLY TO THE BUILDING.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR CUT
 SHEETS FOR ALL EQUIPMENT LISTED IN THE SCHEDULE
 INCLUDING THE CHILLER, BOILER, STILLS ETC. THE SPECS
 SHALL INDICATE THE LISTING AND LABELING, OR TESTING
 STANDARD APPLIED TO EACH PIECE OF EQUIPMENT- SECTION
 107.2.1 WPB.
  
 6) PLEASE PROVIDE AN OUTLINE DETAILING THE DISTILLING
 AND/OR BREWING PROCESS THAT WILL OCCUR AT THIS
 FACILITY. FBC 107.2.1
  
 7) PLEASE PROVIDE DETAILS REGARDING THE MANUFACTURE,
 PROCESSING, GENERATION AND STORAGE OF HAZARDOUS
 MATERIALS AT THIS SITE PER NFPA 101, CHAPTER 6 AND FBC
 SECTION 307.
 [F]307.1 HIGH-HAZARD GROUP H.
 HIGH-HAZARD GROUP H OCCUPANCY INCLUDES, AMONG OTHERS,
 THE USE OF A BUILDING OR STRUCTURE, OR A PORTION
 THEREOF, THAT INVOLVES THE MANUFACTURING, PROCESSING,
 GENERATION OR STORAGE OF MATERIALS THAT CONSTITUTE A
 PHYSICAL OR HEALTH HAZARD IN QUANTITIES IN EXCESS OF
 THOSE ALLOWED IN CONTROL AREAS COMPLYING WITH SECTION
 414, BASED ON THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR
 CONTROL AREAS SET FORTH IN TABLES 307.1(1) AND
 307.1(2). HAZARDOUS OCCUPANCIES ARE CLASSIFIED IN
 GROUPS H-1, H-2, H-3, H-4 AND H-5 AND SHALL BE IN
 ACCORDANCE WITH THIS SECTION, THE REQUIREMENTS OF
 SECTION 415 AND THE FLORIDA FIRE PREVENTION CODE.
 HAZARDOUS MATERIALS STORED, OR USED ON TOP OF ROOFS OR
 CANOPIES, SHALL BE CLASSIFIED AS OUTDOOR STORAGE OR USE
 AND SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE.
 SEE FBC B TABLE 307.1(1)
 [F]307.1.2 HAZARDOUS MATERIALS.
 HAZARDOUS MATERIALS IN ANY QUANTITY SHALL CONFORM TO
 THE REQUIREMENTS OF THIS CODE, INCLUDING SECTION 414,
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 8) SUBMIT TWO COPIES OF THE MATERIAL SAFETY DATA SHEETS
 (MSDS) FOR THE HAZARDOUS MATERIALS (FLAMMABLE LIQUIDS,
 ETC.) THAT WILL BE PRESENT AT THIS FACILITY. FBC B
 307.1.2
  
 9) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION
 DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER
 ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 10) COMPONENTS & CLADDING
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
  
 12)W.P.B. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR
 THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES,
 STILLS ETC, AND PROVIDE ANCHORING DETAILS. FBC-B 1606
 AND 1607
  
 14) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED
 WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS
 REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND
 CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE
 INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION
 107.2.1 WPB.
  
 15) 2017 FBC- ACCESSIBILITY - ADA
 201.1 SCOPE.
 THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE
 SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO
 PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO
 RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2),
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL
 NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE
 BUILDINGS AND FACILITIES, PLACES OF PUBLIC
 ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS
 CODE SHALL COMPLY WITH THIS CODE.
 THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND
 NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM
 RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED
 BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR
 FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508,
 F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS
 DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN;
 BUILDINGS AND FACILITIES WHERE THE ORIGINAL
 CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS
 CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW.
  
 15-1) THE PLANS SHOW A RECEPTION/TASTING AREA THAT
 APPARENTLY WILL BE OPEN TO THE PUBLIC. SPECIFY WHICH
 AREAS WILL BE OPEN TO THE PUBLIC FOR TOURS, ETC. FBC
 107.2.1
  
 15-2) 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE PITS AND PLATFORMS.
 (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES
 AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS.
 (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER
 LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SECTIONS 221 AND 802 ARE MET.
 (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF
 CHAPTER 10 ARE MET.
 (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9.
 (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION
 203.
 BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN.
 ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE
 APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR
 WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS
 REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL
 CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE
 THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED
 TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE
 AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS,
 EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM
 THESE REQUIREMENTS AND MUST BE ACCESSIBLE.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 15-3) PROVIDE AN ACCESSIBLE ROUTE TO AND THROUGH THE
 PUBLIC AREAS. FBC-A 206.1 GENERAL. ACCESSIBLE ROUTES
 SHALL BE PROVIDED IN ACCORDANCE WITH 206 AND SHALL
 COMPLY WITH CHAPTER 4.
  
 15-4) PROVIDE AN ACCESSIBLE BATHROOM.
 FBC-A 213 TOILET FACILITIES AND BATHING FACILITIES
 213.1 GENERAL.
 WHERE TOILET FACILITIES AND BATHING FACILITIES ARE
 PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED IN
 FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT
 TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET
 FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON
 A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN
 ACCESSIBLE ENTRANCE.
 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 16) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR
 THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 17) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 09:17 Rev Time 0.00
Received By jpearson Date 2019-03-16 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-19 Cont ID  
Sent By jpearson Date 2018-11-19 Time 08:11 Rev Time 0.00
Received By jpearson Date 2018-11-19 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-11-01 Cont ID  
Sent By jpearson Date 2018-11-01 Time 09:45 Rev Time 0.00
Received By jpearson Date 2018-11-01 Time 09:38 Sent To  
Notes
2018-11-01 09:38:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
  
 NEW COMMENT:
  
 12. NEW DESIGN PROVIDED SHOWS THE EXISTING 200 AMP
 METER CAN FEEDING NEW MAIN 1 OF 2. THIS MAIN IS RATED
 AT 225 AMPS, WHICH EXCEEDS THE CAPACITY OF THE METER
 CAN. PROVIDE CORRECTION. NEC 110.3
 13. PROVIDE DISONNECT WITHIN SIGHT OF TRANSFORMER
 XFMR-1. NEC 450.14
 14. REMOVE CLOUDS FROM PREVIOUSLY CORRECTED COMMENTS.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-18 Cont ID  
Sent By jpearson Date 2018-09-18 Time 15:57 Rev Time 0.00
Received By jpearson Date 2018-09-18 Time 15:57 Sent To  
Notes
2018-09-18 15:57:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS
 MISSING. NEC 220 (PANEL A AND B DO NOT HAVE TOTALS FOR
 THE LOADS. PANEL SCHEDULE INCOMPLETE.)
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. RISER DIAGRAM SHOWS FEEDERS WITH A REDUCED NEUTRAL
 TO EACH PANEL. HOWEVER, THE PANEL SCHEDULES CALL FOR
 FULL SIZE NEUTRALS. CORRECT DISCREPANCY. IF REDUCED
 NEUTRAL SIZE IS DESIRED, PROVIDE NEUTRAL DEMAND LOAD
 CALCULATION. WPB FBC 107.2.1; NEC 220.61
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-08 Cont ID  
Sent By jpearson Date 2018-07-08 Time 12:46 Rev Time 0.00
Received By jpearson Date 2018-07-08 Time 11:19 Sent To  
Notes
2018-07-08 12:46:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE INTERIOR LIGHTING POWER ALLOWANCE SCHEDULE ON
 SHEET E101 SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. LIGHTING CONTROL IS NOT SHOWN IN DETAILS OR ON PLAN.
 PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 3. SHEET E102, SERVICE KEY NOTE 2 STATES THAT A NEW 600
 AMP SERVICE IS PROPOSED, WHILE THE RISER DIAGRAM SHOWS
 AN 800 AMP SERVICE. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 4. PROVIDE COMPLETE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY
 ONLY SHOWS THE NEW PROPOSED SERVICE, NOT THE EXISTING
 THAT IS TO REMAIN. NEC 215.5, 230, 250.50, 250.94,
 408.30; WPB FBC 107.2.1
 5. PER NEC 230.2, ONLY ONE SERVICE IS PERMITTED UNLESS
 PERMITTED IN 230.2(A) THROUGH (D). EOR HAS NOT DETAILED
 WHY THE ADDITIONAL SERVICE IS REQUESTED. PROVIDE
 DETAILS OF WHY THE EXISTING SERVICE IS NOT ADEQUATE.
 6. MAINS MUST BE GROUPED PER NEC 230.72. PROVIDE
 CORRECTION. NEC 230.72
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 PLAN CURRENTLY ONLY SHOWS CALCULATION FOR SERVICE
 DISCONNECT. NEC 110.9, 110.10
 8. PROVIDE AIC RATING OF EACH PANEL. NEC 110.3, 110.9;
 WPB FBC 107.2.1
 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS
 MISSING. NEC 220
 10. PROVIDE PANEL SCHEDULE FOR EXISTING PANELS
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND GFCI PROTECTION OR
 LIGHTING CONTROL WHERE APPLICABLE TO COMPLY WITH CODE.
 NEC 210.8, 210.19, 210.20, 215.2, 215.5, 408.4; FBC EC
 C405
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-03-15 Cont ID  
Sent By scaldero Date 2019-03-15 Time 09:50 Rev Time 0.00
Received By scaldero Date 2019-03-15 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By scaldero Date 2018-10-29 Time 15:25 Rev Time 0.00
Received By scaldero Date 2018-10-29 Time 13:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-09-11 Cont ID  
Sent By scaldero Date 2018-09-11 Time 13:35 Rev Time 0.00
Received By scaldero Date 2018-09-05 Time 09:16 Sent To  
Notes
2018-09-11 13:35:28PERMIT # 18070030
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW:
  
 1) SHEET A250: PER SECTION 8.7, ANY AREA HAVING A
 DEGREE OF HAZARD GREATER THAN NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
 HAZARD OF CONTENTS SEPARATION IS REQUIRED BETWEEN THE
 INDUSTRIAL USE AREAS AND THE ASSEMBLY AREA
 (RECEPTION/TASTING). ADDITIONALLY, THE OFFICE USE SPACE
 OF THE SECOND FLOOR REQUIRES FIRE-RATED PROTECTION FROM
 THE MODERATE/ORDINARY HAZARD INDUSTRIAL USE AREA
 DIRECTLY BELOW.
  
 NFPA 101: 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43
  
 2) INTERIOR STAIR APPEARS TO BE "OPEN", LEADING DOWN
 FROM AN AREA OF LOWER HAZARD TO AN AREA OF HIGHER
 HAZARD. AS THIS STAIR IS PART OF THE MEANS OF EGRESS,
 IT ALSO NEEDS TO BE REVIEWED AND PROVIDED WITH THE
 PROPER SEPARATION.
  
