| 2018-07-09 16:40:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC |
| | 109.3 (CONTRACT WAS NOT SIGNED AND THEREFORE NOT VALID. |
| | THE SIGNATURE OF OWNER WAS ON THE UTILITIES PAPERWORK, |
| | SO IT OBVIOUSLY IS ATTAINABLE.) |
| | 2. ALL COPIES OF PLAN SHEETS ARE REQUIRED TO HAVE THE |
| | SIGNATURE, PRINTED NAME, AND LICENSE NUMBER(IF |
| | APPLICABLE) OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | THIS INCLUDES THE LOAD CALCULATION SHEET AND RISER |
| | DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.1, 107.2.1 |
| | (SEVERAL SHEETS IN PACKAGE ARE NOT SIGNED BY THE |
| | QUALIFIER. IF ANY SHEETS ARE NOT TO BE USED, THEY |
| | SHOULD BE REMOVED OR MARKED AS VOID. ALL OTHER SHEETS |
| | MUST BEAR THE NAME AND SIGNATURE OF THE QUALIFIER.) |
| | 3. RISER DIAGRAM SHOWS THE NEW 200 AMP TRANSFER SWITCH |
| | FEEDING THE LOAD CONTROL MODULE. IT SEEMS THAT THIS |
| | TRANSFER SWITCH SHOULD FEED A PANEL, WHICH THEN FEEDS |
| | THE LOAD CONTROL MODULE TO THE LOADS THAT ARE BEING |
| | MANAGED. ALSO, HOW IS THE WHOLE HOUSE ON THE GENERATOR |
| | WHEN THERE IS STILL A 100 AMP MAIN THAT IS NOT |
| | CONNECTED TO THE GENERATOR? PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. SHOW ALL LOADS BEING MANAGED. NEC |
| | 215.5; WPB FBC 107.2.1 (RISER DIAGRAM WIRING DOES NOT |
| | MATCH THE SPEC SHEET INSTALLATION AS PROVIDED AND DOES |
| | NOT MAKE SENSE. PROVIDE CORRECTED RISER DIAGRAM SHOWING |
| | ALL PANELS FEED FROM THE TWO TRANSFER SWITCHES AS |
| | PREVIOUSLY REQUESTED.) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |