| Plan Review Stops For Permit 18060781 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-20 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-20 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-30 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-30 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2018-06-30 12:27:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | 2. SEE PLUMBING COMMENTS FOR ACCESSIBILITY; THEY ARE | | | APPLICABLE FOR BUILDING REVIEW. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-20 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-20 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-08-10 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-08-10 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-08-10 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2018-08-10 15:04:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | | | | 5. WIRING FROM POWER COMPANY TO METER AND FROM METER TO | | | FIRST DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT | | | GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.6 | | | RISER MISSING | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-03 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-03 |
Time |
08:42 |
Sent To |
I |
|
| Notes |
| 2018-07-03 09:36:02 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. THE NEC SPECIFIED FOR DESIGN ON SHEET G000 IS NOT | | | THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO | | | SEE CURRENT CODES ABOVE) | | | 2. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | | 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | | EC C405.6.1 | | | 5. WIRING FROM POWER COMPANY TO METER AND FROM METER TO | | | FIRST DISCONNECT SHOULD NOT INCLUDE AN EQUIPMENT | | | GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC 250.6 | | | 6. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED | | | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE | | | CORRECTION. NEC 700.12(F) | | | 7. PANEL SCHEDULE FOR PANEL A STATES THAT IT IS RATED | | | FOR 150 AMPS BUT IS BEING FED WITH CONDUCTORS PROTECTED | | | AT 200 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-20 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-20 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-08-06 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-08-06 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-08-06 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-20 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2018-06-21 11:33:12 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-20 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-26 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-07-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-15 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-08-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-07 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-07 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-21 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-21 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2018-06-21 17:36:55 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18060781 | | | 6/21/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. | | | PLEASE PROVIDE COMPLETE PLANS, SPECIFICATIONS, AND | | | CALCULATIONS FOR THE NEW TENANT BUILDOUT. SECTION 107.1 | | | WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-17 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-17 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-29 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-29 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2018-06-29 17:17:42 | 1ST REVIEW: FBC 2017 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE | | | REAR WALL GRAB BAR SHALLL BE 36 INCHES (915 MM) LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | | | | | 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER | | | | | | 3. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC | | | 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING | | | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE | | | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. | | | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED | | | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER | | | SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 4. SHT. P101 THE FIRE STOPPING DETAILS ARE ILLEGIBLE | | | PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. SHT. P101 THE VENT ON THE WATER CLOSET IS A CODE | | | VIOLATION A DRY VENT CANNOT RUN HORIZONTAL UNTIL IT IS | | | A MIN OF 6" ABOVE FLOOD LEVEL RIM OF THE FIXTURE. IF | | | YOU CONNECT THE LAVATORY BRANCH DRAIN TO THE TOILET | | | BRANCH DRAIN IT WILL BE A WET VENT A COMPLY WITH THE | | | CODE . PER FBC PL 912.1 | | | | | | 6. THE LAVATORY IN THE ACCESSIBLE BATHROOM SHAL HAVE | | | TEMPERED WATER DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|