 3) PER YOUR NARRATIVE RESPONSE, YOU INDICATE THAT THE
 RECEPTION/TASTING AREA WILL BE FOR "PRIVATE USE" AS A
 "WORK AREA". HOWEVER, YOU HAVE PROVIDED AN OCCUPANCY
 LOAD CALCULATION THAT EQUATES TO AN AREA THAT WILL BE
 USED AS AN ASSEMBLY SPACE (1:15). PLEASE CLARIFY
 COMMENTS.
 WILL THIS AREA BE IN ANY WAY ACCESSIBLE TO PERSONS
 OTHER THAN STAFF AND/OR DELIVERY PERSONNEL? IN OTHER
 WORDS, WILL THE GENERAL PUBLIC HAVE ACCESS TO IT FOR
 ANY REASON (I.E. PRIVATE EVENTS, SPECIAL EVENTS,
 PURCHASE OF GOODS, TOURS, ETC.)
  
 4) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 5) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 DELAYED EGRESS INSTALLATION.
  
 7) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-05 Cont ID  
Sent By scaldero Date 2018-07-05 Time 10:34 Rev Time 0.00
Received By scaldero Date 2018-07-05 Time 08:34 Sent To  
Notes
2018-07-05 10:34:07PERMIT #18070030
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) A LIFE SAFETY PLAN (SHEET A250) IS IDENTIFIED ON THE
 SHEET INDEX, HOWEVER IT WAS NOT PROVIDED WITH THIS
 SUBMISSION.
 PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 2) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3
 OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED
 MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE
 SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO
 THE BUILDING.
  
 3) PLEASE PROVIDE DETAILS REGARDING THE HAZARD OF
 CONTENTS, AS DEFINED BY NFPA 101, CHAPTER 6.
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND
 SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED,
 AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED DESIGN PROFESSIONAL (RDP) OR OWNER AND
 SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR
 REVIEW AND APPROVAL ON THE BASIS OF THE CHARACTER OF
 THE CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED
 IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS
 OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL
 GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43.
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR STRUCTURE SHALL BE CLASSIFIED AS LOW,
 ORDINARY, OR HIGH IN ACCORDANCE WITH 6.2.2.2, 6.2.2.3,
 AND 6.2.2.4.
 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL
 BE CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT
 NO SELFPROPAGATING FIRE THEREIN CAN OCCUR.
 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD
 CONTENTS SHALL BE CLASSIFIED AS THOSE THAT ARE LIKELY
 TO BURN WITH MODERATE RAPIDITY OR TO GIVE OFF A
 CONSIDERABLE VOLUME OF SMOKE.
 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS
 SHALL BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN
 WITH EXTREME RAPIDITY OR FROM WHICH EXPLOSIONS ARE
 LIKELY. (FOR MEANS OF EGRESS REQUIREMENTS, SEE SECTION
 7. 11.)
  
 4) PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS/DATA SHEET FOR ALL DISTILLNG AND BREWING
 EQUIPMENT BEING USED.
  
 5) PLEASE PROVIDE AN OUTLINE DETAILING THE DISTILLING
 AND/OR BREWING PROCESS.
  
 6) PLEASE BE ADVISED: WHERE A FIRE SPRINKLER AND/OR
 FIRE ALARM SYSTEM IS REQUIRED PER THE FLORIDA FIRE
 CODE, ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. (SEE FLORIDA ADMINISTRATIVE CODE 61G15
 FOR FULL DETAIL REQUIREMENTS.)
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 16:59 Rev Time 0.00
Received By gjohnson Date 2018-11-29 Time 16:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 06:41 Rev Time 0.00
Received By gjohnson Date 2018-09-27 Time 08:01 Sent To  
Notes
2018-09-28 07:04:492ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. PLEASE CLARIFY THE SYSTEM PRESSURE SHT. P103A UNDER
 THE GAS CALCULATIONS LIST THE PRESSURE AT 2PSIOR LESS
 IS IT 2 PSI OR IS IT LESS THAN 2 PSI. PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHT. P103A THE PLAN IS SHOWING THE METER AND
 REGULATOR OUT SIDE THE NEW FENCE RIGHT IN FRONT OF THE
 PARKING STOP PLEASE SHOW ON THE THE PLAN THAT THE GAS
 RISER, METER AND REGULATOR ARE PROTECTED FROM DAMAGE
 FROM VEHICLES WITH A SUBSTANTIAL TRAFFIC BALLARD. PER
 WPB AMEND TO FBC 107.2.1
  
 3. IT WILL BE REQUIRED TO SUBMIT BEFORE PERMIT ISSUE
 TWO COPY'S OF THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE BOILER AND REGULATOR THE
 BOILER SPECS THAT WHERE PROVIDED DID NOT GIVE
 INFORMATION ON THE STANDARDS THAT IT MEETS OR CLEARLY
 SHOW INSTALLATION OUT DOORS. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2018-08-09 Time 08:44 Sent To  
Notes
2018-08-09 09:10:571ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. HOW WILL THE GAS PIPING BE SECURED IT DOES NOT
 APPEAR TO BE ANY WALLS OR OTHER SUPPORTS TO STRAP THE
 PIPING TO PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 AND FBC FG 404.9 - 404.11.2
  
