Plan Review Details - Permit 18061038
Plan Review Stops For Permit 18061038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 09:00 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 08:59 Sent To  
Notes
2018-12-11 08:54:51PROVISOS:
  
 1) ELEVATION CERTIFICATE
 A. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA; FLOOD MAP IN EFFECT AT TIME OF FOUNDATION PERMIT
 APPLICATION 1979 FIRMS + 2' FREEBOARD; MINIMUM
 ELEVATION = 9.0' NAV88, PROPOSED LOWEST FINISHED FLOOR
 ELEVATION = 9.0' NAV88.
 A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE
 OR FORM BOARD SURVEY IS REQUIRED PRIOR TO CONCRETE
 POUR. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO FINAL INSPECTION AND/OR CO AND/OR
 TCO.
  
 2) [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND
 SOLAR TUBES AS A SUBMITTAL.
  
 3) [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD
 RAIL ENGINEERING AS A SUBMITTAL.
  
 4) [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-14 Cont ID  
Sent By cthroop Date 2018-07-14 Time 10:42 Rev Time 0.00
Received By shill Date 2018-07-14 Time 10:42 Sent To  
Notes
2018-07-14 10:42:40****CORRECTIONS****
 W.P.B. PERMIT: 18061038 (MAIN HOUSE)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEES WILL APPLY
  
 1. [107.3.5.3.1]PROVIDE "CONSTRUCTION DOCUMENTS"
 ELEVATION CERTIFICATE WITH DESIGN FLOOD ELEVATIONS TO
 INCLUDE ANY MECHANICAL EQUIPMENT AS APPLICABLE.
  
 2. [FBC R322.2.1]THE CITY OF WPB HAS ADOPTED A 2?
 FREEBOARD ABOVE B.F.E. SEE AMENDMENT TO FBC R322.2.1 IN
 ORD. NO. 4765-18, ? 2, 3-12-2018(SEC 18-33). SEE
 COMMENTS REGARDING FLOOD VENTS.
  
 3. [FBC R107.2.5]PROVIDE SURVEY OF PROPERTY.
  
 4. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY.
  
 5. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. THE COVER
 SHEETS CALL FOR C-1, C-2 & EC-1. THESE SHEETS ARE NOT
 PROVIDED SO I CANNOT REVIEW THE DRAINAGE AT THIS TIME.
 PLEASE PROVIDE MISSING SHEETS TO SHOW DRAINAGE PLAN.
  
 6. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS, TRANSOMS, SLIDERS AND
 SOLAR TUBES, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED. THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE
 APPROVED BY THE BUILDING OFFICIAL PRIOR TO
 INSTALLATION.
  
 7. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
 THE DEFERRED SUBMITTAL DOCUMENTS SHALL BE APPROVED BY
 THE BUILDING OFFICIAL PRIOR TO INSTALLATION.
  
 8. [FBC 107.2.1.2]OTHER DEFFRRED SUBMITTALS INCLUDE
 STAIRCASES, GUARD RAILS AND TRUSS PACKAGE.
  
 9. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 10. NO ENERGY CALCULATIONS PROVIDED, SO I BELIEVE YOU
 ARE GOING WITH PRESCIPTIVE. PLEASE FOLLOW ALL
 RESIDENTIAL ENEGRY CODE SECTIONS R410-R404 AND INDICATE
 ON PLANS HOW YOU ARE MEETING THE CODE.
 BELOW ARE SOME, BUT NOT ALL, APPLICABLE ITEMS FOR
 REFERENCE.
 [R401.3]ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD.
 [R402.2.4]ACCESS HATCHES AND DOORS.
 [R402.3.2]GLAZED FENESTRATION SHGC
 [TABLE R402.1.2]ASSIGN R-VALUES FROM THIS TABLE FOR
 MASS WALLS AND FLOOR(GARAGE/STORAGE ABV.)
  
 11. [FBC ENERGY TABLE R402.1.2]THE ENERGY CODE REQUIRES
 MINIMUM R-30 AT CEILING.
 [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(SEE ESR-3458
 OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH THICKNESS
 NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX.
 [FBC 2603.4.1.6]PROVIDE IGNITION BARRIER FOR AIR
 HANDLERS IN ATTIC SPACE WHERE ICYNENE IS PRESENT.
  
 12. [FBC R807]SHOW LOCATION AND SIZE OF ATTIC ACCESS ON
 PLANS.
  
