| Plan Review Stops For Permit 18061378 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-13 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-13 |
Time |
06:27 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-07-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-28 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-28 |
Time |
11:53 |
Sent To |
I |
|
| Notes |
| 2018-07-28 12:10:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SATISFY NOTES FROM FIRE DEPARTMENT. | | | | | | INFORMATIONAL NOTE: SEPARATE ELECTRICAL PERMIT WILL BE | | | REQUIRED BY LICENSED ELECTRICIAN FOR 120V | | | CIRCUIT/CONNECTION FACP, OUT OF SCOPE FOR EF LICENSE. | | | FBC 105.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-10 |
Time |
|
Rev Time |
|
| Received By |
pleduc |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-10 12:32:41 | FAILED BY PML DUE TO NO PLANS ATTACHED. THIS | | | APPLICATIONRIDING WITH FS 18061379. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-08-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-08-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-08-07 |
Time |
16:22 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-25 |
Time |
10:46 |
Sent To |
E |
|
| Notes |
| 2018-07-26 14:14:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET FA 2 - THERE IS A HEAT DETECTOR INDICATED IN | | | EACH KITCHEN. THE TEMPATURE RATING APPEARS TO BE 135* . | | | | | | WITH THE BUILDIDNG PROTECTED THROUGHOUT WITH FIRE | | | SPRINKLERS: | | | | | | A) WHAT IS THE TEMPURATURE OF THE FIRE SPRINKLER IN | | | THIS AREA? | | | | | | B) WHAT IS THE PURPOSE OF THIS HEAT DETECTOR? | | | | | | PLEASE REVIEW AND PROVIDE DETAILS AND JUSTIFICATION FOR | | | PLACING THE HD IN THE KITCHEN. | | | | | | | | | | | | | | | 2) SHEET FA 2 - THERE IS ONLY ONE SD INDICATED IN THE | | | MIDDLE OF TWO BEDROOMS. THOUGH THERE IS ONE DOOR | | | LEADING TO THESE BEDROOMS AREAS THERE ARE TWO DISTICT | | | AND SEPARATED BEDROOMS. | | | | | | PER NFPA 101, CHAPTER 32 NEW RESIDENTIAL BOARD AND CARE | | | OCCUPANCIES | | | | | | 32.2.3.4.3.4 EACH SLEEPING ROOM SHALL BE PROVIDED WITH | | | AN | | | APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.10. | | | | | | WHERE THE ROOMS ARE SEPARATED BY WALLS INTO TWO | | | SEPARATE SLEEPING AREAS, EACH AREA SHALL HAVE A SD. | | | | | | | | | | | | 3) FIRE SPRINKLER HYDRAULIC PLANS WERE INCLUDED WITH | | | THE PLAN SETS AND NOT REPLATED TO THE PERMIT | | | APPLICATION. | | | | | | PLEASE REMOVE THEM FROM THE PALN SET OF JUSTIFY . | | | | | | | | | | | | | | | 4) SHEET FA 2 - THERE IS ONLY A HD INDICATED IN | | | THELAUNDRY ROOM. | | | | | | WITH THE BUILDIDNG PROTECTED THROUGHOUT WITH FIRE | | | SPRINKLERS: | | | | | | A) WHAT IS THE TEMPURATURE OF THE FIRE SPRINKLER IN | | | THIS AREA? | | | | | | B) WHAT IS THE PURPOSE OF THIS HEAT DETECTOR? | | | | | | PLEASE REVIEW AND PROVIDE DETAILS AND JUSTIFICATION FOR | | | PLACING THE HD IN THE LAUNDRY ROOM | | | | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-02 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2018-07-10 12:31:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE WERE NO FIRE ALARM DRAWINGS ATTACHED TO THIS | | | APPLICATION. A CALL TO THE PHONE NUMBER INDICATED IT | | | WAS DISCONNETED, TRIED EMAIL WITH NO CONTACT X 10 DAYS. | | | | | | | | | | | | 2) THIS APPLICATION WAS RDING WITH FS 18061379 AND WAS | | | SENT TO ENG. | | | | | | FAILED WAS ENTERED IN ELECTRICAL AND MECHANICAL DUE TO | | | THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-08-13 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-08-06 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2018-08-07 14:00:48 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-08-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-07-16 |
Time |
14:45 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-07-24 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-06-28 |
Time |
11:29 |
Sent To |
FIRE |
|
| Notes |
| 2018-06-29 11:33:16 | TRAVELLING WITH 18061379 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-01 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-01 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-10 |
Time |
|
Rev Time |
|
| Received By |
pleduc |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-10 12:32:58 | FAILED BY PML DUE TO NO PLANS ATTACHED. THIS | | | APPLICATIONRIDING WITH FS 18061379. |
|
|