Plan Review Details - Permit 18061479
Plan Review Stops For Permit 18061479
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-10-04 Cont ID  
Sent By dbattles Date 2019-10-04 Time 10:33 Rev Time 0.00
Received By dbattles Date 2019-10-04 Time 10:33 Sent To  
Notes
2019-10-04 10:34:20PROVISO:
 ROOFING PRODUCT APPROVALS TO BE SUBMITTED WITH ROOFING
 SUB PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 15:31 Rev Time 0.00
Received By dbattles Date 2019-08-27 Time 15:31 Sent To  
Notes
2019-08-27 15:40:52****CORRECTIONS****
 W.P.B. PERMIT: 18061479
 REVIEWED: AUGUST 13, 2018
 2ND REVIEW : APRIL 22, 2019
 3RD REVIEW : AUGUST 27, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE R VALUES ON ENERGY CALCULATIONS AND THA PLANS ARE
 CONFLICTING.
 PLEASE USE THE SAME VALUE ON BOTH OR JUST REFER TO THE
 ENERGY CALCULATIONS ON PLANS.
 ALSO, THE ENERGY CALCULATIONS SHOW AS FULL ATTIC NON
 VENTED WITH BLOWN INSULATION.
  
 CAN YOU SELECT ASSEMBLY CLOSER TO WHAT IS BEING USED. I
 OFTEN SEE CATHEDRAL /SINGLE ASSEMBLY FOR FLAT ROOF DECK
 SINCE IT IS THE CLOSEST OPTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By dbattles Date 2019-04-22 Time 10:40 Rev Time 0.00
Received By dbattles Date 2019-04-22 Time 09:37 Sent To  
Notes
2019-04-22 10:32:11****CORRECTIONS****
 W.P.B. PERMIT: 18061479
 REVIEWED: AUGUST 13, 2018
 2ND REVIEW : APRIL 22, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE.
 -ADDITIONAL COMMENT
 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES. -PLEASE HAVE THE OWNER SIGN THE ENERGY
 CALCULATIONS.
 -ENERGY CALCULATION SAND PLANS ARE CONFLICTING. ENERGY
 CALCS ARE CALLING FOR WOOD FRAMING WITH R-19 AND THEY
 CALL FOR R-30 AT CEILING. PLANS CALL FOR MASONRY WALLS
 AND R-19 RIGID AT CEILING.
 -ENERGY CALCS SAY SLAB ON GRADE, BUT PLANS ALSO SHOW
 RAISED FLOOR. BOTH FLOOR TYPES SHOULD BE ON THE ENERGY
 CALCULATIONS.
 -ENERGY CALS SAY VENTED ATTIC AND PLANS ARE FOR
 UNVENTED.
 -IS RIGID BOARD INSULATION AIR-IMPERMEABLE OR
 AIR-PREMEABLE? COORIDINATE R VALUES BETWEEN PLANS AND
 ENERGY CALCULATIONS.
  
 2. OK.
  
 3. OK.
  
 4. OK.
  
 5. OK.
  
 6. OK.
  
 7. OK.
  
 B. [FBC 107.2.1.2] (SEE ROOFING REVIEW FOR ROOFING
 COMMENTS)
  
 C. OK.
  
 8. NEW COMMENT. DRAWINGS SETS DO NOT MATCH. ONE SET IS
 MISSING SHEET A1.4. THE SHEET IS NOT IN THE VOIDS THAT
 ARE TRAVELING WITH PERMIT SETS. PLEASE ADD OR REMOVE
 SHEET A1.4 SO SETS MATCH AND INTENDED DRAWINGS ARE IN
 THE SET.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 09:26 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 09:25 Sent To  
Notes
2018-08-13 09:27:31****CORRECTIONS****
 W.P.B. PERMIT: 18061479
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 PROVIDE FOR THERMAL ENVELOPE INCLUDING FLOOR SPACE.
  
 2. [FBC R408.1]PROVIDE VENTING CALCULATIONS FOR UNDER
 FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED.
  
 3. [FBC R806]SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW
 R805.5 FOR UNVENTED.
  
 4. [FBC R318]ARE EXISTING SLABS AND EXISTING 2X8 FLOOR
 JOISTS GOING TO STAY IN PLACE? HOW WILL TERMITE
 TREATMENT BE PROVIDED FOR THE ADDITION?
  
 5. [FBC EXISTING 1103]PROVIDE ENGINEERING TO SHOW THAT
 EXISTING WALL CAN SUPPORT NEW ROOF TRUSSES.
  
 6. SHEET A1.2 FIXED WINDOW IN PLAN SAYS 16? H X 72? W.
 THE SCHEDULE SAYS 12? X 72? AND THE MARK SAYS 1 WHILE
 THE PLAN SAYS 2. PLEASE UPDATE TO MATCH AND PROVIDE
 PRESSURE FOR THIS OPENING ON A2.1.
  
 7. [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
 A. PROVIDE PRODUCT APPROVALS FOR WINDOWS, WINDOW MULL,
 DOORS, TRANSOMS, SLIDERS AND SOLAR TUBES, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFFERED.
  
