Plan Review Details - Permit 18061049
Plan Review Stops For Permit 18061049
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 11:39 Rev Time 0.00
Received By shill Date 2018-10-06 Time 11:39 Sent To  
Notes
2018-10-06 11:39:33NOTIFIED M.ORIO, ONLY ONE UNIT AT THIS LOCATION
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 11:29 Rev Time 0.00
Received By shill Date 2018-08-12 Time 11:29 Sent To  
Notes
2018-08-12 11:30:38OUR RECORDS, AND PROPERTY RECORDS, SHOW TWO UNITS AT
 THIS LOCATION, #A AND #B. IT APPEARS THAT THERE IS
 CURRENTLY ONLY ONE TENANT.
  
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 11:52 Rev Time 0.00
Received By shill Date 2018-10-06 Time 11:39 Sent To  
Notes
2018-10-06 11:48:39****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE LAST PERMIT FOR THIS SPACE, 12030654, DOES NOT
 MATCH THE FLOOR PLAN SHOWN AS "EXISTING", SEE ATTACHED.
  
 THIS PERMIT INCORPORATES WALLS/ELEMENTS NOTED ON PLAN
 AS "EXISTING" BUT NOT SHOWN ON 12030654. SUBJECT TO
 FIELD INSPECTOR'S DISCRETION, A REVISION WITH DETAILS
 AND ADDITIONAL INFORMATION MAY BE REQUIRED.
  
 2. EXPIRED PERMITS ARE TO BE RESOLVED PRIOR TO FINAL
 INSPECTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 10:40 Rev Time 0.00
Received By shill Date 2018-08-12 Time 10:40 Sent To  
Notes
2018-08-12 11:01:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 406, THE 6000 SF AREA CART STORAGE AREA
 APPEARS TO BE AN "ENCLOSED PARKING GARAGE". FBC B
 406.5.10, MECHANICAL PAGES SHOW "EXISTING" VENTS BUT DO
 NOT SHOW A VENTILATION SYSTEM FOR THE GARAGE AREA. OUR
 RECORDS SHOW THE MOST RECENT PERMIT, 12030654,
 DESIGNATES THE GOLF CART STORAGE AREA SHOWN ON THE
 PROPOSED PLAN AS "PRODUCT STORAGE" FOR A CONSTRUCTION
 PRODUCT COMPANY, AND SOME OF THE OFFICES ARE NOT SHOWN.
  
 IT APPEARS THAT THIS IS A CHANGE OF OCCUPANCY OR USE.
 REVISE PLAN TO SHOW COMPLIANCE.
  
 2. PLEASE SUBMIT A RECORDS RESEARCH REQUEST. IT APPEARS
 THAT SOME ITEMS SHOWN AS "EXISTING" WERE INSTALLED
 WITHOUT A PERMIT, OR INSTALLED WITH A PERMIT BUT PERMIT
 WAS NOT INSPECTED AND CLOSED. PLEASE INCORPORATE
 EXPIRED PERMITS INTO THE SCOPE OF THIS PERMIT. NOTE
 THAT 05120912 MECHANICAL PERMIT FAILED FOR LACK OF A
 SHUT DOWN TEST AND OTHER ITEMS AND WAS NOT RESCHEDULED;
 SUBSEQUENT 16070647 HAS NO INSPECTIONS, BUT THE PLAN
 SHOWS MECHANICAL EQUIPMENT AS "EXISTING".
  
 THE LAST PERMIT FOR THIS SPACE, 12030654, DOES NOT
 MATCH THE FLOOR PLAN SHOWN AS "EXISTING". PLAN SHOULD
 BE REVISED TO SHOW THE SPACES WHICH APPEAR TO HAVE BEEN
 INSTALLED WITHOUT A PERMIT AS "PROPOSED" OR NOTED THAT
 IT WAS PREVIOUSLY INSTALLED WITHOUT A PERMIT AND IS
 BEING LEGALIZED WITH THE CURRENT PROPOSED PERMIT.
  
 3. FBC EB 301.1, APPLICANT IS TO ELECT A METHOD OF
 COMPLIANCE. REVISE PLAN TO INCLUDE FBC 2017 EXISTING
 BUILDING CODE AND METHOD ELECTED FOR THE ALTERATION.
 INDICATE THAT THIS IS A CHANGE OF OCCUPANCY OR USE AS
 APPLICABLE. MOST COMMON METHOD IS FBC EB ALTERATION
 LEVEL II AND FBC EB CHAPTER 10, CHANGE OF OCCUPANCY.
  
 4. FBC 107, PROVIDE A DEMO PLAN. A0.01 STATES THAT
 INTERIOR DEMO WAS DONE UNDER A SEPARATE PERMIT. IT
 APPEARS THAT BATHROOMS AND OTHER ITEMS WERE DEMOLISHED;
 EITHER PROVIDE A PERMIT NUMBER FOR THIS WORK OR
 INCORPORATE THE DEMO WORK DONE WITHOUT PERMIT INTO THIS
 PERMIT.
  
 5. AS I DO NOT HAVE ALL RECORDS READILY AVAILABLE TO
 ME, IT IS NOT CLEAR IF THE OVERHEAD DOORS AND RELATED
 OPENINGS WERE PERMITTED. IF BUILDING ENVELOPE WAS
 AFFECTED BY WORK WITHOUT PERMIT, INCLUDE WIND DESIGN
 CRITERIA, PRODUCT APPROVALS.
  
 6. SOME OF THE ABOVE REQUESTS THAT CERTAIN ITEMS BE
 INCORPORATED INTO THIS PERMIT. IF ARCHITECT, ENGINEER,
 AND/OR CONTRACTOR DO NOT WISH TO TAKE RESPONSIBILITY
 FOR THESE ITEMS, THE WORK INSTALLED WITHOUT A PERMIT
 CAN BE LEGALIZED VIA A SEPARATE PERMIT, BUT THOSE
 ISSUES ARE TO BE RESOLVED PRIOR TO ISSUANCE OF THIS NEW
 PERMIT WHICH CALLS THE WORK INSTALLED WITHOUT PERMIT
 "EXISTING".
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 13:07 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By jpearson Date 2018-08-06 Time 12:38 Rev Time 0.00
Received By jpearson Date 2018-08-06 Time 10:08 Sent To  
Notes
2018-08-06 12:38:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL B SHOWS THE HIGH LEG ON PHASE C. PROVIDE
 CORRECTION. NEC 408.3(E)(1)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-13 Cont ID  
Sent By pleduc Date 2018-09-13 Time   Rev Time 0.00
Received By pleduc Date 2018-09-13 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By pleduc Date 2018-06-26 Time   Rev Time 0.00
Received By pleduc Date 2018-06-25 Time 16:55 Sent To  
Notes
2018-06-26 15:05:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 0.01 - THERE ARE INDICATIONS THAT THIS IS A
 PROPOSED BUSINESS OCCUPANCY WITH ACCESSORY STORAGE.
  
 ON REVIEW OF THE FLORIDA LIFE SAFETY CODE IT WOULD
 APPEAR THAT THIS IS A PROPOSED STORAGE OCCUPANCY WITH
 ACCESSORY BUSINESS. THE SHOWROOM AREA IS MORE STORAGE
 THAT BUSINESS.
  
 PER NFPA 101
  
 3.3.190.3* BUSINESS OCCUPANCY. AN OCCUPANCY USED FOR
 THE
 TRANSACTION OF BUSINESS OTHER THAN MERCANTILE.
 (SAF-MER)
  
 A.3.3.190.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES
 INCLUDE
 THE FOLLOWING:
 (1) AIR TRAFFIC CONTROL TOWERS (ATCTS)
 (2) CITY HALLS
 (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS,
 CLASSROOMS
 UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES
 (4) COURTHOUSES
 (5) DENTISTS? OFFICES
 (6) DOCTORS? OFFICES
 (7) GENERAL OFFICES
 (8) OUTPATIENT CLINICS (AMBULATORY)
 (9) TOWN HALLS
  
 3.3.190.15* STORAGE OCCUPANCY. AN OCCUPANCY USED
 PRIMARILY
 FOR THE STORAGE OR SHELTERING OF GOODS, MERCHANDISE,
 PRODUCTS, OR
 VEHICLES. (SAF-IND)
  
 A.3.3.190.15 STORAGE OCCUPANCY. STORAGE OCCUPANCIES
 INCLUDE
 THE FOLLOWING:
 (1) BARNS
 (2) BULK OIL STORAGE
 (3) COLD STORAGE
 (4) FREIGHT TERMINALS
 (5) GRAIN ELEVATORS
 (6) HANGARS (FOR STORAGE ONLY)
 (7) PARKING STRUCTURES
 (8) TRUCK AND MARINE TERMINALS
 (9) WAREHOUSES
 STORAGE OCCUPANCIES ARE CHARACTERIZED BY THE PRESENCE
 OF
 RELATIVELY SMALL NUMBERS OF PERSONS IN PROPORTION TO
 THE AREA.
  
 HOWEVER, THIS ALSO APPEARS TO BE A MIXED NON-SEPARATED
 OCCUPANCY, WHICH WOULD REQUIRE THE MOST STRINGENT CODE
 REQUIRMENTS OF THE TWO.
  
 38.1.3 MULTIPLE OCCUPANCIES.
 38.1.3.1 GENERAL.
 38.1.3.1.1 ALL MULTIPLE OCCUPANCIES SHALL BE IN
 ACCORDANCE WITH
 6.1.14 AND 38.1.3.
 38.1.3.1.2 WHERE THERE ARE DIFFERENCES IN THE SPECIFIC
 REQUIREMENTS
 IN THIS CHAPTER AND PROVISIONS FOR MIXED OCCUPANCIES OR
 SEPARATED
 OCCUPANCIES AS SPECIFIED IN 6.1.14.3 AND 6.1.14.4, THE
 REQUIREMENTS
 OF THIS CHAPTER SHALL APPLY.
  
 PLEASE REVIEW, CORRECT OR CLARIFY WITH SPECIFIC LIFE
 SAFETY CODE REFERENCES.
  
  
  
 2) SHEET A 2.01 - THOUGH THE CODE MAY ALLOW FOR
 NON-SEPARATED OCCUPANCY, THE HAZARD OF THE STORAGE AREA
 SHALL BE CONSIDERED.
  
 WHAT IS THE COMPLETE EXTENT OF THE STORAGE AREA?
  
 WHAT WORK WILL OCCUR IN THESE SPACES?
  
 WHERE WILL BATTERIES BE STORED?
  
 WILL THERE BE ACID STORED?
  
 WILL THERE BE OIL OR GAS STORED?
  
 PLEASE PROVIDE AS MUCH DETAILED INFORMATION AS
 POSSIBLE.
  
 PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY
  
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL
 BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF
 SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION
 OR OTHER
 OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY
 OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED
 DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL
 ON THE BASIS
 OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR
 OPERATIONS
 CONDUCTED IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD
 GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF
 THE
 BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE
 FOLLOWING
 MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT
 HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH
 SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN
 ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE
 OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 THROUGH 43
  
 A RATED SEPARATION OF HAZARD, NOT JUST OCCUPANCY, MAY
 BE REQUIRED BASED ON THE WHAT IS BEING DONE IN THE
 STORAGE AREAS.
  
 PLEASE REVIEW, CORRECT WITH REQUIRED SEPARATION, OR
 JUSTIFY WITH DETAILS WHY NOT.
  
  
  
  
 3) SHEET A 0.01 - UNDER THE BUILDING AND CONSTRUCTION
 DATA SECTION THERE IS AN INDICATION OF
 "NON-SPRINKLERED"
  
 UNDER THE INTERIOR FINISHES SECTION THERE IS AN
 INDICATION FO "SPRINKLERED"
  
 PLEASE REVIEW AND CORRECT WHICH ONE IS ACCURATE.
  
  
  
  
 4) SHEET A 2.01 THERE IS A NORTH EAST EXIT DOOR
 INDICATING OUTSWING BUT ON SHEET S 1.0 & E 1 THIS SAME
 DOOR IS INDICATED AS INSWING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 5) SHEET A 2.01 THERE IS AN INDICATION OF EXIT TRAVEL
 PATH THROUGH THE EAST DOUBLE DOORS BUT ON SHEET E 2
 THERE IS NO EXIT SIGNAGE OVER THIS DOOR.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY.
  
  
  
  
 6) SHEET A 2.01 AND E 2 - IN THE CENTER BUSINESS AREA
 THERE IS A CORRIDOR. AT THE EAST END OF THE CORRIDAR BY
 THE BREAK AREA THERE IS NO EXIT SIGN. PEOPLE IN THIS
 CORRIDOR NEED TO BE DIRECTED TO NEAREST EXIT.
  
 PLEASE PALCE AN EXIT SIGN AND THE END OF THE CORRIDOR
 BY THE BREAK AREA.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 11:53 Rev Time 0.00
Received By shill Date 2018-09-27 Time 11:57 Sent To  
Notes
2018-10-01 11:59:21GIVEN TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-24 Cont ID  
Sent By lmarchan Date 2018-09-24 Time 15:40 Rev Time 0.00
Received By lmarchan Date 2018-09-07 Time 15:37 Sent To  
Notes
2018-09-11 15:37:22C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 11:25 Rev Time 0.00
Received By gjohnson Date 2018-06-21 Time 15:14 Sent To  
Notes
2018-06-22 15:14:23B12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 11:39 Rev Time 0.00
Received By shill Date 2018-10-06 Time 11:39 Sent To  
Notes
2018-10-06 11:40:06PLAN STAMPED; $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 11:20 Rev Time 0.00
Received By shill Date 2018-08-12 Time 11:20 Sent To  
Notes
2018-08-12 11:25:13PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-18 Cont ID  
Sent By ccole Date 2018-09-17 Time 12:42 Rev Time 0.00
Received By ccole Date 2018-09-17 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By ccole Date 2018-07-10 Time 10:02 Rev Time 0.00
Received By ccole Date 2018-07-10 Time 07:14 Sent To  
Notes
2018-07-10 10:18:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061049
 7/10/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CART STORAGE GARAGE REQUIRES AN EXHAUST
 VENTILATION SYSTEM THAT IS IN COMPLIANCE WITH SECTION
 404 FBC M. IN ADDITION, PLEASE REFER TO SECTIONS 502.3-
 502.5.3 FBC M PERTAINING TO CART BATTERIES AND BATTERY
 CHARGING AND STORAGE AREA. MORE INFORMATION IS REQUIRED
 FOR A COMPLETE REVIEW INCLUDING THE NUMBER AND
 LOCATIONS OF CARTS BEING STORED, THE TYPE OF BATTERIES,
 AND THE BATTERY CHARGING AND STORAGE AREAS. PLEASE
 INCLUDE EXHAUST VENTLATION CALCULATIONS WITH THE
 REVISED PLANS AND DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By gjohnson Date 2018-09-24 Time 15:35 Rev Time 0.00
Received By gjohnson Date 2018-09-24 Time 15:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 11:25 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 10:34 Sent To  
Notes
***NONE***