Plan Review Details - Permit 18060684
Plan Review Stops For Permit 18060684
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By jesmith Date 2019-01-23 Time 15:29 Rev Time 0.00
Received By pvalenti Date 2019-01-23 Time 15:29 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-07-11 Cont ID  
Sent By rmcdouga Date 2018-07-11 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-07-11 Time 18:59 Sent To  
Notes
2018-07-11 19:00:03THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By pvalenti Date 2019-01-23 Time 13:58 Rev Time 0.00
Received By pvalenti Date 2019-01-23 Time 11:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-10 Cont ID  
Sent By pvalenti Date 2018-12-10 Time 13:32 Rev Time 0.00
Received By pvalenti Date 2018-12-10 Time 11:25 Sent To  
Notes
2018-12-10 13:52:24****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 AFTER REVIEWING THE RESPONSES FROM THE LAST BUILDING
 PLAN REVIEW, THERE ISARE STILL SOME PENDING ITEMS.
  
 PLEASE REVIEW AND SUBMIT THE REQUIRED INFORMATION FROM
 THE LIST:
  
 1. OK
 2. OK
 3. OK
 4. PLEASE PROVIDE THE PRODUCT APPROVAL THAT IS APPROVED
 BY THE REGISTERED DESIGN PROFESSIONAL FOR THE
 WINDOW/DOOR MULLIONS.
 5. OK
 6. & 7 PLEASE PROVIDE THE PRODUCT APPROVAL THAT IS, THE
 ONE TO BE USED, APPROVED BY THE REGISTERED DESIGN
 PROFESSIONAL FOR THE GARAGE DOOR.
 8. OK
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-12 Cont ID  
Sent By pvalenti Date 2018-07-12 Time 18:14 Rev Time 0.00
Received By rmcdouga Date 2018-07-12 Time 18:14 Sent To  
Notes
2018-07-12 17:53:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC RESIDENTIAL SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A DRAINAGE PLAN THAT COMPLIES
 WITH FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING. FBC 107.2.5 THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL
 SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND
 SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE
 TO REMAIN ON THE SITE OR PLOT.
  
 2) THE WOOD FRAME STUCCO WALLS ARE REQUIRED TO COMPLY
 WITH FBC-R703.7 EXTERIOR PLASTER. INSTALLATION OF THESE
 MATERIALS SHALL BE IN COMPLIANCE WITH ASTM C926, ASTM
 C1063 AND THE PROVISIONS OF THIS CODE.
  
 2A) FBC-R703.7.2.1 WEEP SCREEDS. A MINIMUM 0.019-INCH
 (0.5 MM) (NO. 26 GALVANIZED SHEET GAGE),
 CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP SCREED,
 WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF 31/2
 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE
 PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
 2B) FBC-R703.7.3 WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 3C) TABLE FBC-R702.1(1) REQUIRES EXTERIOR CEMENT
 PLASTER ON WIRE LATH TO HAVE A MINIMUM THICKNESS OF 7/8
 INCH.
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
 4A) THE PRODUCT APPROVALS HAVE NOT BEEN APPROVED AND
 ACCEPTED IN WRITING BY THE DOR.
 4B) THE FLORIDA PRODUCT APPROVAL DRAWINGS THAT WERE
 SUBMITTED ARE REQUIRED TO HAVE THE COVERSHEETS WITH THE
 FL NUMBERS THAT LIST THE DRAWING NUMBERS.
 4C) THE PRODUCT APPROVALS FOR THE IMPACT RATED GLASS
 BLOCK, FIXED WINDOWS, STRUCTURAL MULLIONS AND
 HORIZONTAL ROLLING WINDOWS WERE NOT SUBMITTED.
 4D) THE SPECIFIC ITEMS THAT YOU ARE PROPOSING TO BE
 INSTALLED AND THEIR DESIGN PRESSURES NEED TO BE MARKED
 ON THE PRODUCT APPROVAL SUBMITTALS. THERE ARE SEVERAL
 DIFFERENT TYPES OF THE ITEMS LISTED IN THE PRODUCT
 APPROVALS.
  
 5) THE PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOW (NOA
 NO. 15-0602.06) IS SUPERSEDED BY NOA NO. 18-0124.06.
 SUBMIT THE CURRENT ONE.
  
 6) THE PLANS SPECIFY AN OVERHEAD GARAGE DOOR THAT IS 8'
 IN HEIGHT AND THE PRODUCT APPROVALS ARE FOR AN 8' HIGH
 DOOR. IN THE SUBMITTAL DOCUMENTS, THERE IS WHAT APPEARS
 TO BE A HOME DEPOT ORDER FORM FOR A 7' HIGH GARAGE
 OVERHEAD DOOR. PLEASE CLARIFY.
  
 7) THERE ARE PRODUCT APPROVALS FOR TWO DIFFERENT GARAGE
 DOORS HAVING DIFFERENT DESIGN PRESSURES WITH THE
 SUBMITTAL DOCUMENTS. MARK AS VOID OR REMOVE FROM THE
 PERMIT DOCUMENTS THE ONE THAT WILL NOT BE USED.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By jpearson Date 2018-11-01 Time 11:21 Rev Time 0.00
Received By jpearson Date 2018-11-01 Time 10:06 Sent To  
Notes
2018-11-29 14:24:13APPROVED WITH EXCEPTION - SEE PROVISO ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-10 Cont ID  
Sent By jpearson Date 2018-07-10 Time 14:53 Rev Time 0.00
Received By jpearson Date 2018-07-10 Time 10:54 Sent To  
Notes
2018-07-10 14:53:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 2. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 4. AFCI PROTECTION NOTED ON PLAN IS NOT CODE COMPLIANT.
 PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 6. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 7. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 8. LIGHT IN MASTER CLOSET APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 9. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 10. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-23 Cont ID  
Sent By pvalenti Date 2019-01-23 Time 15:29 Rev Time 0.00
Received By pvalenti Date 2018-12-31 Time 13:57 Sent To  
Notes
2019-01-02 13:57:13R25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By cpuell Date 2018-12-11 Time 15:03 Rev Time 0.00
Received By cpuell Date 2018-10-16 Time 11:40 Sent To  
Notes
2018-10-18 11:40:49R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-30 Cont ID  
Sent By thunt Date 2018-07-30 Time 10:13 Rev Time 0.00
Received By thunt Date 2018-06-14 Time 15:11 Sent To I
Notes
2018-06-14 15:11:22R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By pvalenti Date 2019-01-23 Time 13:53 Rev Time 0.00
Received By pvalenti Date 2019-01-23 Time 13:52 Sent To  
Notes
2019-01-23 13:58:00IMPACT FEES:
  
 APPROVED
  
 THE PLANS ARE STAMPED BY THE COUNTY AND A RECEIPT WAS
 PROVIDED.
  
 RECEIPT NUMBER: 2018-1231-186
  
 TRACKING NUMBER: MU-2018-042231-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-11 Cont ID  
Sent By rmcdouga Date 2018-07-11 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2018-07-11 Time 16:57 Sent To  
Notes
2018-07-11 16:57:31BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By cmontell Date 2018-11-01 Time 15:06 Rev Time 0.00
Received By cmontell Date 2018-11-01 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By cmontell Date 2018-07-23 Time 15:01 Rev Time 0.00
Received By cmontell Date 2018-07-23 Time 15:01 Sent To  
Notes
2018-07-23 15:03:03NEED CORRECT ADDRESS ON PLAN FOR PERMIT
  
 CHRIS MONTELLO
 805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-22 Cont ID  
Sent By jesmith Date 2019-01-22 Time 15:32 Rev Time 0.00
Received By jesmith Date 2019-01-22 Time 14:49 Sent To  
Notes
2019-01-22 15:32:24APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-29 Cont ID  
Sent By jesmith Date 2018-11-29 Time 13:57 Rev Time 0.00
Received By jesmith Date 2018-11-29 Time 13:56 Sent To  
Notes
2018-11-29 13:57:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
  
 1. RESPONCE TO ITEM #2 OF THE 1ST REVIEW IS STILL
 INCORRECT. DRY VENTS MUST RISE VERTICALLY FROM THE
 DRAIN BEING VENTED PER FBC RES P3104.3 AND
 P3404.4.PROVIDE A CORRECTED PLUMBING ISOMETRIC REMOVING
 THE FLAT DRYVENTS AND ONLY SHOWING WET VENTING AS
 REQUIRED FBC RES P3108.1
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By thunt Date 2018-07-30 Time 10:04 Rev Time 0.00
Received By thunt Date 2018-07-30 Time 08:41 Sent To  
Notes
2018-07-30 10:13:4107/30/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) VALUE.THE VALUE SEEM'S TOO LOW AND MUST BE ACTUAL
 VALUE.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED
  
 2) PROVIDE A CORRECTED PLUMBING ISOMETRIC REMOVING THE
 FLAT DRYVENTS AND ONLY SHOWING WET VENTING AS REQUIRED
 FBC R P3108.1
  
 3) SHT. A-1 CALLS OUT FOR A TANKLESS WATER HEATER (HWH)
 BUT YOUR FORM R405-2017 IS CALLING OUT A 40 GALLON TANK
 HWH WITH A E.F OF .97. PLEASE CLARIFY WHICH HEATER IS
 BEING USED AND PROVIDE THE FULL INSTALLATION MANUAL.
 PLEASE BE ADVISED I HAVE NEVER COME ACROSS AN ELC
 TANKLESS WITH THAT HIGH VALUE E.F RATING AND THIS MAY
 AFFECT THE OVERALL R405-2017 FORM.
  
 4) TANKLESS MUST BE ABLE TO SUPPLY ALL HOT WATER
 FIXTURE ALL FULL DEMAND. FBC R P2903.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-04 Cont ID  
Sent By awooten Date 2019-01-04 Time   Rev Time 0.00
Received By awooten Date 2019-01-04 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-12-10 Time   Rev Time 0.00
Received By awooten Date 2018-10-29 Time 13:50 Sent To  
Notes
2018-12-10 16:01:48************************************ZONING REVIEW
 FAILED***************************************
  
 PLEASE SUBMIT LANDSCAPE PLANS WITH A SEPARATE PERMIT
 APPLICATION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-30 Cont ID  
Sent By awooten Date 2018-07-30 Time 10:04 Rev Time 0.00
Received By thunt Date 2018-06-20 Time 15:15 Sent To  
Notes
2018-06-21 10:37:41*****************************ZONING REVIEW
 FAILED******************************
  
 PROVIDE LANDSCAPING.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 *GROSS LOT SQUARE FOOTAGE MINUS
 *BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 *OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 *ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 *ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 DIMENSION MECHANICAL EQUIPMENT SETBACKS.
  
 *MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 POOLS, FENCE, AND DRIVEWAYS REQUIRE A SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  