| 2018-07-05 10:30:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE SUBMITTED PLANS APPEARS TO ONLY PROVIDE LIMITED |
| | INFORMATION. |
| | |
| | THERE IS A NOTE INDICATING "UP-GRADE ANSUL FIRE |
| | SYSTEM". |
| | |
| | PER NFPA 17A |
| | |
| | CHAPTER 6 PLANS AND ACCEPTANCE TESTS |
| | |
| | 6.1.1 THE FOLLOWING ITEMS SHALL BE INCLUDED IN THE |
| | SPECIFICATIONS: |
| | (1) DESIGNATION OF THE AUTHORITY HAVING JURISDICTION |
| | AND INDICATION |
| | OF WHETHER PLANS ARE REQUIRED |
| | (2) STATEMENT THAT THE INSTALLATION CONFORMS TO THIS |
| | STANDARD |
| | AND MEETS THE APPROVAL OF THE AUTHORITY HAVING |
| | JURISDICTION |
| | (3) INDICATION THAT ONLY EQUIPMENT REFERENCED IN THE |
| | MANUFACTURER?S |
| | DESIGN, INSTALLATION, AND MAINTENANCE MANUAL |
| | OR ALTERNATIVE SUPPLIERS? COMPONENTS THAT ARE LISTED |
| | FOR |
| | USE WITH THE SPECIFIC EXTINGUISHING SYSTEM SHALL BE |
| | USED |
| | (4) IDENTIFICATION OF SPECIAL AUXILIARY DEVICES |
| | ACCEPTABLE TO |
| | THE SYSTEM MANUFACTURER AND THE AUTHORITY HAVING |
| | JURISDICTION |
| | (5) LIST OF THE SPECIFIC TESTS, IF ANY, THAT ARE |
| | REQUIRED |
| | (6) IDENTIFICATION OF THE HAZARD TO BE PROTECTED, |
| | INCLUDING |
| | SUCH INFORMATION AS PHYSICAL DIMENSIONS, COOKING |
| | APPLIANCES, |
| | ENERGY SOURCES FOR EACH APPLIANCE, AND AIRHANDLING |
| | EQUIPMENT |
| | |
| | 6.3.2 THE PLANS SHALL CONTAIN SUFFICIENT DETAIL TO |
| | ENABLE THE |
| | AUTHORITY HAVING JURISDICTION TO EVALUATE THE |
| | PROTECTION OF THE |
| | HAZARD(S). |
| | 6.3.3 THE DETAILS ON THE SYSTEM SHALL INCLUDE THE |
| | FOLLOWING: |
| | (1) SIZE, LENGTH, AND ARRANGEMENT OF CONNECTED PIPING |
| | (2) DESCRIPTION AND LOCATION OF NOZZLES |
| | 6.3.4 INFORMATION SHALL BE SUBMITTED PERTAINING TO THE |
| | FOLLOWING: |
| | (1) THE LOCATION AND FUNCTION OF DETECTION DEVICES |
| | (2) OPERATING DEVICES |
| | (3) AUXILIARY EQUIPMENT |
| | (4) ELECTRICAL CIRCUITRY |
| | |
| | PLEASE PROVIDE THE ENTIRE SYSTEM COMPONENTS AND FLOWS |
| | AND IDENTIFY WHAT IS EXISTING AND WHAT IS |
| | NEW/UP-GRADING. |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION THAT THE INSTALLATION WILL |
| | COMPLY WITH NFPA 17A PER 6.1.1 (2) ABOVE. |
| | |
| | PLEASE PROVIDE ALLPICABLE NOTE. |
| | |
| | |
| | |
| | 3) THERE ARE MULTIPLE NOZZLE SPEC SHEETS ATTACHED; |
| | HOWEVER, THERE ARE NO INDICATIONS WHICH NOZZLES ARE |
| | BEING USED. |
| | |
| | PLEASE INDICATE WHICH NEW NOZZLES ARE BEING USED AND |
| | WHICH ONES ARE EXISTING. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |