Plan Review Details - Permit 18061230
Plan Review Stops For Permit 18061230
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 17:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-19 Time 17:04 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 15:11 Sent To I
Notes
2018-07-10 15:34:07PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM DESIGN PRESSURE FOR SYSTEM TYPE E(1)
 LISTED ON PAGE 47 OF NOA NO. 17-0824.09 IS -52.5 PSF.
 THIS IS NOT ADEQUATE FOR ROOF ZONES 2 AND 3. SUBMIT TWO
 SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 63 OF THE PRODUCT APPROVAL FOR THE INCREASED
 THE UPLIFT PRESSURES OF ROOF ZONES 2 AND 3,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-03 Cont ID  
Sent By rmcdouga Date 2018-07-03 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2018-07-03 Time 15:02 Sent To I
Notes
2018-07-03 14:45:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS FOR THE ASPHALT SHINGLES (NOA
 NO.14-1022.21) EXPIRED ON 4/22/18. SUBMIT THE CURRENT
 NOA FOR THE GAF SHINGLES. FBC 107.3.4
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5). PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR THE FLAT ROOF COVERING MATERIALS. IF
 ENHANCED FASTENING IS REQUIRED TO INCREASE THE UPLIFT
 PRESSURES FOR ROOF ZONES 2 AND 3, SUBMIT SIGNED AND
 SEALED RAS 117 CALCULATIONS.
  
 3) SPECIFY THE SQUARE FOOTAGE OF THE SLOPED ROOF AND
 THE FLAT ROOF. FBC 107.2.1

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By destabro Date 2018-07-10 Time 10:08 Rev Time 0.00
Received By destabro Date 2018-07-10 Time 10:08 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-07-02 Cont ID  
Sent By destabro Date 2018-07-02 Time 13:45 Rev Time 0.00
Received By destabro Date 2018-07-02 Time 13:45 Sent To I
Notes
2018-07-02 13:46:227/2/2018 - ASPHALT SHINGLE ROOF REPLACEMENT MEETS
 DESIGN GUIDELINES OF HISTORIC DISTRICT. DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-19 Cont ID  
Sent By rmcdouga Date 2018-07-19 Time 17:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-19 Time 17:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-10 Cont ID  
Sent By rmcdouga Date 2018-07-10 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2018-07-06 Time 13:54 Sent To  
Notes
2018-07-09 13:55:13RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-03 Cont ID  
Sent By rmcdouga Date 2018-07-03 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2018-06-26 Time 09:50 Sent To  
Notes
2018-06-27 09:51:11ROUTED TO HISTORIC INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved