Plan Review Details - Permit 18060781
Plan Review Stops For Permit 18060781
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By skennedy Date 2018-08-20 Time 09:12 Rev Time 0.00
Received By skennedy Date 2018-08-20 Time 09:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 12:26 Rev Time 0.00
Received By shill Date 2018-06-30 Time 12:26 Sent To  
Notes
2018-06-30 12:27:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. SEE PLUMBING COMMENTS FOR ACCESSIBILITY; THEY ARE
 APPLICABLE FOR BUILDING REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 15:47 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-10 Cont ID  
Sent By ppetty Date 2018-08-10 Time 15:01 Rev Time 0.00
Received By ppetty Date 2018-08-10 Time 15:01 Sent To  
Notes
2018-08-10 15:04:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 5. WIRING FROM POWER COMPANY TO METER AND FROM METER TO
 FIRST DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.6
 RISER MISSING
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-03 Cont ID  
Sent By jpearson Date 2018-07-03 Time 09:36 Rev Time 0.00
Received By jpearson Date 2018-07-03 Time 08:42 Sent To I
Notes
2018-07-03 09:36:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC SPECIFIED FOR DESIGN ON SHEET G000 IS NOT
 THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO
 SEE CURRENT CODES ABOVE)
 2. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 5. WIRING FROM POWER COMPANY TO METER AND FROM METER TO
 FIRST DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.6
 6. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 7. PANEL SCHEDULE FOR PANEL A STATES THAT IT IS RATED
 FOR 150 AMPS BUT IS BEING FED WITH CONDUCTORS PROTECTED
 AT 200 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 15:48 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By scaldero Date 2018-08-06 Time 10:31 Rev Time 0.00
Received By scaldero Date 2018-08-06 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-21 Cont ID  
Sent By pleduc Date 2018-06-21 Time   Rev Time 0.00
Received By pleduc Date 2018-06-20 Time 11:20 Sent To  
Notes
2018-06-21 11:33:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-20 Cont ID  
Sent By skennedy Date 2018-08-20 Time 09:12 Rev Time 0.00
Received By skennedy Date 2018-07-26 Time 11:26 Sent To  
Notes
2018-07-27 11:26:20B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-15 Time 10:11 Sent To  
Notes
2018-06-19 10:11:16B11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-07 Cont ID  
Sent By ccole Date 2018-08-07 Time 14:13 Rev Time 0.00
Received By ccole Date 2018-08-07 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By ccole Date 2018-06-21 Time 17:33 Rev Time 0.00
Received By ccole Date 2018-06-21 Time 16:53 Sent To  
Notes
2018-06-21 17:36:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18060781
 6/21/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE PROVIDE COMPLETE PLANS, SPECIFICATIONS, AND
 CALCULATIONS FOR THE NEW TENANT BUILDOUT. SECTION 107.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-17 Cont ID  
Sent By gjohnson Date 2018-08-17 Time 16:36 Rev Time 0.00
Received By gjohnson Date 2018-08-17 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 16:41 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 16:41 Sent To  
Notes
2018-06-29 17:17:421ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALLL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER
  
 3. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4. SHT. P101 THE FIRE STOPPING DETAILS ARE ILLEGIBLE
 PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P101 THE VENT ON THE WATER CLOSET IS A CODE
 VIOLATION A DRY VENT CANNOT RUN HORIZONTAL UNTIL IT IS
 A MIN OF 6" ABOVE FLOOD LEVEL RIM OF THE FIXTURE. IF
 YOU CONNECT THE LAVATORY BRANCH DRAIN TO THE TOILET
 BRANCH DRAIN IT WILL BE A WET VENT A COMPLY WITH THE
 CODE . PER FBC PL 912.1
  
 6. THE LAVATORY IN THE ACCESSIBLE BATHROOM SHAL HAVE
 TEMPERED WATER DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  