Plan Review Details - Permit 18070014
Plan Review Stops For Permit 18070014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 14:07 Rev Time 0.00
Received By rmcdouga Date 2018-07-31 Time 13:49 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 14:18 Sent To I
Notes
2018-07-10 14:18:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) SPECIFY ON THE PLANS AND IN THE SCOPE OF WORK THAT
 THE EXISTING KITCHEN CABINET CONFIGURATION IS NOT BEING
 CHANGED. IF CABINETS ARE BEING MOVED OR ADDED TO THE
 EXISTING CONFIGURATION, PROVIDE A PLAN SHOWING THE
 EXITING CABINET LAYOUT AND THE PROPOSED LAYOUT. FBC
 107.2.1
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By jleahy Date 2018-07-31 Time 17:08 Rev Time 0.00
Received By jleahy Date 2018-07-31 Time 17:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-03 Cont ID  
Sent By tklarge Date 2018-07-26 Time 14:37 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 14:25 Sent To  
Notes
2018-07-26 14:37:19SEE GAS PERMIT #18071175.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By jleahy Date 2018-07-31 Time 17:09 Rev Time 0.00
Received By jleahy Date 2018-07-19 Time 15:22 Sent To  
Notes
2018-07-20 15:22:46RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 14:22 Rev Time 0.00
Received By rmcdouga Date 2018-07-02 Time 14:53 Sent To  
Notes
2018-07-03 14:53:23ROUTED TO PLUMBING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 14:07 Rev Time 0.00
Received By rmcdouga Date 2018-07-31 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 14:19 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 14:19 Sent To  
Notes
2018-07-10 14:22:37PROVIDE SPECIFICATIONS FOR THE EXHAUST HOOD TO THE
 FIELD INSPECTOR. THE HOOD IS REQUIRED TO BE FOR
 RESIDENTIAL USE, COMMERCIAL HOODS CAN NOT BE USED IN A
 SINGLE FAMILY DWELLING. FBC 107.2.1.2

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 14:37 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By tklarge Date 2018-07-10 Time 11:33 Rev Time 0.00
Received By tklarge Date 2018-07-10 Time 10:07 Sent To  
Notes
2018-07-10 10:49:061) THE SCOPE OF WORK REFERS TO THE INSTALLATION OF A
 GAS STOVE. THERE IS NO RECORD IN CITY FILES OF AN
 EXISTING GAS SYSTEM AT THIS ADDRESS. IS THERE A NEW GAS
 SYSTEM BEING INSTALLED AT THIS ADDRESS? CLARIFY.
 2) THE ICEMAKER SHALL BE EQUIPPED WITH AN INLINE
 BACKFLOW PREVENTER AND AIR ARRESTORS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  