 13. [FBC R322.2.2]SHOW FLOOD VENT CALCULATIONS FOR
 GARAGE. PAGE M1.1 STATES THAT THESE VENTS ARE 12" OFF
 THE GROUND. FOLLOW R322.2.2.1 FOR INSTALLATION HEIGHTS
 OF FLOOD VENTS. ENGINEERING, CALCULATION, OR PRODUCT
 APPROVAL REQUIRED.
  
 14. [FBC R312.2]WINDOW FALL PROTECTION. INDICATE ON
 PLANS WHERE THIS IS APPLICABLE. IT LOOKS LIKE THE
 WINDOWS ABOVE GARAGE S-1/A302 NEED PROTECTION, BUT I
 CANT TELL IN THE MAIN HOUSE BEDROOMS. SECTION S-4/A303
 DOESN'T SHOW WINDOW HEIGHT IN BEDROOM.
  
 15. [FBC R1001.1]PROVIDE CHIMENY DETAILS TO SHOW
 COMPLIANCE WITH CHAPTER 10 FOR RESIDENTIAL CHIMENY
 SHOWN ON SOUTH LIVING ROOM WALL. IS THE NORTH CHIMENY
 FUNCTIONAL?
  
 16. [FBC R803.2.3.1]SHEATHING FASTENING ON 2/S4 CALLS
 FOR 10D, BUT SHEATHING NAILS NEED TO BE RING SHANK
 RSRS01(2 3/8 X 0.113)
  
 17. [FBC 107.2.5]HOW DOES AHU #5 WORK IN THIS OPEN
 STAIR AREA? IT APPEARS TO BE IN THE 1ST FLOOR STORAGE
 UNDER STAIRS. DUCTS GO OUT FROM THERE, BUT THERE IS NO
 ATTIC SPACE IN THE STAIR OPENING. PLEASE UPDATE TO SHOW
 HOW AHU #5 WILL FIT IN SPACE PROVIDED.
 ALSO, AHU #4 LOOKS LIKE IT IS ON A STAND IN THE 2ND
 FLOOR STORAGE. IT SHOWS THAT IT IS A SMALL CLOSET WITH
 RETURN ON THE WALL. PLEASE SHOW THIS CLOSET ON OTHER
 DRAWINGS FOR SIZING, OR ADJUST AHU #4 ACCORDINGLY TO
 HOW IT IS PLACED.
  
 18. THIS PERMIT WILL BE ISSUED WITH PROVISO:
 A "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE
 IS REQUIRED PRIOR TO CONCRETE POUR
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO C.O.
  
 NOTE:
 A RESPONSE LETTER IS HELPFUL TO EXPEDITE PLAN REVIEW.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-03 Cont ID  
Sent By jpearson Date 2018-12-03 Time 14:14 Rev Time 0.00
Received By jpearson Date 2018-12-03 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-08 Cont ID  
Sent By jpearson Date 2018-07-08 Time 16:42 Rev Time 0.00
Received By jpearson Date 2018-07-08 Time 14:12 Sent To  
Notes
2018-07-08 16:42:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E0.1, LIGHTING ENERGY CONSERVATION NOTE
 SPECIFIES THE WRONG CODE FOR DESIGN. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. SHEET E0.1, CONSTRUCTION ELECTRICAL NOTES, NOTE 1FOR
 AFCI PROTECTION SPECIFIES THE WONG CODE FOR DESIGN AND
 DOES NOT INCLUDE ALL AREAS REQUIRED TO HAVE AFCI
 PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. SOME
 AREAS WILL REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES
 ABOVE); NEC 210.12
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 4. SHEEY E3.1, REMOVE ITEMS NOT ASSOCIATED WITH THIS
 PLAN SUCH AS GENERATOR LOAD SHED CALCULATIONS AND
 GENERATOR NOTES. FYI, WHY IS THERE A 40% REDUCTION OF
 THE LOADS BEING SHED FROM GENERATOR? THEY WOULD EITHER
 BE SHED COMPLETELY OR NOT, THERE IS NO DEMAND FACTOR
 FOR THIS. WPB FBC 107.2.1
 5. RECEPTACLES IS STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D)
 7. PANEL SCHEDULES DO NOT INDICATE THE REQUIRED AFCI
 PROTECTION PER NOTES FOR EACH PANEL. SOME CIRCUITS
 REQUIRE AFCI AND GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8, 210.12, 408.4; WPB FBC 107.2.1
 8. PANEL SCHEDULE FOR PANEL P IS INCOMPLETE. HOW IS THE
 LOAD FOR THIS PANEL DETERMINED WITH NO DESCRIPTION.
 PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 220, 408.4
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 10. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 11. PROVIDE AIC RATING OF TRANSFER SWITCH AND PANELS.
 NEC 110.3, 110.9
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By lcrespo Date 2018-12-28 Time 12:50 Rev Time 0.00
Received By lcrespo Date 2018-12-28 Time 07:12 Sent To  
Notes
2018-12-28 12:51:1612/28/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 17:21 Rev Time 0.00
Received By lcrespo Date 2018-07-26 Time 17:21 Sent To  
Notes
2018-07-26 17:23:381ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 SOME COMMENT MAY NOT APPLY BUT ARE PROVIDED FOR
 REFERENCES.
  
