Plan Review Details - Permit 18060994
Plan Review Stops For Permit 18060994
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-14 Cont ID  
Sent By fgiaquin Date 2018-08-14 Time 06:32 Rev Time 0.00
Received By fgiaquin Date 2018-08-14 Time 06:14 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By fgiaquin Date 2018-06-29 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2018-06-29 Time 05:38 Sent To I
Notes
2018-06-29 05:50:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A PORTION OF WORK PROPOSED NOT WITHIN SCOPE OF FIRE
 ALARM LICENSE. FS 489.505(7) REQUIRED 120V FEED
 NECESSARY TO POWER NEW FACP IS NOT WITHIN SCOPE OF A EF
 LICENSE. ELECTRICAL PERMIT REQUIRED FBC 105.1
  
 2. A ZERO INCREASE OF VALUE IS UNACCECTABLE. ORIGINAL
 WORK ON THE EXISTING PERMIT HAS BEEN COMPLETED AND
 GIVEN A TCO AND DID NOT INCLUDE THE INSTALLTION OF A
 NEW FACP. THE INSTALLATION OF A NEW FACP AND THE
 ASSOCIATED WORK CANNOT BE DONE WITH A ZERO INCREASE IN
 VALUE. PROVIDE CORRECTION OR VALUE WILL BE ADJUSTED BY
 CITY OF WPB. FBC 109.3
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By scaldero Date 2018-08-06 Time 10:35 Rev Time 0.00
Received By scaldero Date 2018-08-06 Time 10:33 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 11:14 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 11:11 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-14 Cont ID  
Sent By fgiaquin Date 2018-08-14 Time 06:32 Rev Time 0.00
Received By fgiaquin Date 2018-07-26 Time 14:31 Sent To  
Notes
2018-07-31 14:31:24RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By fgiaquin Date 2018-06-29 Time 06:10 Rev Time 0.00
Received By fgiaquin Date 2018-06-20 Time 12:58 Sent To  
Notes
2018-06-21 12:58:17REVISION ROUTED TO FIRE INBOX