 3. PLEASE PROVIDE DETAILS OF HOW THE BOILER IS TIED
 DOWN. PER FBC FG 301.10 AND COMPLIANCE WITH FBCFG
 301.11
  
 4. PROVIDE DOCUMENTATION THAT THE BOILER IS RATED FOR
 EXTERIOR USE IN A WET LOCATION. PER WPB AMEND TO FBC
 107.2.1
  
 5. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 7. PROVIDE SITE PLAN SHOWING LOCATION OF THE GAS METER
 AND PIPING. PER WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE DETAIL SHOW HOW THE GAS METER WILL BE
 PROTECTED FROM VEHICULAR TRAFFIC. PER WPB AMEND TO FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 06:59 Rev Time 0.00
Received By gjohnson Date 2019-03-27 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-27 Cont ID  
Sent By lmarchan Date 2019-03-27 Time 10:25 Rev Time 0.00
Received By lmarchan Date 2019-03-14 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 17:00 Rev Time 0.00
Received By gjohnson Date 2018-10-26 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 07:05 Rev Time 0.00
Received By gjohnson Date 2018-09-04 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 09:11 Rev Time 0.00
Received By gjohnson Date 2018-07-03 Time 09:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-03-29 Cont ID  
Sent By lmarchan Date 2019-03-29 Time 09:57 Rev Time 0.00
Received By lmarchan Date 2019-03-27 Time 15:22 Sent To  
Notes
2019-03-29 09:57:33RECEIPT MU-2019-9469 - $0.00 MONEY OWED
2019-03-27 15:22:323/27/19 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By rmcdouga Date 2018-08-02 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2018-08-02 Time 09:55 Sent To  
Notes
2018-08-02 09:57:56THIS IS A CHANGE OF OCCUPANCY WHICH WILL REQUIRE THE
 PLANS TO BE REVIEWED BY PALM BEACH COUNTY TO DETERMINE
 IF ANY IMPACT FEES ARE REQUIRED TO BE PAID.
  
 IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-03-28 Cont ID  
Sent By ccole Date 2019-03-28 Time 10:55 Rev Time 0.00
Received By ccole Date 2019-03-28 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-03-21 Cont ID  
Sent By ccole Date 2019-03-21 Time 11:15 Rev Time 0.00
Received By ccole Date 2019-03-21 Time 08:58 Sent To  
Notes
2019-03-21 11:18:494TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18070030
 9/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-102: VERIFY THE DESIGN AND OPERATION OF THE
 HAZARDOUS EXHAUST VENTILATION SYSTEM (AHU-1 AND EF-1)
 IN THE DISTILLERY SHALL BE SUCH THAT FLAMMABLE
 CONTAMINANTS ARE DILUTED IN NONCONTAMINATED AIR TO
 MAINTAIN CONCENTRATIONS IN THE EXHAUST FLOW BELOW 25
 PERCENT OF THE CONTAMINANT'S LOWER FLAMMABILITY LIMIT.
 HAS CAPTURE AND CONTAINMENT OF FLAMABLE VAPORS IN THEIR
 HEAVIEST CONCENTRATIONSAROUND THE STILLS AND TANKS BEEN
 TAKING INTO CONSIDERATION?- SECTION 502.1.1 FBC M.
  
 A) DESCRIBE THE SEQUENCE OF OPERATION FOR THE SYSTEM.
 WILL THE SYSTEM RUN CONTINUOUSLY, OR INTERMITTENTLY
 WHEN DISTILLERY OPERATIONS ARE BEING CONDUCTED? HOW
 WILL THE NEW GAS SENSORS AFFECT THE OPERATION OF THE
 VENTILATION SYSTEM. WILL THESE SENSORS BE LINKED TO THE
 SYSTEM AND ALSO TO THE FIRE ALARM?
  
 2) SUBMIT A REVISED ENERGY COMPLIANCE REPORT THAT
 INLCUDES THE NEW AC SYSTEM AND THE CHANGES TO THE
 BUILDING ENVELOPE.
  
 3) PLEASE ADJUST THE TOTAL VALUE OF THE PROPOSED
 PROJECT TO INCLUDE THE INCREASED COSTS ASSOCIATED WITH
 THE NEW EXHAUST VENTILATION SYSTEM AND SENSORS IN THE
 DISTILLERY- SECTION 109.3 FBC M.
  
 4) PLEASE NOTE THE LIST OF PROVISOS FROM THE PREVIOUS
 REVIEW.
  
 MECHANICAL PROVISOS.
 11/13/28
  
 1) PRESSURE TESTS FOR CHILLED WATER AND STEAM PIPING
 REQUIRED. REQUIRED TEST PRESSURES SHALL BE PROVIDED BY
 THE DISTILLERY SYSTEM MANUFACTURER AND THE ENGINEER OF
 RECORD.
  
 2) PROVIDE A LETTER FROM THE DISTILLERY SYSTEM
 MANUFACTURER (CORSON) CERTIFYING THE EQUIPMENT- STILLS,
 TANKS, PROCESS PIPINGS ETC.- ARE INSTALLED AND
 FUNCTIONING IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. THE LETTER SHALL BEAR
 THE APPROVAL STAMPS OF THE ENGINEER AND ARCHITECT OF
 RECORD.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE GLYCOL CHILLER AND OUTDOOR BOILER AND ASSOCIATED
 EQUIPMENT SHALL BE SUBMITTED PRIOR TO INSPECTION.
  
 6) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CHILLER, BOILER, AND THE CORSON
 DISTILLERY SYSTEM SHALL BE ONSITE AT TIME OF
 INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By ccole Date 2018-11-13 Time 09:23 Rev Time 0.00
Received By ccole Date 2018-11-05 Time 13:57 Sent To  
Notes
2018-11-13 09:49:42MECHANICAL PROVISOS.
 11/13/28
  
 1) PRESSURE TESTS FOR CHILLED WATER AND STEAM PIPING
 REQUIRED. REQUIRED TEST PRESSURES SHALL BE PROVIDED BY
 THE DISTILLERY SYSTEM MANUFACTURER AND THE ENGINEER OF
 RECORD.
  
 2) PROVIDE A LETTER FROM THE DISTILLERY SYSTEM
 MANUFACTURER (CORSON) CERTIFYING THE EQUIPMENT- STILLS,
 TANKS, PROCESS PIPINGS ETC.- ARE INSTALLED AND
 FUNCTIONING IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. THE LETTER SHALL BEAR
 THE APPROVAL STAMPS OF THE ENGINEER AND ARCHITECT OF
 RECORD.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE GLYCOL CHILLER AND OUTDOOR BOILER AND ASSOCIATED
 EQUIPMENT SHALL BE SUBMITTED PRIOR TO INSPECTION.
  
 4) A REVISED AC DUCT LAYOUT PLAN SHALL BE SUBMITTED FOR
 ALL REQUIRED ALTERATIONS MADE TO THE EXISTING SYSTEMS.
  
 5) THE RUM DISTILLERY PROCESS AND RUM STORAGE SHALL BE
 IN ACCORDANCE WITH HAZARDOUS LIQUID GUIDELINES-
 SECTIONS 307.1.2 & 414 FLORIDA BUILDING CODE SIXTH
 EDITION- 2017, AND NFPA 30-2018. PLEASE NOTE THAT A
 REVISION TO THE APPROVED MECHANICAL PLANS MAY BE
 REQUIRED BASED ON ANY REQUIRED CHANGES TO THE
 ARCHITECTURAL PLANS.
  
 6) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CHILLER, BOILER, AND THE CORSON
 DISTILLERY SYSTEM SHALL BE ONSITE AT TIME OF
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-19 Cont ID  
Sent By ccole Date 2018-09-19 Time 12:09 Rev Time 0.00
Received By ccole Date 2018-09-19 Time 09:57 Sent To  
Notes
2018-09-19 13:19:052ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18070030
 9/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON THE NOTES ON SHEET M-102 ABOUT THE
 RELOCATION OF THE EXISTING AIR HANDLERS, A COMPLETE
 REVIEW OF THE MECHANICAL PLANS CANNOT BE ACCOMPLISHED
 WITHOUT THE NEW AIR HANDLER LOCATIONS SHOWN, AND A
 COMPLETE AC LAYOUT PLAN PROVIDED FOR BOTH THE 1ST AND
 2ND FLOORS. MANY OF THE ROOMS AND SPACES ARE UNDERGOING
 A CHANGE OF USE FROM THEIR PREVIOUS USES, AND
 RECIRCULATION OF AIR FROM SOME OF THESE ROOMS AND
 SPACES IS NOW PROHIBITED I.E THE LAB, AND THE
 DISTILLERY- SEE TABLE 403.3.1.1.
  
 2) SHEET M-102: THE EXHAUST VENTILATION CALCULATIONS
 ARE INCOMPLETE. CALCULATIONS FOR THE LAB, AND THE 2ND
 FLOOR OFFICES AND STORAGE ROOM WERE NOT PROVIDED.
 CONCERNING THE LAB, PLEASE PROVIDE A NARRATIVE THAT
 CLARIFIES THE PROCESSES THAT WILL TAKE PLACE IN THE LAB
 AND WHAT CHEMICALS OR MATERIALS ARE USED AND STORED IN
 THE LAB. PLEASE SEE SECTION 510.1 FBC M. CONCERNING THE
 2ND FLOOR STORAGE ROOM, CLARIFY WHAT MATERIALS WILL BE
 STORED IN THE ROOM AND HOW IT WILL BRE VENTILATED.
  
 3) M-102: REFER TO SECTION 510.9 FBC M AND INDICATE THE
 TYPE OF EXHAUST DUCTWORK TO BE INSTALLED FOR THE LAB
 AND THE BOTTLING ROOM.
  
 4) M-102: IT APPEARS THE TERMINATIONS OF THE LAB AND
 BOTTLING EXHAUST ARE NOT IN COMPLIANCE WITH REQUIRED
 10' CLEARANCE TO THE DOOR AND TO GRADE- SECTION 501.3.1
 FBC M.
  
 5) M-102: A SURVEY WILL BE NEEDED TO DETERMINE IF THE
 O/A INLET AND EXHAUST OUTLET ON THE WEST SIDE OF THE
 BUILDING ARE 10' CLEAR OF THE PROPERTY LINE- SECTIONS
 401.4 AND 501.3.1 FBC M.
  
 6) M-102: THE VENTILATION CALCULATION FOR THE TASTING
 ROOM IS NOT IN COMPLIANCE WITH TABLE 403.3.1.1. THE
 APPROPRIATE RATE SHALL BE BASED ON AN OCCUPANT DENSITY
 OF 100 PERSONS PER S.F. X 7.5 CFMS PER PERSON + 0.18
 CFMS PER SQ. FT. PLEASE CORRECT.
  
 7) THE LOUVER NOA SUBMITTAL IS MISSING PAGE 1.
  
 8) THE SUBMIITED SPECS FOR THE RITE BOILER DO NOT
 PROVIDE ANY LISTING INFORMATION AS REQUIRED BY SECTION
 631.1 FBC FG, OR INDICATE THE UNIT CAN BE INSTALLED ON
 THE EXTERIOR OF THE BUILDING. THE SPECS ARE INDICATING
 AN INTERIOR INSTALLATION.
  
 9) NO ADDITIONAL INFORMATION HAS BEEN SUBMITTED AS
 REQUESTED FOR THE DISTILLERY TANKS, KETTLES, AND
 STILLS. IT IS STILL NOT CLEAR IF THE EQUIPMENT HAS BEEN
 TESTED IN ACCORDANCE WITH ANY LISTING AGENCY OR TESTING
 STANDARD- PLEASE PROVIDE ADDITIONAL INFORMATION.
  
 10) CLARIFY IF VENTING OF THE STILLS, TANKS, AND
 KETTLES IS REQUIRED, AND REVISE THE PLANS ACCORDINGLY
 TO SHOW LOCATIONS AND VENTING DETAILS.
  
 11) THE SUBMITTED SPECS FOR THE BOTTLING MACHINE
 INDICATE THE USE OF CO2 AND OXYGEN TANKS. CLARIFY IF
 TANKS WILL BE STORED AT THE FACILITY AND SHOW WHERE AND
 HOW THEY WILL BE STORED IF APPLICABLE.
  
 LISTED BELOW ARE COMMENTS FROM THE FIRST REVIEW THAT
 STILL EXIST- PLEASE COMPLY.
  
 8) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION
 DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER
 ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS SHOWN ON
 SHEET M-100- SECTION 301.15 FBC M.
  
 10) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED
 WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS
 REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND
 CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE
 INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION
 107.2.1 WPB.
  
 11) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR
 THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES,
 STILLS ETC, AND PROVIDE ANCHORING DETAILS.
  
 12) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR
 THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By ccole Date 2018-07-17 Time 17:10 Rev Time 0.00
Received By ccole Date 2018-07-17 Time 17:10 Sent To  
Notes
2018-07-17 17:36:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070030
 7/17/18
  
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT
 OF RECORD SHALL PROVIDE A LIFE SAFETY PLAN WHICH SHALL
 INCLUDE THE OCCUPANCY CLASSIFCATION(S) OF THE FACILITY,
 OCCUPANT LOAD, FIRE SPRINKLER CLASSIFICATION, LOCATION
 OF FIRE SEPARATIONS AND HOURLY FIRE-RATINGS,
 FIRESTOPPING FOR PIPES, CONDUITS, AND DUCTWORK, EGRESS
 PATHS AND TRAVEL DISTANCES, ETC.- SECTION 107.2.1 WPB.
  
 2) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE ARCHITECT
 SHALL INDICATE THE CLASSIFCATION OF WORK AS OUTLINED IN
 CHAPTER 5 FBC EX. THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY AS DEFINED IN SECTION 202 FBC EX. PLEASE SEE
 SECTION 506 AND CHAPTER 10 FOR ALL REQUIREMENTS.
  
 3) M-100: SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR
 CUT SHEETS FOR ALL EQUIPMENT LISTED IN THE SCHEDULE
 INCLUDING THE CHILLER, BOILER, STILLS ETC. THE SPECS
 SHALL INDICATE THE LISTING AND LABELING, OR TESTING
 STANDARD APPLIED TO EACH PIECE OF EQUIPMENT- SECTION
 107.2.1 WPB.
  
 4) M-101: SHOW PIPING RUN FROM MAKEUP WATER UNIT TO THE
 CHILLER.
  
 5) SHEET M-102: PLEASE INCLUDE VENTILATION CALCULATIONS
 FOR THE LAB, BOTTLING ROOM, AND RECEPTION/TASTING ROOM-
 SEE SECTION 809.2 FBC EX, AND TABLE 403.1.1 FBC M.
 PLEASE NOTE THAT THE LAB ROOM REQUIRES EXHAUST
 VENTILATION PER TABLE 403.1.1.
  
 6) M-102: THE LOUVER SCHEDULE INDICATES "CART STORAGE
 AREA" WHICH APPEARS TO BE AN INCORRECT IDENTIFCATION OF
 THE DISTILLING AND PROCESSING AREA. PLEAE PROVIDE A
 FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE
 LOUVER.
  
 7) M-103: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED STILLS, AND INDICATE HOW THE COMBUSTION AIR
 WILL BE PROVIDED- SECTION 304 FBC FG.
  
 8) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION
 DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER
 ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS SHOWN ON
 SHEET M-100- SECTION 301.15 FBC M.
  
 9) M-003 & M-104: INCLUDE THE TRYMER PIPE INSULATION IN
 THE SPECIFICATIONS, AND ON WHICH PIPING SYSTEMS THE
 INSULATION IS TO BE INSTALLED- CHILLER OR BOILER
 PIPING, OR BOTH. INDICATE THE THICKNESS OF INSULATION
 TO BE INSTALLED AND CLARIFY IF THE INSULATION IS TESTED
 AND RATED FOR EXTERIOR USE, OR IF ANOTHER PRODUCT WILL
 BE USED FOR THE EXTERIOR PIPING- SEE SECTION C403.2.10
 FBC EC.
  
 10) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED
 WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS
 REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND
 CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE
 INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION
 107.2.1 WPB.
  
 11) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR
 THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES,
 STILLS ETC, AND PROVIDE ANCHORING DETAILS.
  
