Plan Review Details - Permit 18060878
Plan Review Stops For Permit 18060878
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-13 Cont ID  
Sent By ccole Date 2018-07-13 Time 08:34 Rev Time 0.00
Received By ccole Date 2018-07-10 Time 09:33 Sent To  
Notes
2018-07-12 09:36:58RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-29 Time 15:22 Sent To  
Notes
2018-07-02 15:22:50RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-27 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-19 Time 13:21 Sent To  
Notes
2018-06-20 13:21:27ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-07-13 Cont ID  
Sent By ccole Date 2018-07-13 Time 08:33 Rev Time 0.00
Received By ccole Date 2018-07-13 Time 07:35 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-09 Cont ID  
Sent By ccole Date 2018-07-09 Time 10:44 Rev Time 0.00
Received By ccole Date 2018-07-09 Time 10:44 Sent To I
Notes
2018-07-09 10:51:482ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18060878
 7/9/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE KITCHEN HOOD EXHAUST IS PROHIBITED FROM
 CONNECTING TO THE DRYER EXHAUST RISER PER SECTIONS
 504.1 AND 504.10 (ITEM #12) FBC M.
  
 2) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST
 ENCLOSURE- SECTION 602.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By ccole Date 2018-06-27 Time 16:16 Rev Time 0.00
Received By ccole Date 2018-06-27 Time 16:16 Sent To I
Notes
2018-06-27 16:26:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060878
 6/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CONTRACTOR'S SIGNATURE SHALL BE ON THE PLAN- SECTION
 107.2.1 FBC. WPB: ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) SHOW THE LOCATIONS OF ALL RETURN GRILLS OR TRANSFERS
 AND PROVIDE DIMENSIONS- SECTION 601.5 AND 601.6 FBC M
  
 3) IDENTIFY ALL ROOMS AND SPACES ON THE PLAN- SECTION
 601.5 FBC M, AND SECTION 107.2.1 WPB.
  
 4) PROVIDE A MINIMUM 8" DUCT TO SUPPLY THE 225 CFMS OF
 AIR TO THE BEDROOM SHOWN TO THE LEFT OF THE BATH-
 DUCTULATOR AT 0.1" FRICTION LOSS.
  
 5) THE DUCT BOARD SHALL BE R-4.2- TABLE C403.2.9.1 FBC
 EC.
  
 6) CLARIFY THE LOCATION OF THE DRYER EXHAUST DUCT, AND
 NOTE THAT IT SHALL NOT BE RUN THROUGH THE PLENUM-
 SECTION 504.4 FBC M.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 HOOD AND EXHAUST DUCT. NOTE: MAKEUP AIR MAY BE REQUIRED
 PER SECTIONS 505.1 & 505.2 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  