| 2018-06-30 09:22:19 | 06/30/2018 1ST GA REVIEW**DENIED** |
| | |
| | 1) PROVIDE SIGN BONA FIDA CONTRACT SHOWING TOTAL COST |
| | OF JOB. WPB AMEND TO THE FBC 109.3 |
| | |
| | 2) FLOOR PLAN LIST (4) 120 GALLON L.P TANK BUT |
| | ISOMETRIC PLAN SHOWS ONLY (3). PLEASE CLARIFY FBC |
| | 107.2.1 |
| | |
| | 3) PIPING MATERIAL NOT LISTED ON ISOMETRIC. SHOW THE |
| | TYPE OF PIPE MATERIAL BEING INSTALLED, ALL PIPE SIZES, |
| | AND THE CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS STEEL TUBING |
| | (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. |
| | |
| | 4) ISOMETRIC LIST SIZING CHARTS TO BE BASED OFF THE |
| | 2017 6TH OF THE FBC WHICH IS THE CURRENT CODE IN AFFECT |
| | BUT CHARTS PROVIDED ARE 2014. SUBMIT TWO COPIES OF THE |
| | APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR |
| | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 5) PLAN SHOWS INTERIOR GAS PIPING BY OTHERS. SHOW WHERE |
| | YOUR SCOPE OF WORK ENDS. YOUR WORK DESCRIPTION LIST |
| | PIPING UP TO 10' BUT THE 2ND STAGE REGULATOR IS SHOWING |
| | OVER 20'. PLEASE CLARIFY FBC 107.2.1 |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |