Plan Review Details - Permit 18061475
Plan Review Stops For Permit 18061475
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By dbattles Date 2018-07-23 Time 08:52 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 10:00 Sent To  
Notes
2018-07-23 08:54:19W.P.B. PERMIT: 18061475
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 109.3]COST EVALUATION OF $50,000.00 SEEMS LOW.
 OUR REVIEW/INSPECTION FEES WILL BE BASED ON INDUSTRY
 STANDARDS. PLEASE HAVE THE ARCHITECT PREPARE COST
 ESTIMATE BASED ON INDUSTRY STANDARD COST OF WORK AS IF
 BEING DONE BY GENERAL CONTRACTOR.
  
 2. [FBC R105.15]DOES THE HOUSE CURRENTLY HAVE HURRICANE
 PROTECTION FOR THE OPENINGS? PLEASE PROVIDE THE TYPE OF
 PROTECTIONS AND SUPPORTING DOCUMENTATION TO SHOW THAT
 IT MEETS WIND CODE REQUIRMENTS.
  
 3. [FBC 107.3.5.3]PROVIDE AREA OF WORK BEING PERFORMED.
 IF >50% OF TOTAL AREA AFFECTED THAN CHANGE TO LEVEL 3
 ALTERATION.
  
 4. PROVIDE PRODUCT APPROVALS FOR ROOF WORK, OR INDICATE
 THAT THEY WILL BE DEFFERED UNTIL ROOF SUB PERMIT IS
 SUBMITTED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By jpearson Date 2018-07-16 Time 18:01 Rev Time 0.00
Received By jpearson Date 2018-07-16 Time 17:27 Sent To  
Notes
2018-07-16 18:01:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. ELECTRICAL NOTE 2 IS NOT CODE COMPLIANT FOR AFCI
 PROTECTION. NOTE THAT SOME AREAS WILL REQUIRE AFCI AND
 GFCI PROTECTION. PER CODE, ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. NOTE 4 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. LIGHTING FOR CLOSETS DOES NOT STATE IF THE LIGHT
 SOURCE IS ENCLOSED. PER CODE: LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE NOTE TO COMPLY. NEC 410.16; FBC RE E4003.12
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION, INCLUDING FOR WASHER. PROVIDE
 CORRECTION. NEC 210.8(A)(9); FBC RE E3902.9
 7. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 9. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By lcrespo Date 2018-08-07 Time 15:17 Rev Time 0.00
Received By lcrespo Date 2018-08-07 Time 14:48 Sent To  
Notes
2018-08-07 15:18:4908/07/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS. PLEASE SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS RES SECS.
 G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC.
 G2420.4.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1.
 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 RES. SEC. G2413.
 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 RANGE, 2017 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4.
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS RES. SEC. G2413.2.
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES.
 SECS. G2426 THRU G2429.1
 10. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
 11. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (FIREPLACE, TANKLESS AND RANGE) TO VERIFY COMPLIANCE
 WITH 2017 FBC FUEL GAS RES. SEC. G2408.1.
 12. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR
 FIREPLACE PER 2017 FBC FUEL GAS SECS. 502 THRU 505 OR
 2017 FBC FUEL GAS RES. SECS. G2426 THRU G2429.1
 13. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION
 SHALL BE ON SITE AT TIME OF INSTALLATION.
 14. ON BOTH COPIES OF A HOUSE PLAN SHOW THE LOCATION OF
 THE TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE
 OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE
 WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 15. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, WHERE APPLICABLE AND SHALL BE ON SITE,
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 16. A ELECTRICAL OUT MAY BE REQUIRED FOR SOURCE OF
 IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 17. A SEPARATE GAS PERMIT SHALL BE REQUIRED, FBC WPB A
 107.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By fmittner Date 2018-07-19 Time 10:40 Rev Time 0.00
Received By fmittner Date 2018-07-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By cpuell Date 2018-08-21 Time 15:27 Rev Time 0.00
Received By cpuell Date 2018-06-29 Time 16:27 Sent To  
Notes
2018-09-26 10:16:38PLANS ARE IN LARGE DRAWER UNDER L
  
2018-07-02 16:27:33R34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 14:47 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 14:47 Sent To  
Notes
2018-08-21 14:48:24[FBC AMENDED 109] PLANS REQUIRE REVIEW BY THE PBC
 IMPACT FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL,
 YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE
 FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF
 THE RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By hmoser Date 2018-07-30 Time 15:18 Rev Time 0.00
Received By hmoser Date 2018-07-30 Time 14:38 Sent To  
Notes
2018-07-30 15:11:39PLAN DENIED
 1) REFER TO SECTION M1503.4 MAKE UP AIR. PROVIDE
 MANUFACTURES INSTALLATION INSTRUCTIONS WITH THE PLAN.
 2) REFER TO SECTION M1803.3 INSTALLATION. MANUFACTURERS
 INSTALLATION INSTRUCTIONS FOR VENT LESS FIRE PLACE
 REQUIRED FOR PLAN REVIEW AND FIRST MECHANICAL ROUGH.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 14:52 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 14:50 Sent To  
Notes
2018-08-21 14:52:39THRESHOLD NOT REACHED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By lcrespo Date 2018-08-07 Time 15:19 Rev Time 0.00
Received By lcrespo Date 2018-08-07 Time 14:16 Sent To  
Notes
2018-08-07 16:04:2508/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON P-02 ON YOUR ISOMETRIC DRAWING THE WASHING
 MACHINE DRAIN CANNOT COME OFF THE LAV ARM INTO A DOUBLE
 SANITARY TEE 2017 FBC R3005.1.1 HORIZONTAL TO VERTICAL
 (MULTIPLE CONNECTION FITTINGS), IT MAY COME OFF THE
 TRUNK LINE DOWNSTREAM FROM BATHROOM GROUP IN MOST
 WASHING MACHINE IT MAY REQUIRE A 3? DRAIN PER
 MANUFACTURES SPECIFICATION.
 2. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC
 R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE,
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
 3. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
 4. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH
 ONE OF THE FOLLOWING MATERIALS:
 PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D4068 OR
 ASTM D4551.
  
 THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 2 INCHES
 (51 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS
 THAN 2 INCHES (51 MM) ABOVE FINISHED THRESHOLDS.
 SHEET-APPLIED LOAD BEARING, BONDED WATERPROOF MEMBRANES
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 14:49 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 14:49 Sent To  
Notes
2018-08-21 14:50:31PRODUCT APPROVALS REQUESTED IN BUILDING COMMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By fmittner Date 2018-07-19 Time 10:40 Rev Time 0.00
Received By fmittner Date 2018-07-19 Time 10:40 Sent To  
Notes
***NONE***