Plan Review Details - Permit 18061145
Plan Review Stops For Permit 18061145
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 14:58 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 14:58 Sent To  
Notes
2018-10-30 15:00:14****CORRECTIONS****
 W.P.B. PERMIT: 18061145
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. AN ADDRESS WILL NEED TO BE PROVIDED FOR LOT 42.
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
 1-2. PROVIDE DOCUMENTATION THAT THE PROPERTY HAS BEEN
 SUB DIVIDED WITH THE PALM BEACH COUNTY PROPERTY
 APPRAISER?S OFFICE.
 ALSO, PROVIDE THE NEW ADDRESS AND PUT IT ON THE
 DRAWINGS IF CHANGED FROM 1113 22ND.
  
 2. OK
  
 3. OK
  
 4. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. ALSO PROVIDE
 THE LOWEST FLOOR ELEVATION ON RELEVANT DRAWINGS. THIS
 SHOULD BE USED IN CONJUCTION WITH DRAINAGE PLAN TO SHOW
 GRADE 4" LOWER THAN LOWEST FLOOR LEVEL AND HOW DRAINAGE
 MEETS REQUIREMENTS IN [FBC R401.3]
  
 4-2. SITE DRAINAGE PROVIDED DOESN?T KEEP THE DRAINAGE
 WITHIN THE SITE.
 [FBC R403.1.7.3] FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 5. OK
  
 6. OK
  
 7. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 7-2 ENERGY CODE COMPLIANCE NEEDS TO BE MET FOR BUILDING
 AS WELL AS MECHANICAL. IF PERFORMANCE BASED ENERGY
 CALCULATIONS AREN?T PROVIDED THAN INDICATE THE METHOD
 USED TO COMPLY FOR ALL BUILDING ELEMENTS AS APPLICABLE
 TO [FBC ENERGY R401.2]
  
 8. OK
  
 9. OK
  
 10. PRODUCT APPROVALS WILL BE A PROVISO TO THE PERMIT.
  
 11. PRODUCT APPROVALS FOR ROOFING TO BE SUBMITTED WITH
 THE SUB-PERMIT FOR ROOFING.
  
 12. OK
  
 13. OK
  
 14. OK
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 07:56 Rev Time 0.00
Received By cmontell Date 2018-07-25 Time 14:36 Sent To  
Notes
2018-07-20 07:57:17****CORRECTIONS****
 W.P.B. PERMIT: 18061145
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. AN ADDRESS WILL NEED TO BE PROVIDED FOR LOT 42.
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
 2. IS THIS PROJECT BEING BUILT WITH FEDERAL FUNDS?
 PLEASE VERIFY THAT ADDITIONAL ADA REQUIREMENTS DON'T
 APPLY IF FEDERAL FUNDING IS BEING USED FOR THIS
 PROJECT.
  
 3. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY.
  
 4. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. ALSO PROVIDE
 THE LOWEST FLOOR ELEVATION ON RELEVANT DRAWINGS. THIS
 SHOULD BE USED IN CONJUCTION WITH DRAINAGE PLAN TO SHOW
 GRADE 4" LOWER THAN LOWEST FLOOR LEVEL AND HOW DRAINAGE
 MEETS REQUIREMENTS IN [FBC R401.3]
  
 5. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS.
  
 6. [FBC 107.3.5.3] PLEASE ADD PROJECT DESIGN DATA:
 ZONING, OCCUPANCY, CONSTRUCTION TYPE AND MEAN ROOF
 HEIGHT(MRH).
  
 7. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 8. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(SEE
 ICC-ES REPORT OR EQUAL) WITH THE TYPE SELECTED TO
 ESTABLISH THICKNESS NEEDED TO MEET REQUIRED R-VALUE,
 FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX.
 IF THERE IS MECHANICAL EQUIPMENT IN THE SPACE THAN IT
 REQUIRES IGNITION BARRIER.
  
 9. [FBC R806.5]DETAIL 5/S-3 SHOWS CONTINOUS VENT AT
 SOFFIT. WITH ICYNENE SPRAYED TO UNDERSIDE OF ROOF DECK.
 THE ATTIC SPACE NEEDS TO BE CONTAINED WITHIN THE
 BUILDING ENVELOPE. PLEASE INDICATE IF THIS IS AN
 UNVENTED ATTIC OR EXPLAIN HOW THE VENTS WON'T BREAK THE
 THERMAL ENVELOPE.
  
 10. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND
 SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED. THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE
 APPROVED BY THE BUILDING OFFICIAL PRIOR TO
 INSTALLATION.
  
 11. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
 THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE APPROVED BY
 THE BUILDING OFFICIAL PRIOR TO INSTALLATION.
  
 12. [FBC R703.4]PROVIDE NOTE FOR TYPE OF WINDOW/DOOR
 FLASHING TO BE USED TO MEET REQUIREMNETS OF [FBC
 R703.4].
  
