Plan Review Details - Permit 18061260
Plan Review Stops For Permit 18061260
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-24 Cont ID  
Sent By dbattles Date 2019-01-24 Time 13:15 Rev Time 0.00
Received By dbattles Date 2019-01-24 Time 13:15 Sent To  
Notes
2019-01-24 13:25:23PROVISO:
 SUBMITTAL FOR METAL STAIR, HANDRAIL AND GUARDS TO BE
 PROVIDED .
  
 ASCE 7-10 SECTION 4.5.1 LOADS ON HANDRAIL AND GUARDRAIL
 SYSTEMS. ALL HANDRAIL AND GUARDRAIL SYSTEMS SHALL BE
 DESIGNED TO ESIST A SINGLE CONCENTRATED LOAD OF 200 LB
 APPLIED IN ANY DIRECTION AT ANY POINT ON THE HANDRAIL
 OR TOP RAIL AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. FURTHER, ALL HANDRAILS AND
 GUARDRAIL SYSTEMS SHALL BE DESIGNED TO RESIST A LOAD OF
 50 POUND-FORCE PER LINEAR FOOT APPLIED IN ANY DIRECTION
 ALONG THE HANDRAIL OR TOP RAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 15:16 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By dbattles Date 2018-08-10 Time 14:13 Rev Time 0.00
Received By dbattles Date 2018-08-10 Time 14:13 Sent To  
Notes
2018-08-10 14:15:06****CORRECTIONS****
 W.P.B. PERMIT: 18061260
 REVIEWED: AUGUST 10, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATION FOR 2 STORY
 STRUCTURE.
  
 2. [FBC ENERGY TABLE R402A]FLOOR BETWEEN GARAGE SHOULD
 BE R13. PLEASE ADD TO ENERGY FORM R402-2017.
  
 3. RE-PRINT 2 COPIES OF FL5684-R8. THE COPIES PROVIDED
 AREN?T LEDGIBLE AFTER THE FIRST COUPLE OF PAGES.
  
 4. [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
  
 5. [R302.6]GARAGE CEILING TO HAVE TYPE NOT LESS THAT
 5/8? TYPE X OR EQUIVELANT DRYWALL WHEN HABITABLE SPACE
 IS PROVIDED ABOVE.
  
 6. [FBC R506.2.3] A 6-MIL (0.006 INCH; 152 ?M)
 POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS
 LAPPED NOT LESS THAN 6 INCHES.
  
 PROVISO:
 PROVIDE ROOF TRUSS ENGINEERING SUBMITTAL PRIOR TO
 INSTALLATION.
 PROVIDE STAIR AND RAIL ENGINEERING SUBMITTAL PRIOR TO
 INSTALLATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-03 Cont ID  
Sent By jpearson Date 2019-02-03 Time 11:09 Rev Time 0.00
Received By jpearson Date 2019-02-03 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-26 Cont ID  
Sent By ppetty Date 2018-10-26 Time 11:47 Rev Time 0.00
Received By ppetty Date 2018-10-26 Time 09:13 Sent To  
Notes
2018-10-26 11:46:11 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.OK
 2.OK
 3. OK
 4.OK
 5.OK
 6.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, NEC 215.5, 230, 250.50,
 250.94, 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB
 FBC 107.2.1.
 7.OK
 8.OK
 9.
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 10. PROVIDE DETAIL OF MAINS, GROUPED IN ONE LOCATION.
 NEC 230.72
 11.OK
 12.OK
 13.OK
 14.OK
 15.OK
 16.FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 17.PARALLEL PATH IN SERVICE RACEWAYS 250.6
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By ppetty Date 2018-07-30 Time 13:45 Rev Time 0.00
Received By ppetty Date 2018-07-30 Time 13:45 Sent To  
Notes
2018-07-30 13:19:54 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. SOME AREAS REQUIRE AFCI AND GFCI
 PROTECTION. NEC 210.8, 210.12; FBC RE E3902
 2.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9
 3. PROVIDE GFCI PROTECTION FOR DISPOSAL RECEPTACLE
 OUTLET WHEN INSTALLED WITHIN 6 FEET OF SINK. NEC
 210.8(A)(7); FBC RE E3902.73.
 4.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 5.PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 6.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1.
 7. PROVIDE TAMPER RESISTANT RECEPTACLES. NEC 406.12
 8.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. SMALL APPLIANCE CIRCUITS SHOULD BE
 CALCULATED AT 1500 VOLT AMPS EACH.NEC 215.2, 220,
 408.30; FBC RE E3602.2
 9.A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 10. PROVIDE DETAIL OF MAINS, GROUPED IN ONE LOCATION.
 NEC 230.72
 11. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 12. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 13.W/H CIRCUT HAS 60A BKR ON #10 WIRE.PROVIDE
 CORRECTION. NEC 310.15(B) (16).
 14. PROVIDE LOCATION OF PANEL ON PLAN.WPB FBC 107.2.1
 15. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-25 Cont ID  
Sent By jduprey Date 2019-02-25 Time 10:40 Rev Time 0.00
Received By jduprey Date 2019-02-25 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-19 Cont ID  
Sent By hmoser Date 2019-02-19 Time 15:51 Rev Time 0.00
Received By hmoser Date 2019-01-15 Time 15:52 Sent To  
Notes
2019-02-16 10:00:312/16 IN HM OFFICE
  
