| Plan Review Stops For Permit 18061038 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-11 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-11 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2018-12-11 08:54:51 | PROVISOS: | | | | | | 1) ELEVATION CERTIFICATE | | | A. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT | | | APPLICATION 1979 FIRMS + 2' FREEBOARD; MINIMUM | | | ELEVATION = 9.0' NAV88, PROPOSED LOWEST FINISHED FLOOR | | | ELEVATION = 9.0' NAV88. | | | A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE | | | OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE | | | POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW | | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS | | | REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR | | | TCO. | | | | | | 2) [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND | | | SOLAR TUBES AS A SUBMITTAL. | | | | | | 3) [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD | | | RAIL ENGINEERING AS A SUBMITTAL. | | | | | | 4) [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO | | | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-14 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-14 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2018-07-14 10:42:40 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18061038 (MAIN HOUSE) | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | IMPACT FEES WILL APPLY | | | | | | 1. [107.3.5.3.1]PROVIDE "CONSTRUCTION DOCUMENTS" | | | ELEVATION CERTIFICATE WITH DESIGN FLOOD ELEVATIONS TO | | | INCLUDE ANY MECHANICAL EQUIPMENT AS APPLICABLE. | | | | | | 2. [FBC R322.2.1]THE CITY OF WPB HAS ADOPTED A 2? | | | FREEBOARD ABOVE B.F.E. SEE AMENDMENT TO FBC R322.2.1 IN | | | ORD. NO. 4765-18, ? 2, 3-12-2018(SEC 18-33). SEE | | | COMMENTS REGARDING FLOOD VENTS. | | | | | | 3. [FBC R107.2.5]PROVIDE SURVEY OF PROPERTY. | | | | | | 4. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING | | | CAPACITY. | | | | | | 5. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. THE COVER | | | SHEETS CALL FOR C-1, C-2 & EC-1. THESE SHEETS ARE NOT | | | PROVIDED SO I CANNOT REVIEW THE DRAINAGE AT THIS TIME. | | | PLEASE PROVIDE MISSING SHEETS TO SHOW DRAINAGE PLAN. | | | | | | 6. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND | | | SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM | | | DEFFERED. THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE | | | APPROVED BY THE BUILDING OFFICIAL PRIOR TO | | | INSTALLATION. | | | | | | 7. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR | | | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. | | | THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE APPROVED BY | | | THE BUILDING OFFICIAL PRIOR TO INSTALLATION. | | | | | | 8. [FBC 107.2.1.2]OTHER DEFFRRED SUBMITTALS INCLUDE | | | STAIRCASES, GUARD RAILS AND TRUSS PACKAGE. | | | | | | 9. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO | | | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. | | | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. | | | | | | 10. NO ENERGY CALCULATIONS PROVIDED, SO I BELIEVE YOU | | | ARE GOING WITH PRESCIPTIVE. PLEASE FOLLOW ALL | | | RESIDENTIAL ENEGRY CODE SECTIONS R410-R404 AND INDICATE | | | ON PLANS HOW YOU ARE MEETING THE CODE. | | | BELOW ARE SOME, BUT NOT ALL, APPLICABLE ITEMS FOR | | | REFERENCE. | | | [R401.3]ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD. | | | [R402.2.4]ACCESS HATCHES AND DOORS. | | | [R402.3.2]GLAZED FENESTRATION SHGC | | | [TABLE R402.1.2]ASSIGN R-VALUES FROM THIS TABLE FOR | | | MASS WALLS AND FLOOR(GARAGE/STORAGE ABV.) | | | | | | 11. [FBC ENERGY TABLE R402.1.2]THE ENERGY CODE REQUIRES | | | MINIMUM R-30 AT CEILING. | | | [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(SEE ESR-3458 | | | OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH THICKNESS | | | NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND | | | SMOKE DEVELOPED INDEX. | | | [FBC 2603.4.1.6]PROVIDE IGNITION BARRIER FOR AIR | | | HANDLERS IN ATTIC SPACE WHERE ICYNENE IS PRESENT. | | | | | | 12. [FBC R807]SHOW LOCATION AND SIZE OF ATTIC ACCESS ON | | | PLANS. | | | | | | 13. [FBC R322.2.2]SHOW FLOOD VENT CALCULATIONS FOR | | | GARAGE. PAGE M1.1 STATES THAT THESE VENTS ARE 12" OFF | | | THE GROUND. FOLLOW R322.2.2.1 FOR INSTALLATION HEIGHTS | | | OF FLOOD VENTS. ENGINEERING, CALCULATION, OR PRODUCT | | | APPROVAL REQUIRED. | | | | | | 14. [FBC R312.2]WINDOW FALL PROTECTION. INDICATE ON | | | PLANS WHERE THIS IS APPLICABLE. IT LOOKS LIKE THE | | | WINDOWS ABOVE GARAGE S-1/A302 NEED PROTECTION, BUT I | | | CANT TELL IN THE MAIN HOUSE BEDROOMS. SECTION S-4/A303 | | | DOESN'T SHOW WINDOW HEIGHT IN BEDROOM. | | | | | | 15. [FBC R1001.1]PROVIDE CHIMENY DETAILS TO SHOW | | | COMPLIANCE WITH CHAPTER 10 FOR RESIDENTIAL CHIMENY | | | SHOWN ON SOUTH LIVING ROOM WALL. IS THE NORTH CHIMENY | | | FUNCTIONAL? | | | | | | 16. [FBC R803.2.3.1]SHEATHING FASTENING ON 2/S4 CALLS | | | FOR 10D, BUT SHEATHING NAILS NEED TO BE RING SHANK | | | RSRS01(2 3/8 X 0.113) | | | | | | 17. [FBC 107.2.5]HOW DOES AHU #5 WORK IN THIS OPEN | | | STAIR AREA? IT APPEARS TO BE IN THE 1ST FLOOR STORAGE | | | UNDER STAIRS. DUCTS GO OUT FROM THERE, BUT THERE IS NO | | | ATTIC SPACE IN THE STAIR OPENING. PLEASE UPDATE TO SHOW | | | HOW AHU #5 WILL FIT IN SPACE PROVIDED. | | | ALSO, AHU #4 LOOKS LIKE IT IS ON A STAND IN THE 2ND | | | FLOOR STORAGE. IT SHOWS THAT IT IS A SMALL CLOSET WITH | | | RETURN ON THE WALL. PLEASE SHOW THIS CLOSET ON OTHER | | | DRAWINGS FOR SIZING, OR ADJUST AHU #4 ACCORDINGLY TO | | | HOW IT IS PLACED. | | | | | | 18. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE | | | IS REQUIRED PRIOR TO CONCRETE POUR | | | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS | | | REQUIRED PRIOR TO C.O. | | | | | | NOTE: | | | A RESPONSE LETTER IS HELPFUL TO EXPEDITE PLAN REVIEW. | | | | | | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-12-03 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-12-03 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-08 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-08 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2018-07-08 16:42:23 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET E0.1, LIGHTING ENERGY CONSERVATION NOTE | | | SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE | | | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) | | | 2. SHEET E0.1, CONSTRUCTION ELECTRICAL NOTES, NOTE 1FOR | | | AFCI PROTECTION SPECIFIES THE WONG CODE FOR DESIGN AND | | | DOES NOT INCLUDE ALL AREAS REQUIRED TO HAVE AFCI | | | PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. SOME | | | AREAS WILL REQUIRE BOTH AFCI AND GFCI PROTECTION. | | | PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES | | | ABOVE); NEC 210.12 | | | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | 4. SHEEY E3.1, REMOVE ITEMS NOT ASSOCIATED WITH THIS | | | PLAN SUCH AS GENERATOR LOAD SHED CALCULATIONS AND | | | GENERATOR NOTES. FYI, WHY IS THERE A 40% REDUCTION OF | | | THE LOADS BEING SHED FROM GENERATOR? THEY WOULD EITHER | | | BE SHED COMPLETELY OR NOT, THERE IS NO DEMAND FACTOR | | | FOR THIS. WPB FBC 107.2.1 | | | 5. RECEPTACLES IS STORAGE AREAS REQUIRE GFCI | | | PROTECTION. PROVIDE CORRECTION. NEC 210.8 | | | 6. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC | | | 210.8(D) | | | 7. PANEL SCHEDULES DO NOT INDICATE THE REQUIRED AFCI | | | PROTECTION PER NOTES FOR EACH PANEL. SOME CIRCUITS | | | REQUIRE AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. | | | NEC 210.8, 210.12, 408.4; WPB FBC 107.2.1 | | | 8. PANEL SCHEDULE FOR PANEL P IS INCOMPLETE. HOW IS THE | | | LOAD FOR THIS PANEL DETERMINED WITH NO DESCRIPTION. | | | PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 220, 408.4 | | | 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94 | | | 10. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 11. PROVIDE AIC RATING OF TRANSFER SWITCH AND PANELS. | | | NEC 110.3, 110.9 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-12-28 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-12-28 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2018-12-28 12:51:16 | 12/28/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-07-26 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-07-26 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2018-07-26 17:23:38 | 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | SOME COMMENT MAY NOT APPLY BUT ARE PROVIDED FOR | | | REFERENCES. | | | | | | 1. ISOMETRIC DRAWING NEED TO CLEARLY SHOW THE LENGTH OF | | | ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS RES | | | SECS. G2413.4.1, G2413.4.2. | | | 2. GAS METER SHOWN DOWNSTREAM OF REGULATOR SHUTOFF | | | VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP | | | REGULATOR. 