 13. [FBC R608.8]PROVIDE LINTEL SCHEDULE TO SHOW
 BEARING. PROVIDE LINTEL DOCUMENTATION FOR SAFE LOADING.
  
 14.[FBC R402.2]DETAIL 5/S3 SAYS CONCRETE COMPRESSIVE
 STRENGTH IS 300. PLEASE UPDATE TO 3000 IF THAT WAS THE
 INTENT. ALSO, ADD COMPRESSIVE STRENGTH FOR GROUT.
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 13:38 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 13:38 Sent To  
Notes
2018-09-22 13:38:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED HAS SOME ITEMS NOT
 INCLUDED AND DEMAND FACTOR APPLIED INCORRECTLY. SEE
 FORMAT IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 (LOAD CALCULATION NOT CORRECT. A LAUNDRY CIRCUIT MUST
 BE INCLUDED AT 1500 VA, AND THIS IS SEPARATE FROM THE
 DRYER WHICH MUST BE CALCULATED AT A MINIMUM OF 5000 VA,
 BREAKER SHOWN FOR DRYER IS 50 AMP WHICH IS MUCH MORE
 THAN 4500 VA. NEC 220.52 AND 220.54)
 2. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ALL
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. WATER HEATER IS NOT SHOWN. NEC 210.8,
 210.12, 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5;
 FBC RE E3706.2, E3902 (WATER HEATER NOT SHOWN IN PANEL
 SCHEDULE, AFCI PROTECTION NOT SHOWN CORRECTLY.)
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902.16 (NOT CORRECTED, NOTE
 STATES THAT RECEPTACLES SHALL BE AFCI PROTECTED WHICH
 IS NOT CODE COMPLIANT.)
 4. CORRECTED.
 5. CORRECTED.
 6. TRANSFER SWITCH REMOVED.
 7. CORRECTED.
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED)
 9. CORRECTED.
 10. PROVIDE ACCURATE RISER DIAGRAM. THE EQUIPMENT
 GROUNDING CONDUCTOR (EGC) SHOULD NOT BE INCLUDED IN THE
 CONDUIT FROM THE METER TO THE MANUAL TRANSFER SWITCH.
 THE EGC FROM THE MANUAL TRANSFER SWITCH TO THE INTERIOR
 PANEL IS NOT SIZED PROPERLY. INTERIOR PANEL STATES THAT
 IS HAS A 125 AMP MAIN, AND BELOW THAT STATES THAT IT
 HAS A 150 AMP MAIN. CORRECT DISCREPANCY. NEC 215.5,
 250.6, 250.122; WPB FBC 107.2.1; FBC RE E3704.6,
 3607.3.1 (RISER STILL NOT CORRECT. RISER DIAGRAM SHOWS
 A FEED FROM THE METER TO THE INTERIOR PANEL WHICH IS
 LOCATED IN THE DINING ROOM. CONDUCTORS THAT ARE NOT
 PROTECTED BY A MAIN BREAKER OR DISCONNECT ARE NOT
 PERMITTED TO RUN THROUGH THE HOUSE IN THIS FASHION.
 PROVIDE EITHER A MAIN ON THE OUTSIDE OF THE HOME, OR
 INSTALL THE CONDUCTORS UNDER THE SLAB. IF CONDUCTORS
 ARE INSTALLED UNDER THE SLAB, THEN THERE SHOULD NOT BE
 AN EQUIPMENT GROUNDING CONDUCTOR IN THIS CONDUIT. IF
 THERE IS A MAIN BREAKER, THAN THE EGC IS NOT SIZED
 PROPERLY. PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC
 RE E3601.6)
 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (NOT
 SHOWN ON RISER DIAGRAM)
 12. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4 (NOT CORRECTED, ALSO
 SIZE OF GROUNDING ELECTRODE CONDUCTOR IS NOT CODE
 COMPLIANT. PROVIDE CORRECTION. NEC 250.66)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
  
 NEW COMMENT:
  
