| 2018-07-19 09:26:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18061451 |
| | 7/19/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COMPLETE FIRE SUPPRESSION LAYOUT DRAWINGS |
| | THAT INCLUDES THE FOLLOWING DETAILS AND NOTES: |
| | |
| | A) UL LISTING AND CODE COMPLIANCE DATA FOR THE SYSTEMS |
| | |
| | B) PIPING RUNS, PIPE SIZES, TYPES OF PIPING. |
| | |
| | C) LOCATIONS OF ANSUL TANKS AND TANK SIZES. |
| | |
| | D) LOCATIONS AND TYPES OF SUPPRESSION NOZZLES AND |
| | POINTS ASSOCIATED WITH EACH, AND TOTAL POINTS ALLOWED |
| | AND TOTAL USED. |
| | |
| | E) LOCATION OF GAS VALVE. |
| | |
| | F) LOCATION OF MANUAL PULL STATION |
| | |
| | G) SEQUENCE OF OPERATION |
| | |
| | 2) THE SUBMITTED PLAN WAS NOT SIGNED BY THE DESIGNER. |
| | PLEASE NOTE THAT ALL PLANS MUST BEAR THE SIGNATURE OF |
| | THE FL. LICENSED DESIGN PROFESSIONAL OR CONTRACTOR |
| | RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB. |
| | |
| | 3) THE $3500.00 VALUE FOR THE PROPOSED FIRE SUPPRESSION |
| | SYSTEMS IS A LOW VALUE FOR THE SYSTEMS. PROVIDE A |
| | CONTRACT AND/OR DETAILED ESTIMATES INVOICES TO VERIFY |
| | THE TOTAL COST WHICH SHALL INCLUDE LABOR, MATERIALS, |
| | EQUIPMENT, DESIGN FEES, OVERHEAD AND PROFIT- SECTION |
| | 109.3 WPB. PLEASE NOTE THAT FIRE SUPPRESSION SYSTEMS |
| | EXCEEDING AT TOTAL VALUE OVER $5000.00 SHALL HAVE |
| | CONSTRUCTION DOCUMENTS PREPARED BY, OR UNDER THE |
| | DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471, |
| | FLORIDA STATUTES- SECTION 105.3.1.2(4) WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |