| Plan Review Stops For Permit 18061479 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-10-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-10-04 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2019-10-04 10:34:20 | PROVISO: | | | ROOFING PRODUCT APPROVALS TO BE SUBMITTED WITH ROOFING | | | SUB PERMIT APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-27 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-27 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2019-08-27 15:40:52 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18061479 | | | REVIEWED: AUGUST 13, 2018 | | | 2ND REVIEW : APRIL 22, 2019 | | | 3RD REVIEW : AUGUST 27, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THE R VALUES ON ENERGY CALCULATIONS AND THA PLANS ARE | | | CONFLICTING. | | | PLEASE USE THE SAME VALUE ON BOTH OR JUST REFER TO THE | | | ENERGY CALCULATIONS ON PLANS. | | | ALSO, THE ENERGY CALCULATIONS SHOW AS FULL ATTIC NON | | | VENTED WITH BLOWN INSULATION. | | | | | | CAN YOU SELECT ASSEMBLY CLOSER TO WHAT IS BEING USED. I | | | OFTEN SEE CATHEDRAL /SINGLE ASSEMBLY FOR FLAT ROOF DECK | | | SINCE IT IS THE CLOSEST OPTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-04-22 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-04-22 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2019-04-22 10:32:11 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18061479 | | | REVIEWED: AUGUST 13, 2018 | | | 2ND REVIEW : APRIL 22, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO | | | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. | | | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. | | | PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE. | | | -ADDITIONAL COMMENT | | | 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS | | | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED | | | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN | | | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, | | | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO | | | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA | | | STATUTES. -PLEASE HAVE THE OWNER SIGN THE ENERGY | | | CALCULATIONS. | | | -ENERGY CALCULATION SAND PLANS ARE CONFLICTING. ENERGY | | | CALCS ARE CALLING FOR WOOD FRAMING WITH R-19 AND THEY | | | CALL FOR R-30 AT CEILING. PLANS CALL FOR MASONRY WALLS | | | AND R-19 RIGID AT CEILING. | | | -ENERGY CALCS SAY SLAB ON GRADE, BUT PLANS ALSO SHOW | | | RAISED FLOOR. BOTH FLOOR TYPES SHOULD BE ON THE ENERGY | | | CALCULATIONS. | | | -ENERGY CALS SAY VENTED ATTIC AND PLANS ARE FOR | | | UNVENTED. | | | -IS RIGID BOARD INSULATION AIR-IMPERMEABLE OR | | | AIR-PREMEABLE? COORIDINATE R VALUES BETWEEN PLANS AND | | | ENERGY CALCULATIONS. | | | | | | 2. OK. | | | | | | 3. OK. | | | | | | 4. OK. | | | | | | 5. OK. | | | | | | 6. OK. | | | | | | 7. OK. | | | | | | B. [FBC 107.2.1.2] (SEE ROOFING REVIEW FOR ROOFING | | | COMMENTS) | | | | | | C. OK. | | | | | | 8. NEW COMMENT. DRAWINGS SETS DO NOT MATCH. ONE SET IS | | | MISSING SHEET A1.4. THE SHEET IS NOT IN THE VOIDS THAT | | | ARE TRAVELING WITH PERMIT SETS. PLEASE ADD OR REMOVE | | | SHEET A1.4 SO SETS MATCH AND INTENDED DRAWINGS ARE IN | | | THE SET. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-13 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-13 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2018-08-13 09:27:31 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18061479 | | | REVIEWED: AUGUST 13, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO | | | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. | | | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. | | | PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE. | | | | | | 2. [FBC R408.1]PROVIDE VENTING CALCULATIONS FOR UNDER | | | FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED. | | | | | | 3. [FBC R806]SUPPLY VENTING CALCULATIONS FOR THE ATTIC | | | AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW | | | R805.5 FOR UNVENTED. | | | | | | 4. [FBC R318]ARE EXISTING SLABS AND EXISTING 2X8 FLOOR | | | JOISTS GOING TO STAY IN PLACE? HOW WILL TERMITE | | | TREATMENT BE PROVIDED FOR THE ADDITION? | | | | | | 5. [FBC EXISTING 1103]PROVIDE ENGINEERING TO SHOW THAT | | | EXISTING WALL CAN SUPPORT NEW ROOF TRUSSES. | | | | | | 6. SHEET A1.2 FIXED WINDOW IN PLAN SAYS 16? H X 72? W. | | | THE SCHEDULE SAYS 12? X 72? AND THE MARK SAYS 1 WHILE | | | THE PLAN SAYS 2. PLEASE UPDATE TO MATCH AND PROVIDE | | | PRESSURE FOR THIS OPENING ON A2.1. | | | | | | 7. [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR | | | REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE | | | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN APPROVED BY THE BUILDING OFFICIAL. | | | A. PROVIDE PRODUCT APPROVALS FOR WINDOWS, WINDOW MULL, | | | DOORS, TRANSOMS, SLIDERS AND SOLAR TUBES, OR INDICATE | | | THAT YOU WOULD LIKE THEM DEFFERED. | | | | | | B. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR | | | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. | | | (SEE ROOFING REVIEW FOR ADDITIONAL ROOFING COMMENTS) | | | | | | C. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR | | | INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. | | | | | | NOTE: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-08-12 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-08-12 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-04-30 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-04-30 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-07-31 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-07-31 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2018-07-31 10:38:30 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902 | | | 2.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10; FBC RE E3603.3 | | | 3.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE | | | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT | | | AVAILABLE PER NEC 110.24. | | | 4.PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | | FBC EC C405.1, R404.1 | | | 5.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND | | | NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. | | | NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | 6.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | 7.