Plan Review Details - Permit 18061379
Plan Review Stops For Permit 18061379
Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-09-07 Cont ID  
Sent By RRossano Date 2018-09-06 Time   Rev Time 2.00
Received By rrossano Date 2018-09-05 Time   Sent To M
Notes
2018-09-07 10:06:47PASSED WITH PROVISOS:
  
 CALL 811 BEFORE YOU DIG. PRE-CONSTRUCTION CONFERENCE
 WILL BE REQUIRED WITH ENGINEERING DEPARTMENT.
  
 FOR WORK IN ROW PLEASE SUBMIT RIGHT OF WAY APPLICATION
 AS SHOWN ON THE FOLLOWING WEBPAGE: HTTP://WPB.ORG/DEPAR
 TMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICAT
 IONS
  
 SEE APPROVED MATERIAL LIST ON THE FOLLOWING WEBPAGE: HT
 TP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS
 ,-PERMITS-APPLICATIONS
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By RRossano Date 2018-08-21 Time   Rev Time 1.00
Received By rrossano Date 2018-08-20 Time   Sent To M
Notes
2018-08-21 07:31:19PLANS ARE BEING DENIED DUE TO OUTSTANDING COMMENTS AT
 CITY OF WEST PALM BEACH ENGINEERING DEPARTMENT REVIEW
 E18010007. THERE ARE OUTSTANDING ITEMS, PLEASE CONTACT
 THE ENGINEERING DEPARTMENT OF FURTHER INFORMATION OR
 COMMENTS. ASLO, PROVIDE SPECIFICATION SHEET FOR DCDA
 BACKFLOW PREVENTION CALLING OUT LEAD-FREE DESIGN.
  
 THANKS,
  
 RICK ROSSANO
 PROJECT COORDINATOR
 WPB ENGINEERING SERVICES
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 CELL: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By RRossano Date 2018-07-23 Time   Rev Time 0.50
Received By rrossano Date 2018-07-23 Time   Sent To M
Notes
2018-07-23 14:43:11RESPOND TO COMMENTS IN WRITING.
  
 #1: RESPOND TO FIRE COMMENTS.
 #2: PROJECTIS UNDER REVIEW AT ENGINEERING SERVICES.
 #3: PROVISO: BACKFLOWS TO BE LEAD-FREE AND USC
 APPROVED.
 #4: PROVIDE SPECIFICATION DETAIL SHEET FOR DCDA
 BACKFLOW ASSEMBLY SHOWING MODEL AMES 3000SS AS SHOWN ON
 SUBMITTED FIRE PROTECTION REPORT; HOWEVER, IT IS NOT
 SPECIFIED AS A LEAD-FREE APPARATUS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 WPB ENGINEERING SERVICES
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-05 Cont ID  
Sent By pleduc Date 2018-09-05 Time   Rev Time 0.00
Received By pleduc Date 2018-09-05 Time 12:41 Sent To ENG
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-08-17 Cont ID  
Sent By pleduc Date 2018-08-17 Time   Rev Time 0.00
Received By pleduc Date 2018-08-15 Time 12:09 Sent To ENG
Notes
2018-08-17 15:50:172ND REVIEW COMMENTS:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE PLAN SETS APPEAR TO BE INCOMPLETE.
  
 I DO NOT KNOW WHICH ONES SHOULD BE VOIDED AND WHICH ONE
 SUBMIITTED.
  
 THERE ARE SHEETS 1 OF 3 MISSING ON THE SET I BELIEVE
 ARE THE PROPER ONES.
  
  
 PLEASE REVIEW AND ENSURE THE VIODED SHEETS ARE
 INDICATED AND ALL SHEETS ARE CONTAINED ON THE PROPER
 ONES AND THAT THEY ARE BOUND TOGETHER TO AVOID
 CONFUSION.
  
  
  
  
 2) THE RESPONSE OF MY ORIGINAL COMMENT 1 WAS THAT THE
 PE SEAL ISSUE HAS BEEN CORRECTED.
  
