| 2018-06-30 09:35:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| | 600.6(A)(1) |
| | |
| | 2. COMMENT THAT SIGN IS CONTROLLED BY PHOTOCELL AND |
| | TIMER SWITCH DOES NOT MEET REQUIREMENTS OF FBC CE |
| | 405.2.4 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| | FBC-EC 405.2.4 |
| | |
| | 3. UNABLE TO ISSUE SUB-ELECTRICAL PERMIT TO ES LICENSE. |
| | LICENSED ELECTRICIAN NEEDED (EC OR ER). DISCONNECT |
| | REQUIREMENTS OF 600.6A1 NEC AND ASTRONOMICAL TIMER |
| | REQUIREMENTS ARE NOT ABLE TO BE INSTALLED BY A ES |
| | LICENSED HOLDER, IT IS NOT WITHIN THEIR SCOPE OF WORK. |
| | PLEASE SEE SCOPE OF WORK FOR ES LICENSE. |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| | FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| | INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| | ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| | CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| | ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| | TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| | THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| | REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| | BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| | STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| | TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| | VOLTS MAXIMUM. |
| | |
| | 4. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT (BY |
| | OWNER AND CONTRACTOR) WITH SCOPE AND VALUE OF WORK, TO |
| | INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| | |
| | 5. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT |
| | CONSIDERED PHYSICALLY SIGNED ( NOTED DIRECTLY ON PLAN |
| | BY ENGINEER.) PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE |
| | THAT THE LICENSEE CREATE BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY |
| | CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS |
| | NOT ALLOWED ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED. |
| | |
| | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| | PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT |
| | THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| | SIGNATURE ILLEGIBLE. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |