| 2018-07-24 11:02:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PANEL MDP SHOWS A 600 AMP MAIN BREAKER WITH A 610 |
| | AMP LOAD. PROVIDE CLARIFICATION AND/OR CORRECTION. WPB |
| | FBC 107.2.1; NEC 408.30, 408.36, 215.2 |
| | 2. RISER DIAGRAM SHOWS PANEL MDP BEING FED FROM FPL |
| | TRANSFORMER, BUT ALSO FROM TRANSFER SWITCH. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. NEC 702.5; WPB FBC |
| | 107.2.1 |
| | 3. PROVIDE CUT SHEETS FOR POLES, CAMERAS, AND FIXTURES. |
| | WPB FBC 107.2.1; NEC 110.3 |
| | 4. PROVIDE VOLTAGE DROP CALCULATION FOR FEEDERS AND |
| | BRANCH CIRCUITS. FBC EC C405.6.3 |
| | 5. PROVIDE WIND LOAD RATING OF POLES. WPB FBC 107.2.1; |
| | FBC 1609; NEC 110.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |