Plan Review Details - Permit 18061140
Plan Review Stops For Permit 18061140
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:47 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:47 Sent To  
Notes
2018-09-01 18:47:49AIPP NOT REQUIRED PER EMAIL FROM SYBILLE WELTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-26 Cont ID  
Sent By dbattles Date 2018-10-26 Time 12:52 Rev Time 0.00
Received By dbattles Date 2018-10-26 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By dbattles Date 2018-10-15 Time 07:47 Rev Time 0.00
Received By dbattles Date 2018-10-13 Time 09:15 Sent To  
Notes
2018-10-15 07:47:51****CORRECTIONS****
 W.P.B. PERMIT: 18061140
 REVIEWED: AUGUST 17, 2018
 2ND REVIEW OCTOBER 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1-7. OK
  
 8. [FBC AMENDED 107.3.5]
 -STAIR 2 4 TH FLOOR LANDING SHOULD HAVE GUARD RAIL AND
 NOT APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL
 LANDING.
 8-2 NOT FULLY ADDRESSED. LOOK AT 4TH FLOOR LANDING ON
 SHEET A-1.04, IT SHOULD MATCH SHEET A-5.02 FOR 4TH
 FLOOR LANDING.
  
 9-38. OK
  
 NEW COMMENT:
 [FBC AMENDED 110.8.4.4]ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA
 STATUTES.
  
 PLEASE PROVIDE ONE ARCHITECTURAL SHEET AND ONE
 STRUCTURAL SHEET WITH THE PHRASE FROM [FBC AMENDED
 110.8.4.4]
 INDEX SHEET OR GENERAL NOTES SHEET WOULD WORK.
  
 THIS REQUIREMENT IS PART OF THRESHOLD BUILDING. SEE
 THRESHOLD COMMENTS FOR ADDITIONAL THRESHOLD
 REQUIREMENTS.
  
 PROVISO: DERFERED SUBMITTALS
 ROOFING
 GUARDS AND HANDRAILS
 TRASH CHUTE
 FENESTRATION
 FLOORING SUBMITTAL WITH REPORTS FOR ICC, STC AND FLAME
 SPREAD/SMOKE DEVELOPED INDEX.
 SHORING/RE-SHORING
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By jgomez Date 2018-08-20 Time 08:57 Rev Time 0.00
Received By dbattles Date 2018-08-17 Time 08:15 Sent To  
Notes
2018-08-20 09:01:59****CORRECTIONS****
 W.P.B. PERMIT: 18061140
 REVIEWED: AUGUST 17, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEPARATE PERMIT REQUIRED FOR DEMO,
 ENGINEERING(CIVIL), LANDSCAPING, IRRIGATION, FENCING,
 DUMPSTER ENCLOSURE AND GENERATOR.
  
 2. [FBC AMENDED 107.2.5]THE SUREVEY PROVIDED SHOWS
 EXISTING CONDITIONS, WHICH IS GOOD FOR THE DEMO PERMIT.
 PLEASE PROVIDE SURVEY TO SHOW NEW BUILDING ON THE SITE.
 SHOW LOWEST FOOR ELEVATION, AND PROVIDE ELEVATIONS IN
 NAVD88.
  
 3. [FBC AMENDED 107.3.5]PLEASE UPDATE INDEX SHEET TO
 INCLUDE G-0.09. I WILL BE PUTTING APPROVAL STAMP ON
 THAT PAGE TO INDICATE ALL SHEETS REVIEWED.
  
 4. SHEETS A-7.02 THRU A-7.09 NAME DESCRIPTION DOESN?T
 MATCH THE SHEET PROVIDED. EX: SHEET A7.02 SAYS WINDOW
 SCHEDULE ON INDEX SHEET, BUT IT IS ACTUALLY GLAZING
 DETAIL SHEET.
  
 5. SHEET A-0.03 SHOW IN INDEX BUT NOT UPLOADED. PLEASE
 UPLOAD SHEET A-0.03 ACCESSIBILITY PLAN.
  
 6. SHEET A-5.02 IS NOT UP-LOAD AND IT IS NEEDED FOR
 STAIR 2 DETAILS.
  
 7. [FBC AMENDED 107.3.5]UPDATE INDEX SECTION FOR
 STRUCTURAL. IT SHOWS AS 8 STORY BUILDING AND SHEETS
 DON?T MATCH WHAT WAS UPLOADED.
 ALSO, SHEETS ARE MISSING. I CAN?T DO A FULL REVIEW
 UNTIL ALL STRUCTURAL SHEETS ARE PROVIDED.
 PLEASE REVIEW STRUCTURAL SECTION IN PROJECT DOX TO
 COMPARE TO ADJUSTED INDEX.
  
 8. [FBC AMENDED 107.3.5]PLEASE UPDATE ALL DRAINGS
 INCLUDING LIFE SAFETY, FLOOR PLANS AND ROOF ACCESS TO
 SHOW HOW STAIRS WORK. LOOKING MAINLY AT AT THE FIRST
 FLOOR, 4 TH FLOOR(STAIR #2) ROOF LANDING(STAIR #1).
 SOME OF THE THINGS I SEE INCLUDE, BUT ARE NOT LIMITED
 TO:
 -STAIR 1 AT GROUND FLOOR SHOULD EXTEND INTO CORRIDOR
 SINCE THAT DISTANCE BETWEEN FLOORS IS GREATER THAN THE
 UPPER FLOORS.
 -STAIR 1 ROOF LANDING SHOULD HAVE GUARD RAIL AND NOT
 APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL
 LANDING. IT ALSO EXITS ONTO ROOF DIFFERNTLY BETWEEN
 PLANS AND DETAILS.
 -STAIR 2 4 TH FLOOR LANDING SHOULD HAVE GUARD RAIL AND
 NOT APPEAR TO CONTINUE GOING UP SINCE IT IS THE FINAL
 LANDING.
  
 9. PLEASE REVIEW ALL STAIRS AND SUPPLY MISSING SHEET
 A-5.02.
 ALSO, IF POSSIBLE ON SHEET A5.01 AND A5.02 CAN YOU KEEP
 THE SAME ORIENTAION AS THE PLANS FOR ENLARGED DETAILS.
  
 10. UPDATE ALL LIFE SAFETY SHEETS FOR THE CURRENT CODE
 VERSION FBC 2017 6TH EDITION. I SEE THREE INSTANCES
 TOTAL(GENERAL NOTES, TRAVEL AND VERTICAL ORIENTED IN
 OCCUPANCY USE)ON ALL FOUR SHEETS.
  
 11. SHEET A-S.03 STAIR SIGNAGE JPG. DIDN?T ATTACH TO
 DRAWING. ADD STAIR SIGNAGE DETAIL.
  
 12. SHEET A-7.05 IMPACT INSULATION AND SOUND
 TRANSMISSION CLASS ARE FOR 6? SLAB. THE FLOORS IN THIS
 PROJECT ARE TO BE 8?.
  
 13. SHEET A7.03 DOOR SCHEDULE REFERS TO ?SEE INTERIOR
 GLAZING?. I SEE REFERENCE TO TEMPERED GLASS, BUT WHAT
 ABOUT FIRE RATING ON DOORS IN THE CORRIDOR(2 HR RATED
 FIRE CORRIDOR).ALSO, THE NOTES BELOW INTERIOR GLAZING
 ARE FOR EXTERIOR DOORS.
  
 14. [FBC ACCESSIBILITY 402.1]PROVIDE ACCESSIBLE ROUTE
 FROM PARKING LOT.
  
 15. [FBC ACCESSIBILITY 208.2]PROVIDE DATA USED TO
 DETERMINE AMOUNT OF ADA SPOTS.
  
 16. [FBC ACCESSIBILITY 404.2.3]DOOR ST2.1 APPEARS TO
 REDUCE THE WIDTH OF 199.1. VERIFY AND ADJUST IF
 APPLICABLE.
  
 17. [FBC ACCESSIBILITY 606.2]CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 18. [FBC ACCESSIBILITY 606.3]HEIGHT. LAVATORIES AND
 SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 THIS APPLIES TO THE 9 ADA UNITS. SHEETS A4.03(UNIT 0C),
 A4.06(UNIT 1C) AND A4.05(UNIT 1B).
  
 19. [FBC ACCESSIBILITY 804.3]KITCHEN WORK SURFACE. IN
 RESIDENTIAL DWELLING UNITS REQUIRED TO COMPLY WITH 809,
 AT LEAST ONE 30 INCHES (760 MM) WIDE MINIMUM SECTION OF
 COUNTER SHALL PROVIDE A KITCHEN WORK SURFACE THAT
 COMPLIES WITH 804.3.
  
 20. [FBC ACCESSIBILITY 804.3.2]HEIGHT. THE KITCHEN WORK
 SURFACE SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.THIS APPLIES TO THE 9 ADA UNITS.
 SHEETS A4.03(UNIT 0C), A4.06(UNIT 1C) AND A4.05(UNIT
 1B).
  
 21. [FBC AMENDED 107.3.5]IS DOOR 121.2 AT GARBAGE ROOM
 A ROLL-UP DOOR? HOW DOES THE TRASH ROOM FUNCTION? FROM
 SITE PLAN AND CIVIL PLANS IT LOOKS LIKE IT EXITS ONTO
 GRASS AND A CURB.
  
 22. IF ELEVATOR PENTHOUSE GOES TO ELEVATION +50?-8? AS
 SHOWN ON A-5.04, ADJUST ELEVATIONS TO SHOW THE ELEVATOR
 PENTHOUSE AT THIS HEIGHT.
  
 23. [FBC 720.2]SHEET A-6.01 GENERAL NOTES SHOWS
 INSULATION CODE REFERENCE FOR INSULATION AS FBC 719.2.
 IT IS NOW 720.2.
  
 24. GROUND LEVEL CORRIDORS CALL FOR WALL TYPE 3. SHEET
 A-6.01 SHOW TYPE 3A TO BE 1 HOUR RATED. THIS CONFLICTS
 WITH LIFE SAFTEY PLAN WHERE IT IS ESTABLISHED AS A 2
 HOUR RATED COORIDOR. PLEASE ADJUST WALL TYPE OR DETAIL
 AS NEEDED. PROVIDE UL
  
 25. SHEET A-1.01 SHOWS THE TRASH ROOM AT 3 HOUR RATING
 AND SECTION A-5.05 SHOWS 2 HOUR WALL. THE WALL TYPE 9A
 SHOWN ON A-1.01 IS FOR 2 HOUR RATING. PLEASE
 CO-ORDINATE THE RATING TO MATCH(SAME COMMENT FOR
 STAIRS)
  
 26. SHEET A-5.05, HOW IS TRASH CHUTE FIRE STOPPING
 INSTALLED IN THIS ASSEMBLY? WILL THAT BE PART OF
 DEFFERED SUBMITTAL?
  
 27. SHEET A-5.05 SECTION 1 CALLS FOR 6 MIL AND 4? SLAB.
 STRUCTURAL, S1.01 FOUNDATION PLAN NOTES, IS CALLING FOR
 5? SLAB WITH 10 MIL. PLEASE CO-ORDINATE WITH
 STRUCTURAL.
  
 28. SHEET A3.01 CALL OUT TO A3.03 AT EXTERIOR WALLS.
 PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND
 ISN?T IN THE INDEX. ALSO, I THINK CALL OUT AT ELEVATER
 SHOULD BE 1/A-5.06 AND AT TRASH CHUTE IT SHOULD BE
 1/5.05
  
 29. SHEET A3.02 CALL OUT TO A3.03 AT EXTERIOR WALLS.
 PLEASE PROVIDE THIS SHEET AS IT IS NOT PROVIDED AND
 ISN?T IN THE INDEX.
  
 30. SHEET A-4.00 WHAT IS THE FINISH FOR ACCESSIBLE
 BALCONIES. [ANSI A137.1 ]IN FLOORING SUBMITTAL PROVIDE
 SPECIFICATION SHEET TO INCLUDE DYNAMIC COEFFICIENT OF
 FRICTION (DCOF) OF EXTERIOR FINISH BEING INSTALLED.
  
 31. [FBC AMENDED 107.3.5.1]PROVIDE STRUCTURAL ANALYSIS
 FOR STRUCTURAL LOAD BEARING COMPONANTS INCLUDING
 DEFLECTIONS OF BEAMS AND SLABS.
  
 32. [FBC 1603]SHEET S1.01 SHOWS (3)COLUMNS CC3 AT THE
 COVERE3D PARKING. WHEN I LOOK AT S1.02 I SEE 3
 ADDITIONAL COLUMNS LABELED CC7 AND BEAM 2B-2. IT
 APPEARS THAT COLUMNS CC3 CARRIES THE BEAM AND
 ADDITIONAL OFFSET COLUMNS CC7. THE END OF 2B-2 ALSO
 BEARS ON SMALLER COLUMNS CC4.
 IS THIS THE CORRECT CONFIGURATION AND DOES CC7 FOUND ON
 FL 2-4 END AT BEAM IN 2 ND FLOOR FRAMING.
  
 33. [FBC 1603]SAME COLUMNS CC3 APPEAR TO SUPPORT
 CANTILEVER APPROXIMATELY 9? FROM COLUMN TO BUILDINGS
 EDGE ABOVE FOR REMAINING OVERHANG OF PARKING AND THE
 REMAINING FLOORS. PLEASE CLARIFY THAT THIS IS CORRECT,
 OR ADJUST AS NEEDED TO TRANFER LOADS TO FOUNDATION.
  
 34. [FBC 1603]SHEET S1.01 CALLS FOR DETAIL 3/S2.01 FOR
 FOOTER AT STOREFRONT. THE DETAIL SAYS SEE PLAN FOR
 WIDTH OF STOREFRONT FOOTER. I DON?T SEE STOREFRONT
 FOOTER ON S1.01. IS THIS WF1 LIKE AT CMU INFILL WALL?
  
 SUBMITTALS AND PRODUCT APPROVALS:
 35. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL,
 PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471
 OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND
 ISSUED BY THE CITY OF WEST PALM BEACH. SUBJECT TO THE
 INSPECTOR?S DISCRETION, THIS MAY BE ACCEPTED IN THE
 FIELD AT TIME OF INSPECTION.
  
 36. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, WINDOW MULL(IF APPLICABLE), DOORS,
 TRANSOMS(IF APPLICABLE), LINTEL W/ SAFELOAD, SLIDING
 GLASS DOORS AND STOREFRONT, OR INDICATE THAT YOU WOULD
 LIKE THEM DEFFERED.
  
 37. [FBC AMENDED 107.2.1.2]PROVIDE SUBMITTAL FOR TRASH
 CHUTE, OR INDICATE THAT IT WILL BE DEFERRED.
  
 38. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT
 ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE
 FOLLOWING REPORTS ARE REQUIRED:
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By jleahy Date 2018-09-21 Time 17:08 Rev Time 0.00
Received By jleahy Date 2018-09-21 Time 17:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By jleahy Date 2018-07-25 Time 12:01 Rev Time 0.00
Received By jleahy Date 2018-07-23 Time 16:07 Sent To  
Notes
2018-07-25 12:21:59FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 LOAD CALCULATION REQUIRED TO BE DONE IN ACCORDANCE WITH
 ARTICLE 220
  
 FAULT CURRENT CALCULATION REQUIRED PER 110.24
  
 MAIN SERVICE OCP OF1200 AMPERES SHALL MEET THE
 REQIREMENTS OF 240.87
  
 PAGE E-1.01
  
 AC ROOMS 109. 119.1, 102.1, 118.2 MISSING SERVICE
 OUTLET FOR THE AC.
  
 PAGE E-1.02
  
 X-15 CLOSETS NEED SERVIE OUTLET FOR THE AC
  
 PAGE E-2.01
  
 PANEL SCHEDULE SHOWS GFI ON SOME CIRCUIT BUT NOT ALL
 REQUIRED CIRCUITS, AFCI PROTECTION IS ALSO MISSING.
 210.8, 210.12(A)(B)
  
 PAGE E-3.01
  
 NEED TO SHOW SIZE OF CONTROLER FOR FIRE PUMP
  
 PAGE E-3.02
  
 FIRE ALARM SYSTEM, PROVIDE SEPARATE PLANS AND PERMIT
 FOR THIS SYSTEM.
  
 PAGE E-3.03
  
 LOW VOLTAGE SYSTEMS REQUIRE A SEPARATE PERMIT.
  
 PAGE E-3.04
  
 FIRE FIGHTER COMMUNICATION SYSTEM REQUIRES SEPARATE
 PLANS AND PERMITS FOR THIS SYSTEM
  
 PAGE E-4.04
  
 LAUNDRY AREA RECEPTACLES REQUIRE AFCI AND GFCI
 PROTECTION 210.8, 210.12(A)(B)
  
 PAGE E-5.01, E-5.02, E-5.03
 AFCI AND GFCI PROTECTION TO BE DONE IN ACCORDANCE WITH
 210.8, AND 210,12(A)(B)
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2018-10-25 Cont ID  
Sent By rrossano Date 2018-10-25 Time   Rev Time 0.00
Received By rrossano Date 2018-10-25 Time   Sent To I
Notes
2018-10-25 10:43:57UNDER FORMAL ENGINEERING REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-10-12 Cont ID  
Sent By rrossano Date 2018-10-12 Time   Rev Time 0.00
Received By rrossano Date 2018-10-12 Time   Sent To I
Notes
2018-10-12 06:53:07ENGINEERING SUBMITTAL IN REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By shill Date 2018-07-25 Time 14:25 Rev Time 0.00
Received By shill Date 2018-07-25 Time 14:25 Sent To  
Notes
2018-07-25 14:25:50CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By scaldero Date 2018-09-13 Time 14:04 Rev Time 0.00
Received By scaldero Date 2018-09-13 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By scaldero Date 2018-07-16 Time 10:42 Rev Time 0.00
Received By scaldero Date 2018-07-05 Time 08:34 Sent To  
Notes
2018-07-05 12:35:24PERMIT # 18061140
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 3) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 4) SHEET FP-3.00 - PER NFPA 20, CHAPTER 4: 4.12.7*
 DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS
 THE PUMP, DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-31 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By lmarchan Date 2018-10-29 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2018-10-24 Time 13:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By dbattles Date 2018-10-15 Time 08:33 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:10 Rev Time 0.00
Received By dbattles Date 2018-06-28 Time 10:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-18 Cont ID  
Sent By lmarchan Date 2019-01-18 Time 07:56 Rev Time 0.00
Received By lmarchan Date 2018-11-29 Time 08:08 Sent To  
Notes
2019-01-18 07:56:29MU-2019-0117-292
2018-11-29 08:08:3711/29/18 SENT EMAIL TO IMPACT FEE OFFICE FOR REVIEW.
 LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By jgomez Date 2018-08-15 Time 12:58 Rev Time 0.00
Received By jgomez Date 2018-08-15 Time 12:55 Sent To  
Notes
2018-08-15 12:59:04IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-11-15 Cont ID  
Sent By ccole Date 2018-11-15 Time 16:50 Rev Time 0.00
Received By ccole Date 2018-11-15 Time 16:09 Sent To  
Notes
2018-11-15 16:55:33MECHANICAL PROVISOS.
 MANUFACTURER'S SPECIFICATIONS FOR THE EQUIPMENT LISTED
 BELOW
 SHALL BE SUBMITTED PRIOR TO INSPECTION
  
 1) GENERATOR
 2) DRYERS
 3) FIRE DAMPERS
 4) MOTORIZED OUTSIDE AIR DAMPERS
 5) DUCT SMOKE DETECTORS
 6) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING
 PRODUCT DATA SHEETS AND NOA'S.
 7) AC CONDENSER STAND NOA
 8) KITCHEN EXHAUST HOODS9I) AC REFRIGERANT RISER
 10) DRYER BOOSTER FAN
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-10-26 Cont ID  
Sent By ccole Date 2018-10-26 Time 16:15 Rev Time 0.00
Received By ccole Date 2018-10-26 Time 09:17 Sent To  
Notes
2018-10-26 16:58:083RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18061140
 9/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 3RD REQUEST TO CHANGE THE AC HEAT LOAD
 CALCULATION LOCATION TO WEST PALM BEACH FROM MIAMI.
  
 2) M-204: THE USE OF THE CORRIDOR SUPPLY AIR AS MAKEUP
 AIR FOR THE DRYER EXHAUST IS NOT IN COMPLIANCE WITH
 SECTION 601.2 (1), BECAUSE THERE IS INADEQUATE AIR IN
 THE CORRIDOR TO SUPPLY THE LAUNDRY ROOM AND STILL
 REMAIN POSITIVELY PRESSURIZED- SEE BELOW.
  
 601.2 AIR MOVEMENT IN EGRESS ELEMENTS.
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
  
 EXCEPTIONS:
 1.USE OF A CORRIDOR AS A SOURCE OF MAKEUP AIR FOR
 EXHAUST SYSTEMS IN ROOMS THAT OPEN DIRECTLY ONTO SUCH
 CORRIDORS, INCLUDING TOILET ROOMS, BATHROOMS, DRESSING
 ROOMS, SMOKING LOUNGES AND JANITOR CLOSETS, SHALL BE
 PERMITTED, PROVIDED THAT EACH SUCH CORRIDOR IS DIRECTLY
 SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER THAN THE
 RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR.
  
 7) UPDATAD DEFERRED SUBMITTAL LIST:
  
 A) GENERATOR
 B) DRYERS
 C) FIRE DAMPERS
 D) MOTORIZED OUTSIDE AIR DAMPERS
 E) DUCT SMOKE DETECTORS
 F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING
 PRODUCT DATA SHEETS AND NOA'S.
 G) AC CONDENSER STAND NOA
 H) KITCHEN EXHAUST HOODS
 I) AC REFRIGERANT RISER
 K) DRYER BOOSTER FAN
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By ccole Date 2018-09-27 Time 14:45 Rev Time 0.00
Received By ccole Date 2018-09-27 Time 07:22 Sent To  
Notes
2018-09-27 14:59:052ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18061140
 9/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CORRECTED HEAT LOAD CALCULATIONS WERE NOT
 SUBMITTED- SEE 1ST REVIEW COMMENT #2- SECTION C402.3.1
 FBC EC.
  
 2) SHEET M-101: PLEASE PROVIDE AN EXHAUST VENTILATION
 CALCULATION FOR THE PARKING GARAGE AREA, AND INDICATE
 THE SEQUENCE OF OPERATION FOR THE FANS- SECTION 404.1
 AND 502.13 FBC M.
  
 3) M-204: THERE IS NO LEGEND TO CLARIFY WHAT THE "FS"
 LABEL AND THE"F" DEVICE SYMBOL PLACED AT THE DRYER
 EXHAUST DUCT/WALL PENETRATIONS STAND FOR- SECTION 107.1
 WPB.
  
 4) M-204: THE REQUESTED MAKE UP AIR FOR THE DRYERS AND
 AIR BALANCE CALCULATIONS FOR THE LAUNDRY ROOM NOT
 PROVIDED- SECTION 504.6 FBC M.
  
 5) M-101: THE REQUESTED DUCT SMOKE DETECTORS IN THE
 SUPPLY SYSTEM NOT PROVIDED FOR THE 5-TON SYSTEMS- SEE
 1ST REVIEW COMMENT #12 AND SECTION 606.2.1 FBC M.
  
 6) AS PREVIOUSLY REQUESTED PROVIDE A CONDENSATE PIPING
 RISER AND FLOOR PLAN DRAWING- SEE 1ST REVIEW COMMENT
 #16
  
 7) UPDATAD DEFERRED SUBMITTAL LIST:
  
 A) GENERATOR
 B) DRYERS
 C) FIRE DAMPERS
 D) MOTORIZED OUTSIDE AIR DAMPERS
 E) DUCT SMOKE DETECTORS
 F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING
 PRODUCT DATA SHEETS AND NOA'S.
 G) AC CONDENSER STAND NOA
 H) KITCHEN EXHAUST HOODS
 I) AC REFRIGERANT RISER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-20 Cont ID  
Sent By ccole Date 2018-07-23 Time 13:34 Rev Time 0.00
Received By ccole Date 2018-07-19 Time 16:55 Sent To  
Notes
2018-07-20 15:18:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061140
 7/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ENERGY COMPLIANCE REPORT IN ACCORDANCE
 WITH SECTIONS C101.5 AND C401.2 FBC EC.
  