 1. ISOMETRIC DRAWING NEED TO CLEARLY SHOW THE LENGTH OF
 ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2. GAS METER SHOWN DOWNSTREAM OF REGULATOR SHUTOFF
 VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR. 2017 FBC FUEL GAS RES. SEC. G2420.4.
 3. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) ON
 ISOMETRIC P0.4. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW ALL SHUT-OFF VALVE TO EACH APPLIANCE IN
 ISOMETRIC, 2017 FBC FUEL GAS SEC. 409.4, FBC FUEL GAS
 RES. SEC. G2420.4
 5. THE PLANS ON P1.1 SHOWS A GAS DRYER DOWNSTAIRS BUT
 ON THE P1.2 SECOND FLOOR SHOWS THE SECOND DRYER BUT NOT
 LABELED AS GAS OR NO GAS SHOWN TO IT. IS IT GAS AND IF
 IT IS PLEASE LABEL ON PLANS, WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC R
 G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
 7. PLEASE SUBMIT A DETAIL SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL
 GAS RES. SECS. G2426 THRU G2429.1
 8. PLEASE SHOW ALL SHUTOFF VALVES ON GAS ISOMERIC, 2017
 FBC FUEL GAS RES. SEC. 404.15, 411.
 9. WATER HEATERS WILL REQUIRE A SEPARATE IGNITION
 SOURCE AND IT IS BEING LABELED ON A SEPARATE CIRCUIT
 FOR IGNITION ON TANKLESS, WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 10. PLEASE PROVIDE ON ALL APPLIANCES MANUFACTURES
 SPECIFICATION, FBC FG R2434.1 GENERAL.
 11. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1.
 12. PLEASE SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC
 FUEL GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2,
 & G2413.3.
 13. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION 2017 FBC FUEL GAS SEC. 402.2 AND 301.3 OR
 2017 FBC FUEL GAS RES. SEC. G2413.2 AND G2404.3.
 14. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER
 A ROOF. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE
 GRILL TO VERIFY IF THE HOOD IS NEEDED. FGC SEC.305.1,
 FBC-RES. SEC.G2408.1.
 15. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 16. SUBMIT SPECIFICATION FOR THE GENERATOR. THE
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR SHALL
 BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR SHALL
 BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-09 Cont ID  
Sent By dbattles Date 2019-01-09 Time 16:13 Rev Time 0.00
Received By dbattles Date 2019-01-09 Time 11:39 Sent To  
Notes
2019-01-09 11:39:11IMPACT ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-08 Cont ID  
Sent By cpuell Date 2019-01-08 Time 15:18 Rev Time 0.00
Received By cpuell Date 2019-01-03 Time 14:24 Sent To  
Notes
2019-01-04 14:24:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-28 Cont ID  
Sent By lcrespo Date 2018-12-28 Time 12:50 Rev Time 0.00
Received By lcrespo Date 2018-11-19 Time 14:25 Sent To  
Notes
2018-11-19 14:25:30R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 17:27 Rev Time 0.00
Received By lcrespo Date 2018-06-21 Time 13:17 Sent To  
Notes
2018-06-21 13:17:31R41

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-01-09 Cont ID  
Sent By dbattles Date 2019-01-09 Time 16:13 Rev Time 0.00
Received By dbattles Date 2019-01-09 Time 16:13 Sent To  
Notes
2019-01-09 16:14:02STAMP ON PLANS-OK
 MU-2018-007041-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 09:00 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 09:00 Sent To  
Notes
2018-12-11 09:02:25UPON APPROVAL OF ZONING, GAS, MECHANICAL AND PLUMBING
 CHECK OUT ONE SET OF DRAWINGS TO TAKE TO PBC FOR IMPACT
 REVIEW.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 11:55 Rev Time 0.00
Received By shill Date 2018-07-14 Time 11:55 Sent To  
Notes
2018-07-14 11:56:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-12 Cont ID  
Sent By hmoser Date 2018-12-12 Time 14:38 Rev Time 0.00
Received By hmoser Date 2018-12-12 Time 09:53 Sent To  
Notes
2018-12-12 14:38:07PASS PROVISO
 1) PROVIDE DUCT SIZE FOR 1ST FLOOR STORAGE ROOM 136
 SECTION 107 FBC 2017 FOR 1ST INSPECTION.
 2) PROVIDE RETURN AIR DUCT IN HER OFFICE ROOM 114 1ST
 FLOOR
 SECTION M1602.3 BALANCED RETURN AIR 2017 RESIDENTIAL
 CODE.
 3) REFER TO SECTION M1305 APPLIANCE ACCESS FOR
 INSPECTION
 SERVICE, REPAIR AND REPLACEMENT 2017 RESIDENTIAL CODE.
 4) REFER TO SECTION 403.3.6 AIR HANDLING UNITS 2017
 FLORIDA ENERGY CODE.
 HAVE ALL 4 COMMENTS COMPLETED FOR 1ST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By hmoser Date 2018-07-19 Time 15:13 Rev Time 0.00
Received By hmoser Date 2018-07-19 Time 15:13 Sent To  
Notes
2018-07-19 15:27:06PLAN DENIED
 1) REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING
 2017 RESIDENTIAL CODE
 2) THERE WERE NO MECHANICAL PLAN SUBMITTED FOR PERMIT
 18061039
 3) SPECIAL FLOOD ZONE AREA AE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 09:02 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 09:02 Sent To  
Notes
2018-12-11 09:03:09SEE PROVISO IN BUILDING REVIEW.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 11:56 Rev Time 0.00
Received By shill Date 2018-07-14 Time 11:56 Sent To  
Notes
2018-07-14 11:56:24SEE BUILDING REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By lcrespo Date 2018-12-28 Time 12:50 Rev Time 0.00
Received By lcrespo Date 2018-12-28 Time 07:11 Sent To  
Notes
2018-12-28 12:52:0012/28/18 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 17:27 Rev Time 0.00
Received By lcrespo Date 2018-07-26 Time 17:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 13:25 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 13:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-08 Cont ID  
Sent By mcruz Date 2019-01-08 Time 14:32 Rev Time 0.00
Received By mcruz Date 2019-01-08 Time 14:32 Sent To PC
Notes
2019-01-08 14:33:31CHIMNEY SHALL NOT EXCEED 33' FEET MEASURED FROM GRADE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-05 Cont ID  
Sent By mcruz Date 2018-12-05 Time 09:55 Rev Time 0.00
Received By mcruz Date 2018-12-05 Time 09:26 Sent To PC
Notes
2018-12-05 09:55:13ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 REPEAT COMMENT--
 1) CHIMNEY EXCEEDS HEIGHT LIMITATION. PURSUANT TO SEC.
 94-306(A) - HEATING, VENTILATION, AND AIR CONDITIONING
 EQUIPMENT; CHURCH STEEPLES, BELL TOWERS, FLAG POLES,
 CHIMNEYS, PARAPETS, STAIR ENCLOSURES, TANKS, DECORATIVE
 FEATURES, ELEVATOR HOISTWAYS OR EQUIPMENT, TELEVISION
 OR RADIO ANTENNAS, AND RELATED MECHANICAL OR FUNCTIONAL
 FEATURES MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN
 PERCENT. ****NOTE: MAXIMUM DIMENSION FOR CHIMNEY IS 3'
 ABOVE THE HEIGHT OF HOUSE.****
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-16 Cont ID  
Sent By mcruz Date 2018-07-16 Time 12:30 Rev Time 0.00
Received By mcruz Date 2018-07-16 Time 10:59 Sent To PC
Notes
2018-07-16 12:29:47ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) CHIMNEY EXCEEDS HEIGHT LIMITATION. PURSUANT TO SEC.
 94-306(A) - HEATING, VENTILATION, AND AIR CONDITIONING
 EQUIPMENT; CHURCH STEEPLES, BELL TOWERS, FLAG POLES,
 CHIMNEYS, PARAPETS, STAIR ENCLOSURES, TANKS, DECORATIVE
 FEATURES, ELEVATOR HOISTWAYS OR EQUIPMENT, TELEVISION
 OR RADIO ANTENNAS, AND RELATED MECHANICAL OR FUNCTIONAL
 FEATURES MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN
 PERCENT.
 2) PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]