2017 FBC FUEL GAS RES. SEC. G2420.4. | | | 3. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) ON | | | ISOMETRIC P0.4. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 4. SHOW ALL SHUT-OFF VALVE TO EACH APPLIANCE IN | | | ISOMETRIC, 2017 FBC FUEL GAS SEC. 409.4, FBC FUEL GAS | | | RES. SEC. G2420.4 | | | 5. THE PLANS ON P1.1 SHOWS A GAS DRYER DOWNSTAIRS BUT | | | ON THE P1.2 SECOND FLOOR SHOWS THE SECOND DRYER BUT NOT | | | LABELED AS GAS OR NO GAS SHOWN TO IT. IS IT GAS AND IF | | | IT IS PLEASE LABEL ON PLANS, WPB AMENDMENTS TO THE FBC | | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR GAS | | | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE | | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC R | | | G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR | | | SYSTEM. | | | 7. PLEASE SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, | | | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND | | | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL | | | GAS RES. SECS. G2426 THRU G2429.1 | | | 8. PLEASE SHOW ALL SHUTOFF VALVES ON GAS ISOMERIC, 2017 | | | FBC FUEL GAS RES. SEC. 404.15, 411. | | | 9. WATER HEATERS WILL REQUIRE A SEPARATE IGNITION | | | SOURCE AND IT IS BEING LABELED ON A SEPARATE CIRCUIT | | | FOR IGNITION ON TANKLESS, WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 10. PLEASE PROVIDE ON ALL APPLIANCES MANUFACTURES | | | SPECIFICATION, FBC FG R2434.1 GENERAL. | | | 11. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1. | | | 12. PLEASE SUBMIT TWO COPIES OF THE APPLICABLE SIZING | | | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON | | | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) | | | FROM THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN | | | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC | | | FUEL GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, | | | & G2413.3. | | | 13. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION 2017 FBC FUEL GAS SEC. 402.2 AND 301.3 OR | | | 2017 FBC FUEL GAS RES. SEC. G2413.2 AND G2404.3. | | | 14. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER | | | A ROOF. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE | | | GRILL TO VERIFY IF THE HOOD IS NEEDED. FGC SEC.305.1, | | | FBC-RES. SEC.G2408.1. | | | 15. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND | | | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR | | | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION | | | OF THE WATER HEATER SHALL COMPLY WITH THE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE | | | PLAN CAN BE HAND DRAWN. WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 16. SUBMIT SPECIFICATION FOR THE GENERATOR. THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR SHALL | | | BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL | | | BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE | | | GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-01-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-01-09 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-01-09 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2019-01-09 11:39:11 | IMPACT ROUTED TO DBATTLES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-01-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-01-08 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-01-03 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2019-01-04 14:24:48 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-12-28 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-11-19 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-07-26 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-06-21 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2019-01-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-01-09 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-01-09 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2019-01-09 16:14:02 | STAMP ON PLANS-OK | | | MU-2018-007041-0000 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-11 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-11 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2018-12-11 09:02:25 | UPON APPROVAL OF ZONING, GAS, MECHANICAL AND PLUMBING | | | CHECK OUT ONE SET OF DRAWINGS TO TAKE TO PBC FOR IMPACT | | | REVIEW. | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-07-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-14 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-14 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2018-07-14 11:56:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE, IF APPLICABLE, PROVIDED. | | | | | | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET | | | OF PLANS TO TAKE TO THE COUNTY. | | | | | | 561-233-5025 FOR MORE INFORMATION | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-12-12 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-12-12 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2018-12-12 14:38:07 | PASS PROVISO | | | 1) PROVIDE DUCT SIZE FOR 1ST FLOOR STORAGE ROOM 136 | | | SECTION 107 FBC 2017 FOR 1ST INSPECTION. | | | 2) PROVIDE RETURN AIR DUCT IN HER OFFICE ROOM 114 1ST | | | FLOOR | | | SECTION M1602.3 BALANCED RETURN AIR 2017 RESIDENTIAL | | | CODE. | | | 3) REFER TO SECTION M1305 APPLIANCE ACCESS FOR | | | INSPECTION | | | SERVICE, REPAIR AND REPLACEMENT 2017 RESIDENTIAL CODE. | | | 4) REFER TO SECTION 403.3.6 AIR HANDLING UNITS 2017 | | | FLORIDA ENERGY CODE. | | | HAVE ALL 4 COMMENTS COMPLETED FOR 1ST INSPECTION. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-07-19 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-07-19 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2018-07-19 15:27:06 | PLAN DENIED | | | 1) REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE | | | SIZING | | | 2017 RESIDENTIAL CODE | | | 2) THERE WERE NO MECHANICAL PLAN SUBMITTED FOR PERMIT | | | 18061039 | | | 3) SPECIAL FLOOD ZONE AREA AE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-11 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-11 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2018-12-11 09:03:09 | SEE PROVISO IN BUILDING REVIEW. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2018-07-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-14 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-14 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2018-07-14 11:56:24 | SEE BUILDING REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-12-28 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-12-28 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2018-12-28 12:52:00 | 12/28/18 REVIEWED FOR CODE COMPLIANCE | | | (PLUMBING/BACKFLOW) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-07-26 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-07-26 |
Time |
17:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-11 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-11 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-01-08 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-01-08 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-01-08 |
Time |
14:32 |
Sent To |
PC |
|
| Notes |
| 2019-01-08 14:33:31 | CHIMNEY SHALL NOT EXCEED 33' FEET MEASURED FROM GRADE. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-12-05 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-12-05 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-12-05 |
Time |
09:26 |
Sent To |
PC |
|
| Notes |
| 2018-12-05 09:55:13 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | REPEAT COMMENT-- | | | 1) CHIMNEY EXCEEDS HEIGHT LIMITATION. PURSUANT TO SEC. | | | 94-306(A) - HEATING, VENTILATION, AND AIR CONDITIONING | | | EQUIPMENT; CHURCH STEEPLES, BELL TOWERS, FLAG POLES, | | | CHIMNEYS, PARAPETS, STAIR ENCLOSURES, TANKS, DECORATIVE | | | FEATURES, ELEVATOR HOISTWAYS OR EQUIPMENT, TELEVISION | | | OR RADIO ANTENNAS, AND RELATED MECHANICAL OR FUNCTIONAL | | | FEATURES MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN | | | PERCENT. ****NOTE: MAXIMUM DIMENSION FOR CHIMNEY IS 3' | | | ABOVE THE HEIGHT OF HOUSE.**** | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-16 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-16 |
Time |
10:59 |
Sent To |
PC |
|
| Notes |
| 2018-07-16 12:29:47 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) CHIMNEY EXCEEDS HEIGHT LIMITATION. PURSUANT TO SEC. | | | 94-306(A) - HEATING, VENTILATION, AND AIR CONDITIONING | | | EQUIPMENT; CHURCH STEEPLES, BELL TOWERS, FLAG POLES, | | | CHIMNEYS, PARAPETS, STAIR ENCLOSURES, TANKS, DECORATIVE | | | FEATURES, ELEVATOR HOISTWAYS OR EQUIPMENT, TELEVISION | | | OR RADIO ANTENNAS, AND RELATED MECHANICAL OR FUNCTIONAL | | | FEATURES MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN | | | PERCENT. | | | 2) PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] |
|
|