 2) THE HEAT LOAD CALCULATIONS ARE INDICATING MIAMI AS
 THE LOCATION USED TO ESTABLISH DRY AND WET BULB
 TEMPERATURES- PLEASE CORRECT.
  
 3) SHEET M-101: THE PARKING AREA ON THE NORTH SIDE OF
 THE BUILDING IS CLASSIFIED AS AN ENCLOSED PARKING
 GARAGE PER SECTIONS 406.5.1, 406.5.2, AND 406.6 FBC B.
 PROVIDE A MECHANICAL VENTILATION SYSTEM AS REQUIRED BY
 SECTION 406.6.2 FBC B, AND IN COMPLIANCE WITH SECTION
 404 FBC M.
  
 4) M-101: THE DRYER, TOILET, AND FIRE PUMP EXHAUST
 SYSTEMS SHALL NOT TERMINATE AND DISCHARGE INTO THE
 ENCLOSED PARKING GARAGE PER SECTION 501.3 FBC M. PLEASE
 RELOCATE THESE TERRMINATIONS TO LOCATIONS IN
 COMPLIANCE.
  
 5) M-101 & M-501: A SECTION CUT OF THE GENERATOR AND
 GENERATOR ROOM IS SHOWN ON SHEET M-501. HOWEVER THERE
 IS NO GENERATOR OR GENERATOR ROOM SHOWN ON THE PLAN.
  
 6) M-201, 202, & 203: A) PLEASE UPDATE NOTE #4 TO THE
 CURRENT FBC-17 MECHANICAL CODE. B) IN REFERENCE TO NOTE
 #2B, THE WEST PALM BEACH BUILDING DEPARTMENT DOES NOT
 PERFORM INSPECTIONS ON INTUMESCENT PAINT APPLICATIONS,
 AND WILL REQUIRE THE DESIGN PROFESSIONAL OF RECORD TO
 CERTIFY THE APPLICATIONS. C) REMOVE NOTE #13 AS NO
 OUTSIDE AIR DUCTS ARE SHOWN ON THE PLANS AND
  
 SHEET M-300 SPECIFIES NATURAL VENTILATION.
  
 7) M-204: WHICH AC SYSTEM IS BEING INSTALLED IN THE AC
 CLOSET 112.1.
  
 8) M-204: SUPPLY DUCT FOR RESTROOM 113 NOT SHOWN.
  
 9) M-204: INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR
 THE LAUNDRY ROOM AND PROVIDE AN AIR BALANCE CALCULATION
  
 10 )M-204: OUTSIDE AIR DUCT AND DAMPER FOR FCU-B NOT
 SHOWN.
  
 11) M-300: PLEASE INCLUDE THE CORRIDORS ON THE 2ND,
 3RD, AND 4TH FLOORS IN THE O/A CALCS.
  
 12) M-300: THE HVAC DESIGN TABLE INDICATES DUCT SMOKE
 DETECTORS HOWEVER NONE ARE SHOWN ON THE PLANS- PLEASE
 CORRECT AND NOTE THAT SYSTEMS FCU-D, E, & F ARE 5-TON
 SYSTEMS WHICH TYPICALLY HAVE THE CAPACITIES TO EXCEED
 2000 CFMS OF SUPPLY AIR. PLEASE PROVIDE A DUCT SMOKE
 DETECTOR IN THE SUPPLY SYSTEMS OF THE AIR HANDLERS-
 SECTION 606.2.1 FBC M.
  
 13) M-400: PLEASE INDICATE THE REFRIGERANT PIPING
 SIZES, AND SHOW THE PIPING RUNS ON THE FLOOR PLANS.
  
 14) M-501: THE MIAMI-DADE NOA #15-0902.02 HAS BEEN
 SUPERSEDED BY #17-1218.02. PLEASE CORRECT THE NOTE AND
 SUBMIT TWO COPIES OF THE NOA.
  
 15) PROVIDE A CONDENSATE PIPING RISER, AND SHOW THE
 PIPING RUNS ON THE PLUMBING FLOOR PLANS.
  
 16) REQUIRED PRODUCT SUBMITTALS:
  
 A) GENERATOR
 B) DRYERS
 C) FIRE DAMPERS
 D) MOTORIZED OUTSIDE AIR DAMPERS
 E) DUCT SMOKE DETECTORS
 F) OUTSIDE AIR AND EXHAUST INLET LOUVERS, INCLUDING
 PRODUCT DATA SHEETS AND NOA'S.
 G) AC CONDENSER STAND NOA
 H) KITCHEN EXHAUST HOODS
  
 17) ADVISORY: A TEST AND BALANCE REPORT FOR THE AC
 SYSTEMS WILL BE REQUIRED AT FINAL MECHANICAL
 INSPECTION- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By gjohnson Date 2018-10-29 Time 09:01 Rev Time 0.00
Received By gjohnson Date 2018-10-26 Time 12:48 Sent To  
Notes
2018-10-29 09:01:13PLUMBING PROVISO:
 1. SHOW MOP SINK FOR THE GROUND FLOOR P-4 ON THE
 SANITARY ISOMETRIC SHT. P-3.03. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 1. PROVIDE RISER DIAGRAM FOR THE CONDENSATE AND WATER
 HEATER DRAIN PAN. . PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-03 Cont ID  
Sent By gjohnson Date 2018-10-03 Time 07:49 Rev Time 0.00
Received By gjohnson Date 2018-10-02 Time 12:52 Sent To  
Notes
2018-10-03 07:59:472ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 NOT COMPLIED 8. SHT. P- 3.00 PLEASE ENLARGE THE WATER
 AND SANITARY ISOMETRIC DRAWING ON SEPARATE SHEETS THEY
 ARE TO CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB
 AMEND TO FBC 107.3.5.1.3(13) SHT. P-3.0 WAS NOT REVISED
 AND THE SANITARY ISOMETRIC THAT WAS ADDED TO SHT.
 P.3.03 IS MORE CONGESTED AND OVERLAPS THE SOIL STACK
 RISER. THE SANITARY NEEDS TO BE ENLARGED AND PLACED ON
 SEPARATE SHEET.
  
 COMPLIED PARTIALLY 9. SHT. P- 3.00 SHOW THE PIPE SIZE
 ON THE WATER AND SANITARY ISOMETRIC DRAWINGS. PER WPB
 AMEND TO FBC 107.3.5.1.3(13) NEED TO SIZE ALL THE
 BRANCHES ON THE WATER ISOMETRIC.
  
 COMPLIED PARTIALLY 10. P -4.01 THE ELECTRIC WATER
 HEATER DETAIL HAS THE FOLLOWING CODE VIOLATIONS.
 C) SHOWS WATER HEATER MOUNTED ON SHELF IS THIS CORRECT
 AN 80 GAL HEATER ON THE SHELF IF SO PROVIDE DETAIL FOR
 SHELVING TO HOLD THE WEIGHT OF THE 80 GAL HEATER 800LBS
 + PER WPB AMEND TO FBC 107.2.1 PROVIDE A DETAIL FOR THE
 SHELVING FOR THE 80 GAL HEATER IT SHALL BA ABLE TO
 SUPPORT 1000 POUNDS OR MORE.
  
 COMPLIED PARTIALLY 11. A SERVICE SINK IS REQUIRED ON
 GROUND FLOOR PE FBC PL TABLE 403.1 MOP SINK NOT ADDED
 TO ISOMETRIC DRAWING PLEASE CLARIFY.
  
 NEW COMMENTS:
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND SIZING
 FOR THE LINT INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 2. THE DISCHARGE FROM THE ELEVATOR SUMP PUMP SHALL
 DISCHARGE INTO OIL SEPARATOR OR HAVE AN OILMINDER ALARM
 ON THE PUMP PROVIDE MANUFACTURE SPECIFICATIONS ON PUMP
 AND OIL SEPARATOR IF ONE IS BEING USED. PER FBC PL
 1003.4
  
 3. PLEASE PROVIDE ISOMETRIC FOR CONDENSATE AND WATER
 HEATER PAN DRAIN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By gjohnson Date 2018-08-13 Time 07:11 Rev Time 0.00
Received By gjohnson Date 2018-08-13 Time 07:11 Sent To  
Notes
2018-08-13 11:05:281ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE ENLARGED UNIT PLANS WHAT THE
 DESIGN SPEC THE BATHROOM IS A OR B PER FHA GUIDELINES.
  
 2. PLEASE SHOW CLEAR FLOOR SPACE FOR WATER CLOSETS ON
 THE ENLARGED UNITS PLANS PER FHA G REQ. 7 (2)(A)(III)
 OR (B)(IV)
  
 3. SHT. G-007 UNDER THE REQUIREMENT IT IS REFERENCING A
 DETAIL ON SHT. A-3.1.2 I WAS UNABLE TO LOCATE THIS PAGE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PROVIDE A DETAIL SHOWING THE DIMENSIONS OF
 THE EMERGENCY SCUPPER. PER WPB AMEND TO FBC 107.2.1
  
 5. THE BREAKROOM SINK AND THE SINK IN THE COMMUNITY
 ROOM SHALL BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER
 THAN 34" AND A CLEAR FLOOR SPACE OF 30" X 48" PER FHAG
 REQ. #2(14) / (ANSI) A117.1-1986 4.19.2.2, 4.19.3
  
 6. SEPARATE PERMITS ARE REQUIRED FOR BACKFLOW
 ASSEMBLIES LOCATED AT METER PLEASE PLACE NOTE ON PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 7. PROVIDE DETAIL WITH THE DIMENSION FOR THE
 ACCESSIBILITY IN THE COMMON BATHROOMS OM THE GROUND
 FLOOR. PER FHAG REQ. #2(14) / (ANSI) A117.1-1986
 A) CLEAR FLOOR SPACE FOR TOILET. 416.2 , 417.3
 B) GRAB BARS 4.17.6
 C) LAVATORY 4.19.2
  
 8. SHT. P- 3.00 PLEASE ENLARGE THE WATER AND SANITARY
 ISOMETRIC DRAWING ON SEPARATE SHEETS THEY ARE TO
 CONGESTED TO DETERMINE CODE COMPLIANCE. PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
  
 9. SHT. P- 3.00 SHOW THE PIPE SIZE ON THE WATER AND
 SANITARY ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 10. P -4.01 THE ELECTRIC WATER HEATER DETAIL HAS THE
 FOLLOWING CODE VIOLATIONS.
 A) IT SHOWS THE T + P RELIEF PIPING DISCHARGING INTO A
 MOP SINK THERE IS NO MOP SINK SHOW THE PIPIG SHALL
 COMPLY WITH FBC PL 504.6. 2.DISCHARGE THROUGH AN AIR
 GAP LOCATED IN THE SAME ROOM AS THE WATER HEATER.
 B)IT SHOWS DRAIN PAN DISCHARGING TO MOP SINK NO MOP
 SINK SHOWN PLEASE CLARIFY
 C) SHOWS WATER HEATER MOUNTED ON SHELF IS THIS CORRECT
 AN 80 GAL HEATER ON THE SHELF IF SO PROVIDE DETAIL FOR
 SHELVING TO HOLD THE WEIGHT OF THE 80 GAL HEATER 800LBS
 + PER WPB AMEND TO FBC 107.2.1
  
 11. A SERVICE SINK IS REQUIRED ON GROUND FLOOR PE FBC
 PL TABLE 403.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-10-13 Cont ID  
Sent By dbattles Date 2018-10-13 Time 10:22 Rev Time 0.00
Received By dbattles Date 2018-10-13 Time 10:22 Sent To  
Notes
2018-10-13 10:22:57ROOFING SUBMITTAL DEFERED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:05 Rev Time 0.00
Received By dbattles Date 2018-08-20 Time 09:04 Sent To  
Notes
2018-08-20 09:04:49[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 11:04 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 11:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 10:56 Rev Time 0.00
Received By dbattles Date 2018-10-29 Time 09:11 Sent To  
Notes
2018-10-29 10:59:13ANY ADDITIONAL SHEETS FOR MECHANICAL REVIEW 4 WILL NEED
 TO BE CHECKED.
2018-10-29 09:11:36DIG SIG ON PLUMB SHT. OK GPJ 10/29/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By dbattles Date 2018-10-15 Time 07:48 Rev Time 0.00
Received By dbattles Date 2018-10-15 Time 07:49 Sent To  
Notes
2018-10-15 07:49:02REVIEW #2 RE-SUB WILL NEED TO BE CHECKED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:02 Rev Time 0.00
Received By dbattles Date 2018-08-20 Time 09:02 Sent To  
Notes
2018-08-20 09:03:23PENDING RE-SUBMITTAL CHECK

