Plan Review Details - Permit 18061066
Plan Review Stops For Permit 18061066
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By cthroop Date 2018-07-05 Time 15:00 Rev Time 0.00
Received By cthroop Date 2018-07-05 Time 14:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-29 Cont ID  
Sent By jleahy Date 2018-06-29 Time 16:22 Rev Time 0.00
Received By jleahy Date 2018-06-29 Time 16:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-16 Cont ID  
Sent By lcrespo Date 2018-08-16 Time 06:50 Rev Time 0.00
Received By lcrespo Date 2018-08-16 Time 06:50 Sent To  
Notes
2018-08-16 06:51:3908/16/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By thunt Date 2018-06-30 Time 11:33 Rev Time 0.00
Received By thunt Date 2018-06-30 Time 11:33 Sent To B
Notes
2018-06-30 11:40:3906/30/2018 1ST GAS REVIEW**DENIED**
  
 1) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 2) YOU HAVE NOT INCLUDED THE .5 LB SIZING CHART OE
 LISTED THE MATERIAL BEING USED AFTER THE PRESSURE
 REGULATOR. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3
  
 3) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. FGC SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3
  
 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 5) SHOW CONNECTION AND PIPE SIZING OF WHERE THIS NEW
 LINE IS CONNECTING TO EXISTING GAS SYSTEM. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-16 Cont ID  
Sent By lcrespo Date 2018-08-16 Time 06:50 Rev Time 0.00
Received By lcrespo Date 2018-08-08 Time 15:06 Sent To  
Notes
2018-08-09 15:06:27RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-05 Cont ID  
Sent By cthroop Date 2018-07-05 Time 15:01 Rev Time 0.00
Received By cthroop Date 2018-06-22 Time 12:49 Sent To I
Notes
2018-06-25 12:50:07ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-27 Cont ID  
Sent By mcruz Date 2018-06-27 Time 14:51 Rev Time 0.00
Received By mcruz Date 2018-06-27 Time 14:35 Sent To  
Notes
2018-06-27 14:53:15ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 8.6' FROM REAR PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]