Plan Review Details - Permit 18061371
Plan Review Stops For Permit 18061371
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 13:42 Rev Time 0.00
Received By dbattles Date 2018-10-19 Time 13:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-01 Cont ID  
Sent By dbattles Date 2018-08-01 Time 16:24 Rev Time 0.00
Received By dbattles Date 2018-08-01 Time 13:31 Sent To  
Notes
2018-08-01 16:25:10****CORRECTIONS****
 W.P.B. PERMIT: 18061371
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, DOORS AND SHUTTER SYSTEMS, OR INDICATE THAT
 YOU WOULD LIKE THEM DEFFERED.
  
 2. [FBC 107.3.5.3]PROVIDE +/- PRESSURES FOR ALL
 OPENINGS BASED ON DESIGN CRITERIA .
  
 3. IS THE ROOF BEING REPLACED. IF SO, PROVIDE PRODUCT
 APPROVALS.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-11 Time 15:05 Rev Time 0.00
Received By jpearson Date 2018-12-10 Time 13:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 08:29 Rev Time 0.00
Received By jpearson Date 2018-09-25 Time 16:30 Sent To  
Notes
2018-09-26 08:29:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED, SHOWN ON PERMIT 15070145.
 5. CORRECTED, SHOWN ON PERMIT 15070145.
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOTE 3
 ON SHEET E-3 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14)
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (NOTE 2 ON
 SHEET E-3 DOES NOT INCLUDE THE ALL AREAS REQUIRED TO BE
 AFCI PROTECTED. PROVIDE CORRECTION.)
 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (THIS NOTE WAS ADDED TO SHEET
 E-2, BUT A CONFLICTING NOTE EXIST ON SHEET E-3. CORRECT
 DISCREPANCY. WPB FBC 107.2.1)
 9. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 (LOAD CALCULATION WAS PROVIDED ONLY FOR GARAGE PANEL,
 NOT ENTIRE SERVICE. BE ADVISED THAT DEMAND FACTORS USED
 CANNOT BE APPLIED TO THE GARAGE PANEL AS IT IS NOT FEED
 BY A 100 AMP FEEDER. NEC 220.82; FBC RE3602.2.1.
 ADDITIONALLY, UPON RESEARCHING PERMIT 15070145, I SEE
 THAT THE STATED LOAD ON THE SERVICE IS 175 AMPS, WITH
 10 AMPS INCLUDED FOR THE GARAGE. NOW, WITH THE
 ADDITIONAL LOAD OF THE GARAGE, BASED ON THESE NUMBERS
 AND THE PROPER CALCULATION FOR THE GARAGE PANEL, THE
 SERVICE WILL BE OVERLOADED. PROVIDE CORRECTION AND
 PROVIDE ACCURATE LOAD CALCULATION AS PREVIOUSLY
 REQUESTED. NEC 220; FBC RE 3602)
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. AN ARCHITECT HAS SIGNED AND SEALED THE "E" SHEETS.
 PROVIDE CORRECTION. FS 471.003(2)(H), 471.025; WPB FBC
 107.1
 12. THE CABANA MEETS THE DEFINITION OF A BEDROOM IN THE
 FLORIDA STATUTES AND SHOULD HAVE A SMOKE ALARM
 INSTALLED. FS 381.0065; FBC RE R314.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 14:22 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 12:50 Sent To  
Notes
2018-07-26 14:15:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 9. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 10. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By fmittner Date 2018-10-19 Time 14:29 Rev Time 0.00
Received By fmittner Date 2018-10-19 Time 14:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-07-09 Cont ID  
Sent By destabro Date 2018-07-09 Time 14:40 Rev Time 0.00
Received By destabro Date 2018-07-09 Time 14:40 Sent To B
Notes
2018-07-09 14:40:387/9/2018 - MEETS CONDITIONS OF APPROVAL OUTLINED IN HPB
 CASE NO. 18-36. DLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-12-28 Cont ID  
Sent By dbattles Date 2018-12-28 Time 08:19 Rev Time 0.00
Received By dbattles Date 2018-12-26 Time 11:43 Sent To  
Notes
2018-12-27 11:44:13IMPACT FEES ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 15:05 Rev Time 0.00
Received By dbattles Date 2018-12-07 Time 11:27 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 14:34 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 11:01 Sent To  
Notes
2018-09-13 11:01:49R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 15:01 Rev Time 0.00
Received By dbattles Date 2018-06-28 Time 16:13 Sent To  
Notes
2018-06-28 16:13:58R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-28 Cont ID  
Sent By dbattles Date 2018-12-28 Time 08:18 Rev Time 0.00
Received By dbattles Date 2018-12-28 Time 08:17 Sent To  
Notes
2018-12-28 08:18:54PLANS STAMPED - OK
 MU-2018-041791-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 15:05 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 15:05 Sent To  
Notes
2018-12-11 15:09:06PLEASE CHECK OUT ONE SET OF PLANS TO TAKE TO PALM BEACH
 COUNTY FORI IMPACT REVIEW.
 RETURN THE PLANS WITH PBC STAMP AND COPY OF RECEIPT.
  
 [FBC AMENDED 109] PLANS REQUIRE REVIEW BY THE PBC
 IMPACT FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL,
 YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE
 FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF
 THE RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By dbattles Date 2018-08-21 Time 15:01 Rev Time 0.00
Received By dbattles Date 2018-08-21 Time 15:01 Sent To  
Notes
2018-08-21 15:01:23[FBC AMENDED 109] PLANS REQUIRE REVIEW BY THE PBC
 IMPACT FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL,
 YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE
 FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF
 THE RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By cmontell Date 2018-10-11 Time 14:02 Rev Time 0.00
Received By cmontell Date 2018-10-11 Time 13:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-03 Cont ID  
Sent By cmontell Date 2018-08-03 Time 14:53 Rev Time 0.00
Received By cmontell Date 2018-08-03 Time 14:53 Sent To  
Notes
2018-08-03 14:41:26MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL LOAD CALCULATIONS PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. M1401.3 EQUIPMENT AND
 APPLIANCE SIZING

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By fmittner Date 2018-10-19 Time 14:29 Rev Time 0.00
Received By fmittner Date 2018-10-19 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-09 Cont ID  
Sent By destabro Date 2018-07-09 Time 14:39 Rev Time 0.00
Received By destabro Date 2018-07-09 Time 14:39 Sent To HIST
Notes
***NONE***