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status P Date 2018-11-28 Cont ID  
Sent By dbattles Date 2018-11-28 Time 10:26 Rev Time 0.00
Received By dbattles Date 2018-11-28 Time 10:26 Sent To  
Notes
2018-11-28 10:35:47DIGITAL COPY UPLOADED INTO PROJECT DOX.
 THREE ORIGINALS IN MAIL.- RECEIVED 11/28/18
  
 MORGAN DICKENSON - S.I. INSPECTOR
 954-501-1242
  
 JOHNATHON KLEVAN - INSPECTOR
 561-844-2404

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 10:58 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 10:58 Sent To  
Notes
2018-11-15 11:00:58PENDING UPLOAD OF NOTARIZED COPY TO PROJECT DOX.
 REQUESTED 3 ORIGINALS TO BE DELIVERED TO OFFICE.
  
 PER OUR CONVERSATION WE WILL BE PROVIDING YOU WITH 3
 ORIGINAL COPIES OF THE SIGNED AND NOTARIZED THRESHOLD
 AGREEMENT WHICH WILL BE MAILED TO YOUR OFFICE ADDRESSED
 TO YOU.
  
 TO CONFIRM, YOU ARE ALSO REQUESTING A DIGITAL COPY OF
 THE SIGNED AND NOTARIZED ORIGINALS TO BE UPLOADED. THE
 OWNER/CONTRACTOR PORTION THAT WAS UPLOADED WAS SIGNED
 AND NOTARIZED. WE WILL UPLOAD THE THRESHOLD INSPECTOR
 PORTION OF THE AGREEMENT SIGNED AND NOTARIZED TO
 REPLACE THE ONE THAT WAS SIGNED ONLY AND NOT NOTARIZED.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 10:57 Rev Time 0.00
Received By dbattles Date 2018-10-26 Time 12:52 Sent To  
Notes
2018-10-29 10:57:57REVIEW OF RESUMES IN PROGRESS 10/29/18
  
 I HAVE RESUMES FOR THE THRESHOLD INSPECTOR PLUS ONE
 ADDITIONAL INSPECTOR.
 ONE MORE INSPECTOR ON BOARD WOULD BE BENEFICIAL TO
 PROVIDE ADEQUATE COVERAGE FOR THIS PROJECT.
  
 THE THRESHOLD INSPECTOR AGREEMENT WAS UPLOADED TO
 PROJECT DOX, BUT IT IS ONLY THE LAST PAGE WITH
 CONTRACTOR AND OWNER SIGNATURE.
 PLEASE UPLOAD THE FULL AGREEMENT WITH ALL SIGNATURES.
  
 UPON FINAL REVIEW I WILL REQUEST THREE ORIGINALS TO BE
 SUBMITTED TO THE OFFICE.
  
 THANK YOU,
 DYLAN BATTLES
 561-805-6718
 [email protected]

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By dbattles Date 2018-10-15 Time 07:49 Rev Time 0.00
Received By dbattles Date 2018-10-15 Time 07:49 Sent To  
Notes
2018-10-15 07:51:00PLEASE CONTACT ME TO GET THIS INITIATED, OR TELL ME WHO
 RECEIVED THE THRESHOLD AGREEMENT IS THIS OFFICE.
  
 [F.S. 553.79(5)]THIS IS A THRESHOLD BUILDING. THE
 FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). -(SEE BUILDING COMMENT TO
 INSERT SHEETS)
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:10 Rev Time 0.00
Received By dbattles Date 2018-08-20 Time 09:10 Sent To  
Notes
2018-08-20 09:10:28110.8 THRESHOLD BUILDING.
  
 110.8.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL
 INSPECTOR MAY NOT SERVE AS A
 SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE
 BUILDING OFFICIAL, THE ARCHITECT OR THE
 ENGINEER OF RECORD. THE CONTRACTOR'S CONTRACTUAL OR
 STATUTORY OBLIGATIONS ARE NOT RELIEVED BY
 ANY ACTION OF THE SPECIAL INSPECTOR.
  
 110.8.2 THE SPECIAL INSPECTOR SHALL DETERMINE THAT A
 PROFESSIONAL ENGINEER WHO
 SPECIALIZES IN SHORING DESIGN HAS INSPECTED THE SHORING
 AND RESHORING FOR CONFORMANCE WITH
 THE SHORING AND RESHORING PLANS SUBMITTED TO THE
 ENFORCING AGENCY. A FEE SIMPLE TITLE OWNER
 OF A BUILDING, WHICH DOES NOT MEET THE MINIMUM SIZE,
 HEIGHT, OCCUPANCY, OCCUPANCY
 CLASSIFICATION OR NUMBER-OF-STORIES CRITERIA WHICH
 WOULD RESULT IN CLASSIFICATION AS A THRESHOLD
 BUILDING UNDER S. 553 .71(12), MAY DESIGNATE SUCH
 BUILDING AS A THRESHOLD BUILDING, SUBJECT
 TO MORE THAN THE MINIMUM NUMBER OF INSPECTIONS REQUIRED
 BY THE FLORIDA BUILDING CODE.
 45
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, 6TH EDITION (2017)
 110.8.3 THE FEE OWNER OF A THRESHOLD BUILDING SHALL
 SELECT AND PAY ALL COSTS OF
 EMPLOYING A SPECIAL INSPECTOR, BUT THE SPECIAL
 INSPECTOR SHALL BE RESPONSIBLE TO THE
 ENFORCEMENT AGENCY. THE INSPECTOR SHALL BE A PERSON
 CERTIFIED, LICENSED OR REGISTERED
 UNDER CHAPTER 471, FLORIDA STATUTES, AS AN ENGINEER OR
 UNDER CHAPTER 481, FLORIDA
 STATUTES, AS AN ARCHITECT.
  
 110.8.4 EACH ENFORCEMENT AGENCY SHALL REQUIRE THAT, ON
 EVERY THRESHOLD BUILDING:
  
 110.8.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION OF THE
 BUILDING AND PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY, FILE A SIGNED
 AND SEALED STATEMENT WITH THE
 ENFORCEMENT AGENCY IN SUBSTANTIALLY THE FOLLOWING FORM:
 "TO THE BEST OF MY KNOWLEDGE
 AND BELIEF, THE ABOVE DESCRIBED CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS
 COMPLIES WITH THE PERMITTED DOCUMENTS, AND THE SHORING
 AND RESHORING CONFORMS TO THE
 SHORING AND RESHORING PLANS SUBMITTED TO THE
 ENFORCEMENT AGENCY."
  
 110.8.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH
 BUILDING CODES APPLY SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR REVIEW FOR
 COMPLIANCE WITH THE CODES AND MADE PART OF THE
 ENFORCEMENT AGENCY'S RECORDED SET OF
 PERMIT DOCUMENTS.
  
 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, PLANS
 AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE
 SHORING DOCUMENTS BY THE CONTRACTOR .
  
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633.
 FLORIDA STATUTES.
  
 110.8.5 NO ENFORCING AGENCY MAY ISSUE A BUILDING PERMIT
 FOR CONSTRUCTION OF ANY
 THRESHOLD BUILDING EXCEPT TO A LICENSED GENERAL
 CONTRACTOR, AS DEFINED IN SECTION
 489.105(3) (A), FLORIDA STATUTES, OR TO A LICENSED
 BUILDING CONTRACTOR, AS DEFINED IN SECTION
 489. 105(3) (B), FLORIDA STATUTES, WITHIN THE SCOPE OF
 HER OR HIS LICENSE. THE NAMED
 CONTRACTOR TO WHOM THE BUILDING PERMIT IS ISSUED SHALL
 HAVE THE RESPONSIBILITY FOR
 SUPERVISION, DIRECTION, MANAGEMENT AND CONTROL OF THE
 CONSTRUCTION ACTIVITIES ON THE
 PROJECT FOR WHICH THE BUILDING PERMIT WAS ISSUED.
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM
 STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS REQUIRED
 BY THIS CODE, SECTION 553.73, FLORIDA
 STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE
 BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS
 RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING
 INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR
 UNDER CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS
 OF THRESHOLD BUILDINGS REQUIRED BY
 SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION TO
 THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By llouie Date 2018-09-21 Time   Rev Time 0.00
Received By llouie Date 2018-09-21 Time   Sent To  
Notes
2018-09-21 13:29:26ZONING PROVISOS:
  
 1.) A MINOR SITE PLAN AMENDMENT WILL BE REQUIRED FOR
 THE AS-BUILT PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY (C.O). [REFERENCE: ISPR 16-01A]
  
 2.) SEPARATE PERMITS REQUIRED FOR THE FOLLOWING:
 LANDSCAPING AND IRRIGATION, FENCE.
  
  
 NOTES:
  
 PER THE SITE PLAN CONDITIONAL APPROVAL LETTER, ISSUED
 ON 6/12/18, THE FOLLOWING CONDITIONS APPLY:
  
 1.) NO STRUCTURE ALONG THE NORTH PROPERTY LINE (I.E. 6
 FT. HIGH FENCE) SHALL BE PLACED WITHIN THE 5 FT. WIDE
 UTILITY EASEMENT, UNLESS A HOLD HARMLESS AGREEMENT
 BETWEEN THE PROPERTY OWNER/TENANT AND ALL UTILITY
 PROVIDERS HAS BEEN APPROVED BY THE CITY.
  
 2.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, AN APPLICATION FOR A TREE ALTERATION
 PERMIT SHALL BE SUBMITTED, REVIEWED AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION.
  
  
 ** CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 ANY QUESTIONS. **
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By LL Date 2018-07-10 Time   Rev Time  
Received By llouie Date 2018-07-10 Time   Sent To  
Notes
2018-07-10 12:59:51** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY IS OUTDATED AND DOES NOT REFLECT THE CORRECT
 BOUNDARY LINES OF THE PROPERTY. [NOTE: THE PROPERTY WAS
 REPLATTED IN 2017 BY RESOLUTION NO. 244-17]
  
 2.) SHEET G-0.08 (ZONING CHART): PROVIDED OFFICE SPACE
 SQUARE FOOTAGE OF 1995 SQ. FT. DOES NOT MATCH THE
 APPROVED OFFICE SQUARE FOOTAGE OF 1,902 SQ. FT. PLEASE
 ADDRESS.
  
 3.) INFORMATION ON SHEET G-0.09 HAS INCORRECT
 INFORMATION ON THE MINIMUM UNIT SIZE AND NUMBER OF
 STUDIO APARTMENTS. PLEASE CORRECT.
  
 4.) FLOOR PLAN LAYOUT DOES NOT MATCH THE APPROVED
 PLANS. ADDITIONALLY, THE PLANS SHOULD MATCH ON ALL
 SHEETS FOR CONSISTENCY.
  
 5.) SITE PLAN DOES NOT MATCH THE APPROVED SITE PLAN.
 INCONSISTENCIES HAVE BEEN DETECTED IN THE FLOOR PLAN
 AND SETBACK INFORMATION.
  
 6.) WEST BUILDING ELEVATION IN THE PERMIT SET DOES NOT
 MATCH THE WEST ELEVATION IN THE APPROVED SITE PLAN SET.
 PLEASE ADDRESS.
  
  
 NOTES:
  
 * REFERENCE: ISPR 17-01A (APPROVED 6/12/18) AND ZBA
 3356
  
 * SEPARATE PERMITS REQUIRED FOR LANDSCAPING AND
 IRRIGATION.
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: CMUD-EDGE SUB-DISTRICT
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  