Plan Review Details - Permit 18060693
Plan Review Stops For Permit 18060693
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-03-22 Cont ID  
Sent By jduprey Date 2019-03-22 Time 15:44 Rev Time 0.00
Received By jduprey Date 2019-03-22 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-08 Cont ID  
Sent By jduprey Date 2019-02-08 Time 09:13 Rev Time 0.00
Received By jduprey Date 2019-02-08 Time 09:07 Sent To  
Notes
2019-02-08 09:12:48*PROVISO*
  
 PROVIDE A REVISED SHEET A-1 WITH DESIGNER'S ORIGINAL
 SIGNATURE, A COPY WILL NOT BE ACCEPTED. PLANS THAT HAVE
 BEEN PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD SHALL BEAR THE ORIGINAL SIGNATURE, DATE AND SEAL
 OF THE ENGINEER PER FL ADMIN. CODE RULE 61G15-23.001.
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-30 Cont ID  
Sent By shill Date 2018-10-30 Time 18:03 Rev Time 0.00
Received By shill Date 2018-10-29 Time 07:50 Sent To  
Notes
2018-10-30 18:05:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC A 206.2.2, PROVIDE THE SIZE OF THE TABLES.
  
 THIS CAN BE PROVIDED VIA EMAIL. CONTRACTOR WAS SENT AN
 EMAIL BUT NO RESPONSE AT THIS TIME.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 14:54 Rev Time 0.00
Received By shill Date 2018-09-02 Time 14:54 Sent To  
Notes
2018-09-02 14:55:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENT FROM PREVIOUS LIST NOT ADDRESSED:
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471.
  
 SHEET A1 APPEARS TO HAVE A PHOTOCOPY SIGNATURE AND IS
 NOT SEALED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 18:28 Rev Time 0.00
Received By shill Date 2018-07-07 Time 18:28 Sent To  
Notes
2018-07-07 18:29:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-03-21 Cont ID  
Sent By jpearson Date 2019-03-21 Time 10:39 Rev Time 0.00
Received By jpearson Date 2019-03-21 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-09 Cont ID  
Sent By jpearson Date 2018-10-09 Time 10:29 Rev Time 0.00
Received By jpearson Date 2018-10-09 Time 10:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By ppetty Date 2018-08-28 Time 09:39 Rev Time 0.00
Received By ppetty Date 2018-08-28 Time 09:39 Sent To  
Notes
2018-08-27 14:50:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 600.5
 2. OK
 3. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-67
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By jpearson Date 2018-07-12 Time 08:33 Rev Time 0.00
Received By jpearson Date 2018-07-12 Time 07:35 Sent To I
Notes
2018-07-12 08:33:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW OUTLETS PER CODE. THIS CANNOT BE
 TIED TO SIGN CIRCUIT, WHICH IS REQUIRED TO BE A
 DEDICATED CIRCUIT. NEC 210.62, 600.5
 2. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 3. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-03-11 Cont ID  
Sent By scaldero Date 2019-03-11 Time 10:37 Rev Time 0.00
Received By scaldero Date 2019-03-11 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 11:33 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 11:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 11:48 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 11:45 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-25 Cont ID  
Sent By thunt Date 2019-03-25 Time 06:28 Rev Time 0.00
Received By thunt Date 2019-03-05 Time 15:04 Sent To  
Notes
2019-03-06 15:04:24B10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-30 Cont ID  
Sent By shill Date 2018-10-30 Time 18:05 Rev Time 0.00
Received By shill Date 2018-10-02 Time 10:01 Sent To  
Notes
2018-10-04 10:03:16B01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 14:55 Rev Time 0.00
Received By shill Date 2018-08-07 Time 14:18 Sent To  
Notes
2018-08-08 14:18:51B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-07-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-14 Time 15:07 Sent To  
Notes
2018-06-14 15:07:50B06

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-03-21 Cont ID  
Sent By ccole Date 2019-03-21 Time 12:41 Rev Time 0.00
Received By ccole Date 2019-03-21 Time 12:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-22 Cont ID  
Sent By ccole Date 2018-10-22 Time 12:04 Rev Time 0.00
Received By ccole Date 2018-10-22 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By ccole Date 2018-08-23 Time 16:21 Rev Time 0.00
Received By ccole Date 2018-08-23 Time 16:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By ccole Date 2018-06-26 Time 16:17 Rev Time 0.00
Received By ccole Date 2018-06-26 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-03-25 Cont ID  
Sent By thunt Date 2019-03-25 Time 06:28 Rev Time 0.00
Received By thunt Date 2019-03-25 Time 06:03 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 14:06 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 14:06 Sent To  
Notes
2018-10-23 14:06:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW:
 PLUMBING COMMENTS: DENIED
 PREVIOUS COMMENT NOT COMPLIED WITH.
  
 4. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC 202.4, 202.4.1, 202.4.2
 WHEN EVER YOU ALTER A SPACE IT IS NECESSARY TO COMPLY
 WITH THE ACCESSIBILITY CODE INCLUDING EXISTING ELEMENTS
 BUT THE CODE ONLY REQUIRES THAT 20% OF THE OVERALL COST
 OF THE JOB BE USED ON BRING UP THE LEVEL OF
 ACCESSIBILITY. THE CODE LIST THE REQUIRED ELEMENTS THAT
 SHALL COMPLY. THE COST BREAK PROVIDES DOCUMENTATION OF
 HOW YOUR COMPLYING WITH THE ABOVE MENTIONED CODES.
 PLEASE READ THESE CODE SECTIONS TO FAMILIARIZE YOURSELF
 ON THIS SECTION OF THE CODE. FBC ACC 202.4, 202.4.1,
 202.4.2
  
  
 PLUMBING PROVISO
 1. HOT WATER IS REQUIRED FOR THE BREAKROOM SINK. PER
 FBC PL 607.1; MISPRINT ON PLUMBING WATER ISOMETRIC.
 NOTE THE REDLINE CORRECTION TO READ HW
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-31 Cont ID  
Sent By gjohnson Date 2018-08-31 Time 11:29 Rev Time 0.00
Received By gjohnson Date 2018-08-31 Time 09:35 Sent To  
Notes
2018-08-31 11:58:511ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 3. HOT WATER IS REQUIRED FOR THE BREAKROOM SINK. PER
 FBC PL 607.1
  
 4. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC 202.4, 202.4.1, 202.4.2
 WHEN EVER YOU ALTER A SPACE IT IS NECESSARY TO COMPLY
 WITH THE ACCESSIBILITY CODE INCLUDING EXISTING ELEMENTS
 BUT THE CODE ONLY REQUIRES THAT 20% OF THE OVERALL COST
 OF THE JOB BE USED ON BRING UP THE LEVEL OF
 ACCESSIBILITY. THE CODE LIST THE REQUIRED ELEMENTS THAT
 SHALL COMPLY. THE COST BREAK PROVIDES DOCUMENTATION OF
 HOW YOUR COMPLYING WITH THE ABOVE MENTIONED CODES.
 PLEASE READ THESE CODE SECTIONS TO FAMILIARIZE YOURSELF
 ON THIS SECTION OF THE CODE. FBC ACC 202.4, 202.4.1,
 202.4.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By gjohnson Date 2018-07-10 Time 16:20 Rev Time 0.00
Received By gjohnson Date 2018-07-10 Time 16:20 Sent To  
Notes
2018-07-10 17:38:051ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW SIDE GRAB BAR SHALL COMPLY WITH FBC ACC
 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
  
 2. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL
 CONNECT TO THE BUILDING DRAIN DOWN STREAM OF THE
 EXISTING BATHROOM GROUP. PER FBC PL 912.1
  
 3. HOT WATER IS REQUIRED FOR THE BREAKROOM SINK. PER
 FBC PL 607.1
  
 4. PLEASE PROVIDE A COST BREAKDOWN TO SHOW COMPLIANCE
 WITH FBC ACC 202.4, 202.4.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  