 12) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR
 THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE
 CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL
 COST OF THE PROJECT INCLUDING, LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE
 WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-04-02 Cont ID  
Sent By gjohnson Date 2019-04-02 Time 06:59 Rev Time 0.00
Received By gjohnson Date 2019-04-02 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 17:00 Rev Time 0.00
Received By gjohnson Date 2018-11-29 Time 17:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By gjohnson Date 2018-09-27 Time 14:38 Rev Time 0.00
Received By gjohnson Date 2018-09-27 Time 08:01 Sent To  
Notes
2018-09-27 17:43:112ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE SHOWN TO BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISH FLOOR. PER FBC ACC
 609.4
  
 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC
 ACC 604.7
  
 3. THE SINK NEXT TO THE BATHROOM APPEARS TO BE NEW IT
 DOES NOT APPEARS ON PREVIOUS PLANS IN OUR PERMIT
 RECORDS IT SHALL COMPLY WITH FBC ACC 212.2, 212.3
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4. SHT P-102 UNDER THE FIXTURE SCHEDULE FS-1 NEEDS TO
 BE REMOVED IF THE OUTDOOR FLOOR SINK WAS DELETED , WC
 HAS THE SPECIFICATIONS FOR THE LAVATORY PLEASE COMPLY.
 PER WPB AMEND TO FBC 107.2.1
  
 5. YOU ARE MISSING THE MANUFACTURE SPECIFICATIONS FOR
 THE ETP PLEASE PROVIDE SPECS FOR THE ZURN Z1020LF AND
 THE BACFLOW FEBCO 850 ALL VALVES AND DEVICES FITTINGS
 AND PIPE CONNECT TO THE POTABLE WATER SYSTEM SHALL BE
 LEAD FREE PER FBC PL 605.2.1 PLACE NOTE ON PLAN
  
 6. BACKFLOW REQUIRED ON CW CONNECTION TO THE CHILLED
 WATER SYSTEM. PER FBC PL 608.3
  
 7. THE PREVIOUS PLANS IN OUR PERMIT RECORDS SHOWS A
 SRVICE SINK ON THE BACKSIDE OF THE LAVATORY AND A WATER
 COOLER IF THESE HAVE BEEN REMOVED AT SOME POINT IT IS
 REQUIRED TO HAVE THEM PER THE FBC PL TABLE 308.5 AND
 SHALL COMPLY WITH CURRENT CODE.
  
 8. SHT P -103 APPEARS TO HAVE BEEN REPLACED BY SHEET
 P-103A PLEASE REMOVE ALL OLD SHEETS. PER WPB AMEND TO
 FBC 107.2.1
  
 9. SEE MECHANICALLY COMMENTS FOR DISTILLING EQUIPMENT
 COMMENTS SHALL COMPLY PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-09 Cont ID  
Sent By gjohnson Date 2018-08-09 Time 06:30 Rev Time 0.00
Received By gjohnson Date 2018-08-07 Time 16:01 Sent To  
Notes
2018-08-09 08:37:361ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE THE TYPE OF OCCUPANCY ON THE PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE ON THE PLAN THE LEVEL OF ALTERATION
 IT APPEARS TO BE A CHANGE OF OCCUPANCY FROOM A BUSINESS
 TO AN F-1 AND THERE FOR SHALL COMPLY WITH FBC EX CH 10
  
 3. LIST OCCUPANT LOAD ON PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 4. THIS ALTERATION SHALL COMPLY WITH FBC ACC 202.4
 PLEASE PROVIDE A COST BREAK DOWN TO SHOW COMPLIANCE.
 PER FBC ACC 202.4.1, 202.4.2
  
 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR ETP, WATER
 SOFTENER AND THE CONDENSATE RETURN WATER SYSTEM. PER
 WPB AMEND TO FBC 107.2.1
  
 6. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FROM
 SCHIER FOR THE GREASE INTERCEPTOR. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE FLOOR DRAIN NEXT TO THE BOILER IS NOT VENTED.
 PER FBC PL 901.2.1
  
 8. THE FLOOR DRAIN NEXT TO THE BOILER APPEARS TO BE ON
 THE EXTERIOR OF THE BUILDING THE SANITARY SHALL NOT
 RECEIVE RAIN WATER HOW WILL THIS FLOOR DRAINBE
 PROTECTED FROM RECEIVING RAIN WATER. PER CITY OF WEST
 PALM BEACH CODE O ORDINANCE SEC. 90-126.(5)
  
 9. SHT PP-101 THE BOILER IS MISSING THE WATER
 CONNECTION ON THE FLOOR PLAN AND THE WATER ISOMETRIC
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. A BACK FLOW IS REQUIRED ON THE EPT AND THE
 CONDENSATE RETURN FEED WATER SYSTEM. PER FBC PL 608.3
  
 11. SHT P-104 DETAIL B SHOWS A SHELF BRACKET WITH A
 RATING OF 150LBS A 45GAL WATER HEATER WEIGHS OVER
 400LBS WHEN IT IS FULL PLEASE PROVIDE A PLATFORM SYSTEM
 THAT EXCEEDS THIS WEIGHT. PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P-104 DETAIL G AND M SHOW A SINGLE TRAP PRIMER
 VALVE THE WATER ISOMETRIC SHOWS A LARGE MULTI PORT
 ELECTRONIC TRAP PRIMER VALVE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-03-28 Cont ID  
Sent By pvalenti Date 2019-03-28 Time 16:39 Rev Time 0.00
Received By pvalenti Date 2019-03-28 Time 16:38 Sent To  
Notes
2019-03-28 10:55:36MECH SHEETS GOOD

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 18:05 Rev Time 0.00
Received By shill Date 2019-03-21 Time 08:27 Sent To  
Notes
2019-03-26 18:06:25BLDG SHEETS OK
 NEW SHEETS SUBMITTED NEXT REVIEW REQUIRE VERIFICATION
  
2019-03-21 08:27:40MECH SHEETS OK
2019-03-16 09:07:00ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-11-01 Cont ID  
Sent By jpearson Date 2018-11-01 Time 08:02 Rev Time 0.00
Received By jpearson Date 2018-11-01 Time 08:02 Sent To  
Notes
2018-11-01 08:02:20PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481
  
 THE FOLLOWING SHEETS HAVE A CORRUPTED SIGNATURE:
  
 E002, E003, E100, E101, E105, FA100, FA101, M002, M003,
 M101, M104, M105, M106, M107, M108, M109, M110, M111,
 M112, P001, P002, P003, P004, P103, P103B, P104, P105.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By shill Date 2018-09-05 Time 18:28 Rev Time 0.00
Received By shill Date 2018-09-05 Time 18:21 Sent To  
Notes
2018-09-05 18:28:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ENERGY CALCS OK
 A SHEETS OK
  
 ALL MEP SHEETS EXCEPT FOR E001 HAVE AN INVALID
 SIGNATURE (ALTERED OR CORRUPTED SINCE THE SIGNATURE WAS
 APPLIED)
  
 AFTER ALL PLAN REVIEWS HAVE PASSED, SEND A CORRECTLY
 SIGNED PDF WITH ALL MEP PAGES VIA EMAIL TO:
  
 [email protected]
 [email protected]
  
 IN THE SUBJECT LINE OF THE EMAIL INCLUDE THE PERMIT
 NUMBER AND "SIGNATURE DOCUMENTS"
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-03-27 Cont ID  
Sent By llouie Date 2019-03-27 Time   Rev Time 0.00
Received By llouie Date 2019-03-27 Time   Sent To  
Notes
2019-03-27 16:57:07ZONING PROVISO:
  
 1.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 LOT PAVEMENT STRIPING, WALL/FENCE, PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.).
  
  
 NOTES:
  
 * TOTAL VALUE OF PROJECT (TO DATE): INTERIOR BUILDOUT
 (#18070030) $410, 250 + INTERIOR DEMO (#18071011)
 $2,350 = $412,600.
  
 * CURRENT VALUE OF EXISTING STRUCTURE = $698,684 (2018
 PAPA). VALUE OF THE PROJECT EXCEEDS 50% VALUE OF THE
 STRUCTURE. THEREFORE, UPGRADE TO LANDSCAPING (TO MEET
 ZLDRS), TO THE GREATEST EXTENT POSSIBLE, IS REQUIRED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-03-27 Cont ID  
Sent By llouie Date 2019-03-27 Time   Rev Time 0.00
Received By llouie Date 2019-03-27 Time   Sent To  
Notes
2019-03-27 10:21:10** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) FLOOR PLANS DO NOT MATCH ELEVATIONS. PLEASE
 CORRECT.
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 LOT/PAVEMENT STRIPING, WALL/FENCE.
  
 * NO STRUCTURES (I.E. WALL/FENCE) SHALL BE BUILT WITHIN
 THE 6 FT. WIDE FPL EASEMENT, UNLESS A HOLD HARMLESS
 AGREEMENT IS PROVIDED TO THE CITY.
  
 * TOTAL VALUE OF PROJECT (TO DATE): INTERIOR BUILDOUT
 (#18070030) $410, 250 + INTERIOR DEMO (#18071011)
 $2,350 = $412,600.
  
 * CURRENT VALUE OF EXISTING STRUCTURE = $698,684 (2018
 PAPA). VALUE OF THE PROJECT EXCEEDS 50% VALUE OF THE
 STRUCTURE. THEREFORE, UPGRADE TO LANDSCAPING (TO MEET
 ZLDRS), TO THE GREATEST EXTENT POSSIBLE, IS REQUIRED.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: I
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-13 Cont ID  
Sent By llouie Date 2018-11-13 Time   Rev Time 0.00
Received By llouie Date 2018-11-13 Time   Sent To  
Notes
2018-11-13 15:47:58** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY IS MISSING FROM
 THE PERMIT PACKET. PLEASE PROVIDE.
  
 2.) PROPOSED NEW STRUCTURES AT THE REAR OF THE PROPERTY
 (CHILLER/BOILER) SHALL BE SETBACK AT LEAST 5 FT. FROM
 THE PROPERTY LINE(S)
  
 3.) EXISTING FLOOR PLAN OF THE SECOND LEVEL IS MISSING.
 PLEASE PROVIDE SO THAT STAFF CAN COMPARE THE EXISTING
 SECOND FLOOR LAYOUT TO THE PROPOSED SECOND FLOOR
 LAYOUT.
  
 4.) PROPOSED BUILDING ELEVATIONS SEEM TO BE MISSING
 FROM THE PERMIT SUBMITTAL. PLEASE PROVIDE.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 LOT/PAVEMENT STRIPING, WALL/FENCE.
  
 * NO STRUCTURES (I.E. WALL/FENCE) SHALL BE BUILT WITHIN
 THE 6 FT. WIDE FPL EASEMENT, UNLESS A HOLD HARMLESS
 AGREEMENT IS PROVIDED TO THE CITY.
  
 * TOTAL VALUE OF PROJECT (TO DATE): INTERIOR BUILDOUT
 (#18070030) $410,250 + INTERIOR DEMO (#18071011) $2,350
 = $412,600.
  
 * CURRENT VALUE OF EXISTING STRUCTURE = $698,684 (2018
 PAPA). VALUE OF PROJECT EXCEEDS 50% VALUE OF THE
 STRUCTURE. THEREFORE, UPGRADE TO LANDSCAPING (TO MEET
 ZLDRS), TO THE GREATEST EXTENT POSSIBLE, IS REQUIRED.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: I
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  