2019-01-16 15:52:52R15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-02 Cont ID  
Sent By cpuell Date 2018-12-02 Time 08:45 Rev Time 0.00
Received By cpuell Date 2018-10-02 Time 10:19 Sent To  
Notes
2018-10-11 16:24:38R12
2018-10-04 10:19:54LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 19:55 Rev Time 0.00
Received By lcrespo Date 2018-06-26 Time 14:50 Sent To  
Notes
2018-06-27 14:50:14R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By jduprey Date 2019-02-25 Time 10:32 Rev Time 0.00
Received By jduprey Date 2019-02-25 Time 10:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By dbattles Date 2018-08-10 Time 14:23 Rev Time 0.00
Received By dbattles Date 2018-08-10 Time 14:23 Sent To  
Notes
2018-08-10 14:23:58[FBC 109] PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE
 OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By hmoser Date 2019-02-19 Time 15:50 Rev Time 0.00
Received By hmoser Date 2019-02-19 Time 15:50 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By hmoser Date 2018-10-29 Time 11:26 Rev Time 0.00
Received By hmoser Date 2018-10-29 Time 10:14 Sent To  
Notes
2018-10-29 11:26:31PLAN DENIED
 REFER TO SECTION R403.7 HEATING AND COOLING EQUIPMENT.
 2017 FLORIDA ENERGY CODE ( PROVIDE ENERGY CALCULATIONS)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 09:53 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 08:59 Sent To  
Notes
2018-08-04 09:53:32PLAN DENIED
 1) REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING
 2017 RESIDENTIAL CODE
 2) MISSING DUCT SIZE ON BATHROOM SUPPLY DUCT. SECTION
 107 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-29 Cont ID  
Sent By gjohnson Date 2019-01-29 Time 08:58 Rev Time 0.00
Received By gjohnson Date 2019-01-29 Time 08:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-06 Cont ID  
Sent By jesmith Date 2018-11-06 Time 15:16 Rev Time 0.00
Received By jesmith Date 2018-11-06 Time 15:16 Sent To  
Notes
2018-11-06 15:16:39PLUMBING COMMENTS: APPROVED
 PROVISO
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE. BACKFLOW PREVENTER REQUIRED PER THE
 CITY OF WEST PALM BEACH ORD #2853-95. PLEASE CONTACT
 CITY OF WPB UTILITIES AT 561-822-2240 FOR FURTHER
 DIRECTIONS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 EMAIL: [email protected]
 PHONE: 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 19:54 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 19:54 Sent To  
Notes
2018-08-22 19:55:2208/22/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ISOMETRIC SHOWS KITCHEN SINK TIED TO A BATHROOM
 GROUP, IT SHALL RUN DOWNSTREAM OF THE BATHROOM GROUP.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. RELIEF LINE SHALL DUMP INTO PAN DRAIN AND PAN DRAIN
 SHALL TERMINATE OUTSIDE. 2017 FBC R 2801.6.2
 3. THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE LINING
 FBC R 2709.2 LINING REQUIRED.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOES NOT COVER THEM PER MANUFACTURES
 SPECIFICATIONS.
  
 4. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY
 FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL
 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO
 BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN
 THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012. NEACA
 HOT WATER REGULATION 2015 AND IT SHOULD BE AT EF 0.95,
 PLEASE VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-20
 15-REGULATIONS/ FOR FURTHER DETAILS.
  
 5. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. A
 BACKFLOW DEVICE MAY BE REQUIRED BY THE CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT CROSS CONNECTION MANUAL.
 A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND
 APPLICATION ALONG WITH CERTIFICATION BY UTILITIES WITH
 A FINAL INSPECTION WILL BE REQUIRED. CALL THE UTILITY
 DEPARTMENT FOR INFORMATION AT 561 822-2240.
  
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-11-09 Cont ID  
Sent By dbattles Date 2018-11-09 Time 15:11 Rev Time 0.00
Received By dbattles Date 2018-11-09 Time 15:11 Sent To  
Notes
2018-11-09 15:13:59PRODUCT APPROVAL-OK FOR SHINGLE ROOF
 NOTE ADDED TO PLANS FOR DOUBLE LAYER UNDERLAYMENT FOR
 3:12

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By dbattles Date 2018-08-10 Time 14:24 Rev Time 0.00
Received By dbattles Date 2018-08-10 Time 14:24 Sent To  
Notes
2018-08-10 14:25:21DOUBLE LAYER UNDERLAYMENT REQUIRED FOR 3:12
 SHINGLE TILE PRODUCT APPROVAL OK.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-14 Cont ID  
Sent By mcruz Date 2019-02-14 Time 13:11 Rev Time 0.00
Received By mcruz Date 2019-02-12 Time 11:06 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-30 Cont ID  
Sent By mcruz Date 2018-11-30 Time 16:27 Rev Time 0.00
Received By mcruz Date 2018-11-30 Time 16:09 Sent To PC
Notes
2018-11-30 16:27:05ZONING PASSED WITH PROVISO: KITCHEN AND 220 CONNECTIONS
 TO BE REMOVED. THIS IS A BEDROOM ADDITION NOT AN
 APARTMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By MC Date 2018-07-12 Time 13:43 Rev Time 0.00
Received By mcruz Date 2018-07-12 Time 12:56 Sent To  
Notes
2018-07-12 13:43:40ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) GARAGE APARTMENT IS NOT PERMITTED. WHILE THE ZONING
 DISTRICT ALLOWS FOR GARAGE APARTMENTS, THIS PROPERTY
 DOES NOT MEET THE MINIMUM LOT AREA OF 6,000 SQ. FT.
 REQUIRED TO ALLOW A GARAGE APARTMENT.
 2) INDICATE ON PLAN DIMENSION FROM PRINCIPAL STRUCTURE
 TO GARAGE. MUST BE AT LEAST 6 FEET.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]