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE | | | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND | | | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, | | | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC | | | 107.2.1 | | | 8.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING | | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC | | | 107.2.1 | | | 9.SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC | | | 210.52; FBC RE E3901.2.1 | | | | | | THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE | | | STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO | | | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 | | | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET | | | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS | | | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC | | | 210.52(C)(1); FBC RE E3901.4 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-10-04 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-26 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2019-09-27 14:18:55 | RESUB ROUTED TO HMOSER'S OFFICE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-27 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-01 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-04-30 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-04-16 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-23 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-06-29 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-11-06 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-06 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-06 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2019-11-06 10:35:02 | OK-STAMP ON PLANS | | | MU-2019-033920-0000 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-13 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-13 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2018-08-13 09:25:53 | [FBC 109] PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE | | | OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-10-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-10-04 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-10-04 |
Time |
08:16 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-08-21 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-08-21 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-08-21 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2019-08-21 14:10:09 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - NEED RETURN AIR IN BEDROOMS PER 2017 FLORIDA | | | BUILDING CODE - RESIDENTIAL, SIXTH EDITION SEC M1602.3 | | | BALANCED RETURN AIR. | | | | | | CHRIS MONTELLO | | | 805-6733 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-04-30 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-04-30 |
Time |
14:15 |
Sent To |
I |
|
| Notes |
| 2019-04-30 15:23:39 | PLAN DENIED | | | 1) ENERGY CALCULATIONS AND PLAN DO NOT MATCH. | | | PROVIDE AHRI SHEET FOR EQUIPMENT ON PLAN. | | | 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR | | | 3) PROVIDE A SIGNATURE ON THE PLAN OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-08-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-08-04 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2018-08-04 10:39:02 | NO AIR CONDITIONING PLANS SECTION 107 FBC 2017 | | | NO ENERGY CALCULATIONS SECTION M1401.3 | | | EQUIPMENT AND APPLIANCE SIZING 2017 | | | RESIDENTIAL CODE. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-21 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-21 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-21 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2019-08-21 07:24:48 | 08/21/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-04-24 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-24 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-24 |
Time |
18:35 |
Sent To |
|
|
| Notes |
| 2019-04-24 18:35:52 | PLUMBING PROVISO: SHOWER SHALL BE EITHER RECESSED WITH | | | POUR INTEGRALLY WALLS/FLOOR FBC-R P2709.2 OR PRE | | | PITCHED ?? PER FOOT AND ONE OF THE MATERIALS CALLED OUT | | | IN FBC-R P2709.2.1- 2709.4 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-23 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-08-23 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2018-08-23 07:23:04 | 08/23/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM AND SHOW THE | | | CONNECTION TO THE SANITARY SYSTEM AND TERMINATION OUT | | | THE STRUCTURE, WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 | | | (11) RESIDENTIAL PLUMBING | | | 2. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE | | | LINING FBC R 2709.2 LINING REQUIRED. | | | NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS | | | PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4" | | | IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER, | | | BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR | | | APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO | | | THE MORTAR DOES NOT COVER THEM PER MANUFACTURES | | | SPECIFICATIONS. | | | 3. PLEASE PROVIDE DIMENSIONS OF FIXTURES ON A1.2 AND | | | CONFORM TO THE 2017 R2705.1 (5) GENERAL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-27 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-27 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2019-08-27 08:32:26 | PLEASE PROVIDE ROOFING PRODUCT APPROVALS WITH ROOFING | | | SUB-PERMIT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-04-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-04-22 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-04-22 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-13 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-13 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2018-08-13 09:24:55 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18061479 | | | REVIEWED: AUGUST 13, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR ROOFING, | | | OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. | | | | | | PROVIDE ROOF DECK NAILING DIAGRAM AND FASTENER TYPE AND | | | SPACING. | | | | | | PROVIDE INSULATION ATTACHMENT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-08-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-08-14 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-09 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-07-09 |
Time |
10:39 |
Rev Time |
|
| Received By |
awooten |
Date |
2018-07-09 |
Time |
|
Sent To |
|
|
| Notes |
|
|