 THE SHEETS I BELIEVE TO BE THE PROPER ONES HAS THE SAME
 PE SEAL AS THE ORIGINA,L ONLY WITH ANOTHER DATE.
  
 IS THIS THE INTENT OF YOUR RESPONSE COMMENT OR IS THE
 SEAL SUPPOSED TO BE REMOVED.
  
 PLEASE CLARIFY.
  
  
  
 3) IT REMIANS UNCLEAR WHICH 20 HEADS REPRESENT AREA 1.
  
 PLEASE INDICATE WITH BOUNDARY LINES AND/OR CLOUDS
 WITHIN THE FLOOR PLAN WHERE THE AREA IS AND EXACTLY
 WHAT HEADS ARE REPRESENTED.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By pleduc Date 2018-07-10 Time   Rev Time 0.00
Received By pleduc Date 2018-07-10 Time 12:14 Sent To ENG
Notes
2018-07-10 12:25:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THESE SHOP DRAWINGS HAVE A PE STAMP AND SEAL. I
 COULD NOT VERIFY IF THIS PE WAAS THE SAME ONE AS THE
 MASTER. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE
 AND NO RESPONSE TO EMAIL X 10 DAYS.
  
 THERE CAN ONLY BE ONE PE RESPONSIBLE FOR THE ENGINEERED
 DRAWINGS UNLESS EXPRESSLY DELEGATED BY THE MASTER PE.
  
 VERIFY THE SAME PE OF REMOVE STAMP AND SEAL.
  
  
  
 2) THERE IS FIRE LINE UNDERGROUND INDICATED; HOWEVER, I
 COULD NOT VERIFY FL CONTRACTOR I, II OR V ON THE STATE
 WEBSITE. CALLED TO VERIFY WITH THE PHONE OUT OF SERVICE
 AND NO RESPONSE TO EMAIL X 10 DAYS.
  
 PROVIDE VALID FL LICENSE FOR UNDERGROUND CONTRACTOR
 WORK.
  
  
  
 3) A REMOTE AREA 1 IS INDICATED ON THE HYDRAULIC SHEET;
 HOWEVER, IT IS NOT INDICATED ON THE PLAN DRAWINGS.
  
 PROVIDE THE LOCATION AND DIMENSIONS OF THE REMOTE AREA
 1 ON THE DRAWING SHEETS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-09-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-31 Time 15:29 Sent To  
Notes
2018-09-04 15:29:57RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-08-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-13 Time 15:41 Sent To  
Notes
2018-08-14 15:41:16RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-24 Time   Rev Time 0.00
Received By cpuell Date 2018-06-28 Time 11:33 Sent To FIRE
Notes
2018-06-29 11:33:48TRAVELLING WITH 18061379

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-09-14 Cont ID  
Sent By ccole Date 2018-09-14 Time 15:02 Rev Time 0.00
Received By ccole Date 2018-09-14 Time 14:50 Sent To I
Notes
2018-09-14 15:03:48MECHANICAL PROVISO:
  
 SEPARATE PERMIT REQUIRED FOR THE BACKFLOW PREVENTER.
  
 CCOLE- 9/14/18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 07:49 Rev Time 0.00
Received By ccole Date 2018-08-23 Time 17:22 Sent To I
Notes
2018-08-24 07:56:042ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18061379
 8/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO FIRE DEPT. COMMENTS AND PROVIDE COMPLETE
 PLAN SETS FOR REVIEW. IT APPEARS THAT SHEET 1 OF 3 IS
 MISSING FROM THE NEW SHEETS 2 & 3 SETS THAT WERE
 SIGNED, SEALED AND DATED BY THE ENGINEER ON 8/11/18.
 SEE ADVISORY NOTE BELOW:
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By ccole Date 2018-07-24 Time 13:02 Rev Time 0.00
Received By ccole Date 2018-07-24 Time 12:59 Sent To I
Notes
2018-07-24 13:06:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061379
 7/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER. THE DEVICE SHALL COMPLY WITH THE CITY OF
 WEST PALM BEACH UTILITIES DEPARTMENT CROSS-CONNECTION
 CONTROL MANUAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  