 16. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 09:52 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 08:28 Sent To  
Notes
2018-07-20 09:52:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED HAS SOME ITEMS NOT
 INCLUDED AND DEMAND FACTOR APPLIED INCORRECTLY. SEE
 FORMAT IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 2. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ALL
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. WATER HEATER IS NOT SHOWN. NEC 210.8,
 210.12, 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5;
 FBC RE E3706.2, E3902
 3. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902.16
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 6. PROVIDE SPEC SHEET FOR MANUAL TRANSFER SWITCH
 SHOWING THAT IT IS SERVICE ENTRANCE RATED. NEC 110.3;
 FBC RE E3606.4
 7. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 9. PROVIDE LOCATION OF SERVICE EQUIPMENT ON PLAN. WPB
 FBC 107.2.1
 10. PROVIDE ACCURATE RISER DIAGRAM. THE EQUIPMENT
 GROUNDING CONDUCTOR (EGC) SHOULD NOT BE INCLUDED IN THE
 CONDUIT FROM THE METER TO THE MANUAL TRANSFER SWITCH.
 THE EGC FROM THE MANUAL TRANSFER SWITCH TO THE INTERIOR
 PANEL IS NOT SIZED PROPERLY. INTERIOR PANEL STATES THAT
 IS HAS A 125 AMP MAIN, AND BELOW THAT STATES THAT IT
 HAS A 150 AMP MAIN. CORRECT DISCREPANCY. NEC 215.5,
 250.6, 250.122; WPB FBC 107.2.1; FBC RE E3704.6,
 3607.3.1
 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 12. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 13. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 14. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. SEE MASTER BEDROOM
 AND AREA LEFT OF RANGE AS EXAMPLES. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 15. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 15:01 Rev Time 0.00
Received By dbattles Date 2018-09-17 Time 14:55 Sent To  
Notes
2018-10-30 08:12:4310/30 TO DB DESK
  
2018-09-18 14:56:00R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-30 Cont ID  
Sent By dbattles Date 2018-07-30 Time 14:35 Rev Time 0.00
Received By dbattles Date 2018-06-25 Time 13:45 Sent To  
Notes
2018-06-26 13:45:33R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By dbattles Date 2018-07-30 Time 14:35 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 14:35 Sent To  
Notes
2018-07-30 14:35:25[FBC 109]IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT
 SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED.
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
 561-233-5025 FOR MORE INFORMATION
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By cmontell Date 2018-10-11 Time 14:40 Rev Time 0.00
Received By cmontell Date   Time   Sent To  
Notes
2018-10-11 14:40:15MECHANCIAL PLAN REVIEW FAIL
  
  
 1 - HEAT LOAD CALCULATION REQUIRED, 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. M1401.3EQUIPMENT AND
 APPLIANCE SIZING.
  
 2 - ENERGY CALCULATION REQUIRED, 2017 FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC. R405.4.2 COMPLIANCE
 REPORT.
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By cmontell Date 2018-07-25 Time 14:59 Rev Time 0.00
Received By cmontell Date 2018-07-25 Time 14:38 Sent To  
Notes
2018-07-25 14:58:49MECHANCIAL PLAN REVIEW FAIL
  
  
 1 - NO MECHANICAL PLANS, 2017 FLORIDA BUILDING CODE -
 BUILDING SEC. 107.2.1INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2 - HEAT LOAD CALCULATION REQUIRED, 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. M1401.3EQUIPMENT AND
 APPLIANCE SIZING.
  
 3 - ENERGY CALCULATION REQUIRED, 2017 FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC. R405.4.2 COMPLIANCE
 REPORT.
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-09 Cont ID  
Sent By jesmith Date 2018-10-09 Time 09:33 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 09:17 Sent To  
Notes
2018-10-09 09:33:21PLUMBING COMMENTS: APPROVED
 CODE COMPLIANT ISO PROVIDED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By thunt Date 2018-07-30 Time 14:23 Rev Time 0.00
Received By thunt Date 2018-07-30 Time 14:23 Sent To  
Notes
2018-07-30 14:25:4007/30/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE A CODE COMPLIANT ISOMETRIC DRAWING. BOTH
 BATHROOM HAVE 2 WET VENTED FIXTURES BEYOND THE VENT.
 ONLY 1 WET VENTED FIXTURE IS PERMITTED UPSTREAM FROM
 THE VENT. FBC R P3108.2.1
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 15:01 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 15:00 Sent To  
Notes
2018-10-30 15:01:34ROOFER TO PROVIDE PRODUCT APPROVALS WITH SUB-PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By dbattles Date 2018-07-30 Time 14:31 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 14:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-04 Cont ID  
Sent By mcruz Date 2018-10-04 Time 11:07 Rev Time 0.00
Received By mcruz Date 2018-10-04 Time 11:03 Sent To PC
Notes
2018-10-04 11:07:34ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 2) SHOW SETBACK DIMENSION ON WEST SIDE OF PROPERTY.
 REQUIRES A MINIMUM OF 4'.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By MC Date 2018-07-10 Time 11:41 Rev Time 0.00
Received By mcruz Date 2018-07-10 Time 11:03 Sent To PC
Notes
2018-07-10 11:41:49ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-71, TABLE III-1 A SINGLE-FAMILY
 DWELLING IS PERMITTED PER LOT IN A SF 11 ZONING
 DISTRICT. A MINOR SUBDIVISION APPROVAL WILL BE REQUIRED
 IN ORDER TO BUILD A SINGLE-FAMILY HOME AT THIS
 LOCATION. PROPERTY DEVELOPMENT REGULATIONS HAVE BEEN
 ENCLOSED FOR YOUR REVIEW.
 2) SEPERATE PERMITS ARE REQUIRED FOR: A/C EQUIMENT,
 FENCES AND LANDSCAPING.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy