Plan Review Details - Permit 18060946
Plan Review Stops For Permit 18060946
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-16 Cont ID  
Sent By jgomez Date 2018-07-16 Time 08:41 Rev Time 0.00
Received By jgomez Date 2018-07-12 Time 13:37 Sent To  
Notes
2018-07-13 13:37:53RESUB OF REVISION ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 18:53 Rev Time 0.00
Received By jgomez Date 2018-06-20 Time 12:55 Sent To I
Notes
2018-06-21 12:55:57REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-16 Cont ID  
Sent By jgomez Date 2018-07-16 Time 08:41 Rev Time 0.00
Received By jgomez Date 2018-07-16 Time 08:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 18:38 Rev Time 0.00
Received By jgomez Date 2018-06-29 Time 18:17 Sent To  
Notes
2018-06-29 18:53:17RESIDENTIAL (R3) MECHANICAL REVISION REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
  
 1- BEDROOM/DEN TRANSFER DUCT SIZE SPECIFIED DOESN'T
 COMPLY WITH THE BALANCED RETURN AIR SEC. M1602.4
 FBC-RESIDENTIAL. THERE ARE TWO SUPPLY DUCTS SHOWN FOR
 THIS ROOM. PLAN SHOW A 9" TRANSFER DUCT. NEED AT LEAST
 A 10" TRANSFER DUCT. REVISE AS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
  
  