Plan Review Details - Permit 18060719
Plan Review Stops For Permit 18060719
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2018-08-21 Time 06:55 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By jleahy Date 2018-06-20 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 13:33 Sent To  
Notes
2018-06-22 18:40:58ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  
2018-06-20 13:34:27FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GENERATOR PAD DONE UNDER ELECTRICAL PLAN REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-20 Cont ID  
Sent By jleahy Date 2018-06-20 Time 13:33 Rev Time 0.00
Received By jleahy Date 2018-06-20 Time 13:32 Sent To G
Notes
2018-06-20 13:36:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 VALUE OF JOB RAISED TO 13,200

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 18:22 Rev Time 0.00
Received By lcrespo Date 2018-08-20 Time 18:21 Sent To  
Notes
2018-08-20 18:22:4208/20/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 15:43 Rev Time 0.00
Received By thunt Date 2018-06-29 Time 15:43 Sent To I
Notes
2018-06-29 15:53:1006/29/2018 1ST GAS REVIEW**DENIED**
  
 1) YOUR PLANS ARE REFERENCING THE 2007 AND 2014 FBC.
 THE CODE IN AFFECT AT THIS TIME IS THE 2017 6TH ED OF
 THE FBC. YOU HAVE NOT INCLUDED A 2 PSI IZING CHART
 EITHER. SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 2) PLAN IS SHOWING SYSTEM AS 2 PSI BUT YOUR PLAN DOES
 NOT SHOW NOR HAVE YOU INCLUDED THE MANUFACTURES
 INSTALLATION MANUALS FOR THE PRESSURE REGULATORS.
 SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.
  
 3) TOTAL JOB VALUE SEEM LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT SHOWING THE COMPLETE COST OF THE GENERATOR
 INSTALLED. FBC 109.3
  
 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 07:05 Rev Time 0.00
Received By rmcdouga Date 2018-08-15 Time 13:10 Sent To  
Notes
2018-08-16 13:11:03RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 15:53 Rev Time 0.00
Received By thunt Date 2018-06-14 Time 16:03 Sent To I
Notes
2018-06-14 16:03:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-19 Cont ID  
Sent By mcruz Date 2018-06-19 Time 10:47 Rev Time 0.00
Received By mcruz Date 2018-06-19 Time 10:43 Sent To B
Notes
2018-06-19 10:50:17ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 9' FROM REAR PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]