Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By jgomez Date 2018-07-02 Time 16:02 Rev Time 0.00
Received By jgomez Date 2018-07-02 Time 14:50 Sent To  
Notes
2018-07-02 16:12:40RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ACCORDING TO PICTURES SUBMITTED. THE ROOF NEEDS TO
 BE RECONSTRUCTED. PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR THE RECONSTRUCTION OF THE THE ROOF.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) L FOR THE
 FINISHED ROOFING TO BE INSTALLED. SHINGLES?. NOTE:
 SPECIFY ROOF PITCH.
 FAC 61G20-3.001.
  
 3- THE PROPOSED SCOPE OF WORK REQUIRES TWO DIFFERENT
 PERMIT APPLICATION. ONE FOR BUILDING FOR THE FRAMING OF
 THE ROOF. AND, ONE ROOFING FOR THE INSTALLATION OF THE
 ROOF FINISH. COMPLETE A SEPARATE PERMIT APPLICATION FOR
 ROOFING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  