 B. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
 (SEE ROOFING REVIEW FOR ADDITIONAL ROOFING COMMENTS)
  
 C. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-12 Cont ID  
Sent By ppetty Date 2019-08-12 Time 10:16 Rev Time 0.00
Received By ppetty Date 2019-08-12 Time 10:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By ppetty Date 2019-04-30 Time 11:47 Rev Time 0.00
Received By ppetty Date 2019-04-30 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By ppetty Date 2018-07-31 Time 10:39 Rev Time 0.00
Received By ppetty Date 2018-07-31 Time 09:57 Sent To  
Notes
2018-07-31 10:38:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 3.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
 4.PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND
 NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE.
 NEC 215.2, 220, 408.30; FBC RE E3602.2
 6.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 7.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
 8.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 9.SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1
  
 THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901.4
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-04 Cont ID  
Sent By dbattles Date 2019-10-04 Time 10:33 Rev Time 0.00
Received By dbattles Date 2019-09-26 Time 14:18 Sent To  
Notes
2019-09-27 14:18:55RESUB ROUTED TO HMOSER'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 15:40 Rev Time 0.00
Received By dbattles Date 2019-08-01 Time 14:39 Sent To  
Notes
2019-08-02 14:39:32R32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-30 Cont ID  
Sent By hmoser Date 2019-04-30 Time 15:24 Rev Time 0.00
Received By hmoser Date 2019-04-16 Time 14:00 Sent To  
Notes
2019-04-17 14:01:07R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-23 Cont ID  
Sent By lcrespo Date 2018-08-23 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2018-06-29 Time 16:24 Sent To  
Notes
2018-07-02 16:24:36R33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-11-06 Cont ID  
Sent By dbattles Date 2019-11-06 Time 10:34 Rev Time 0.00
Received By dbattles Date 2019-11-06 Time 10:34 Sent To  
Notes
2019-11-06 10:35:02OK-STAMP ON PLANS
 MU-2019-033920-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 09:25 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 09:25 Sent To  
Notes
2018-08-13 09:25:53[FBC 109] PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE
 OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-10-04 Cont ID  
Sent By hmoser Date 2019-10-04 Time 08:25 Rev Time 0.00
Received By hmoser Date 2019-10-04 Time 08:16 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-08-21 Cont ID  
Sent By cmontell Date 2019-08-21 Time 14:21 Rev Time 0.00
Received By cmontell Date 2019-08-21 Time 14:08 Sent To  
Notes
2019-08-21 14:10:09MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURN AIR IN BEDROOMS PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL, SIXTH EDITION SEC M1602.3
 BALANCED RETURN AIR.
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-30 Cont ID  
Sent By hmoser Date 2019-04-30 Time 15:23 Rev Time 0.00
Received By hmoser Date 2019-04-30 Time 14:15 Sent To I
Notes
2019-04-30 15:23:39PLAN DENIED
 1) ENERGY CALCULATIONS AND PLAN DO NOT MATCH.
 PROVIDE AHRI SHEET FOR EQUIPMENT ON PLAN.
 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR
 3) PROVIDE A SIGNATURE ON THE PLAN OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 10:33 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 10:33 Sent To  
Notes
2018-08-04 10:39:02NO AIR CONDITIONING PLANS SECTION 107 FBC 2017
 NO ENERGY CALCULATIONS SECTION M1401.3
 EQUIPMENT AND APPLIANCE SIZING 2017
 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-21 Cont ID  
Sent By lcrespo Date 2019-08-21 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2019-08-21 Time 07:21 Sent To  
Notes
2019-08-21 07:24:4808/21/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 18:35 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 18:35 Sent To  
Notes
2019-04-24 18:35:52PLUMBING PROVISO: SHOWER SHALL BE EITHER RECESSED WITH
 POUR INTEGRALLY WALLS/FLOOR FBC-R P2709.2 OR PRE
 PITCHED ?? PER FOOT AND ONE OF THE MATERIALS CALLED OUT
 IN FBC-R P2709.2.1- 2709.4
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-23 Cont ID  
Sent By lcrespo Date 2018-08-23 Time 07:22 Rev Time 0.00
Received By lcrespo Date 2018-08-23 Time 06:35 Sent To  
Notes
2018-08-23 07:23:0408/23/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM AND SHOW THE
 CONNECTION TO THE SANITARY SYSTEM AND TERMINATION OUT
 THE STRUCTURE, WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3
 (11) RESIDENTIAL PLUMBING
 2. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING FBC R 2709.2 LINING REQUIRED.
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
 3. PLEASE PROVIDE DIMENSIONS OF FIXTURES ON A1.2 AND
 CONFORM TO THE 2017 R2705.1 (5) GENERAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 08:27 Rev Time 0.00
Received By dbattles Date 2019-08-27 Time 08:27 Sent To  
Notes
2019-08-27 08:32:26PLEASE PROVIDE ROOFING PRODUCT APPROVALS WITH ROOFING
 SUB-PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By dbattles Date 2019-04-22 Time 10:40 Rev Time 0.00
Received By dbattles Date 2019-04-22 Time 10:40 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 09:23 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 09:22 Sent To  
Notes
2018-08-13 09:24:55****CORRECTIONS****
 W.P.B. PERMIT: 18061479
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR ROOFING,
 OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 PROVIDE ROOF DECK NAILING DIAGRAM AND FASTENER TYPE AND
 SPACING.
  
 PROVIDE INSULATION ATTACHMENT.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By awooten Date 2019-08-14 Time   Rev Time 0.00
Received By awooten Date 2019-08-14 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-09 Cont ID  
Sent By awooten Date 2018-07-09 Time 10:39 Rev Time  
Received By awooten Date 2018-07-09 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved