Plan Review Details - Permit 18061156
Plan Review Stops For Permit 18061156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 12:04 Rev Time 0.00
Received By shill Date 2018-08-25 Time 12:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 11:35 Rev Time 0.00
Received By shill Date 2018-07-08 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-11 Cont ID  
Sent By fgiaquin Date 2018-08-11 Time 11:36 Rev Time 0.00
Received By fgiaquin Date 2018-08-11 Time 11:30 Sent To  
Notes
2018-08-11 11:36:40THIS PLAN HAS BEEN PASSED PROVISIONALLY:
  
 SUBMIT ACCURATE PANEL SCHEDULE SHOWING OCP AND PROPER
 WATTAGE BEFORE FINAL.
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-11 Cont ID  
Sent By fgiaquin Date 2018-07-11 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2018-07-11 Time 06:41 Sent To  
Notes
2018-07-11 06:51:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CLEAR LOCATION OF ELECTRICAL PANEL. PANEL
 APPEARS TO BE IN CLOSET ALONG WITH W/H AND AHU. PANEL
 APPEARS TO NOT HAVE THE REQUIRED WORKING CLEARANCE TO
 MEET NEC 110.26A1 & A2.
  
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE.
 OVERCURRENT PROTECTION, WIRE AND CONDUIT SIZE FOR
 EXISTING PANEL IN UNIT. NEC 215.5; WPB FBC 107.2.1
 VOLTAGE AT TRUMP TOWER IS BELIEVED TO BE 208V NOT 240V,
 WHICH WOULD CHANGE THE LOAD CALCULATION FROM 132.45AMPS
 TO 153AMPS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 10:46 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By tklarge Date 2018-08-28 Time 05:21 Rev Time 0.00
Received By tklarge Date 2018-08-08 Time 15:28 Sent To  
Notes
2018-08-25 12:04:308/25 TO TL DESK
  
2018-08-09 15:29:06RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 14:36 Rev Time 0.00
Received By tklarge Date 2018-06-25 Time 13:56 Sent To  
Notes
2018-06-26 13:56:40B02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-07-02 Cont ID  
Sent By ccole Date 2018-07-02 Time 14:39 Rev Time 0.00
Received By ccole Date 2018-07-02 Time 14:39 Sent To  
Notes
2018-07-02 14:43:43SEPARATE PERMIT FOR MECHANICAL- SEE NOTE ON SHEET 01.
 CCOLE-7/2/18

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By tklarge Date 2018-08-28 Time 05:21 Rev Time 0.00
Received By tklarge Date 2018-08-28 Time 05:02 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 14:36 Rev Time 0.00
Received By tklarge Date 2018-07-31 Time 13:10 Sent To I
Notes
2018-07-31 14:36:301) THE MINIMUM SIZE OF THE HORIZONTAL AND VERTICAL
 DRAIN FOR THE WASHING MACHINE SHALL BE A MINIMUM OF 3
 INCHES PER THE 2017 FBC-PLUMBING SEC.406.2.
 2) NEW TUB & SHOWER VALVES SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC. 424.3.
  
 NOTE: THIS STRUCTURE WAS BUILT IN 1986 SO FAIR HOUSING
 DOES NOT APPLY.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  