| Plan Review Stops For Permit 18061007 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-09-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-09-16 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
| 2018-09-16 12:10:37 | CHANGED VALUE FROM $15000 TO $49913 PER CONTRACT | | | SUPPLIED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-13 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-13 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2018-08-13 13:58:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. A | | | COST BREAKDOWN MAY BE REQUIRED. | | | THIS CAN BE SENT VIA EMAIL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-07 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-07 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2018-07-07 18:49:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS, FS471. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-09-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-16 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-16 |
Time |
12:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-08-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-07 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-07 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2018-08-07 08:38:01 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE SHOW WINDOW OUTLETS PER 210.62 | | | 2. PLAN DOES NOT SHOW LOCATION OF MECHANICAL EQUIPMENT. | | | PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC | | | 210.63 | | | 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 4. PROVIDE AUTOMATIC CONTROL FOR SIGN CIRCUIT. FBC EC | | | 405.2.4 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-11 |
Time |
05:38 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-11 |
Time |
05:26 |
Sent To |
|
|
| Notes |
| 2018-07-11 05:36:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ELECTRICAL WORK SHOWN ON SUBMITTED PLAN. NOTE #5 | | | IN "SCOPE OF WORK" STATES NEW SWITCHES, RECEPTACLES, | | | SENSORS, ETC WILL BE INSTALLED. PROVIDE ELECTRICAL PLAN | | | FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN | | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. IF | | | THERE IS NOT ANY ELECTRICAL WORK INCLUDED WITH THIS | | | PERMIT, STATE THAT ON PLAN. FS 471.003(2)(H); 471.025; | | | WPB FBC 107.2.1, 107.3.5 | | | | | | 2, PLANS PREPARED BY AN ENGINEER MUST BE SIGNED AND | | | SEALED. PE ONLY SIGNED PLANS. ELECTRICAL PLAN IS | | | REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN | | | PROFESSIONAL. PROVIDE CORRECTION. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-07-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-24 |
Time |
10:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-26 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-09-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-09-16 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-09-11 |
Time |
10:13 |
Sent To |
I |
|
| Notes |
| 2018-09-13 10:13:14 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-13 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-19 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-07-11 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-06-22 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2018-07-13 10:45:05 | LAST REVIEW DONE ON 07/11/18 BY ELECTRICAL REVIEWER. | | 2018-06-25 15:07:19 | B21 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-27 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-27 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-27 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-27 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2018-06-27 14:51:06 | 1ST REVIEW FBC-2017 MECHANICAL | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE MECHANICAL PLAN SHEET M-100.00 WHICH IS | | | LISTED IN THE INDEX ON COVER SHEET T-100.00. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|