Plan Review Details - Permit 18060663
Plan Review Stops For Permit 18060663
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By jleahy Date 2018-11-01 Time 13:14 Rev Time 0.00
Received By jleahy Date 2018-11-01 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By jleahy Date 2018-06-18 Time 07:33 Rev Time 0.00
Received By jleahy Date 2018-06-18 Time 07:33 Sent To  
Notes
2018-06-18 07:40:55FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO VALUE SHOWN
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
  
 F.S. 471.003 (H)?ANY ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE
 PRACTICE INCLUDES THE DESIGN AND FABRICATION
 OF ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL SYSTEMS, RESPECTIVELY, WHICH SHE OR HE
 INSTALLS BY VIRTUE OF A LICENSE
 ISSUED UNDER CHAPTER 489, UNDER 1PART I OF CHAPTER 553,
 OR UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON
 ANY CONSTRUCTION
 PROJECT WHICH:
  
 1.?REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
  
  
 2.A .REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM;
  
  
 PLAN DOES NOT SHOW GROUNDING
  
 PLAN SOES NOT STATE VOLTAGE
  
 WHERE DOES TEMPORARY TRANSFORMER GET ITS POWER?

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-01 Cont ID  
Sent By jleahy Date 2018-11-01 Time 13:15 Rev Time 0.00
Received By jleahy Date 2018-10-26 Time 15:06 Sent To  
Notes
2018-10-29 15:07:06RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-18 Cont ID  
Sent By jleahy Date 2018-06-18 Time 07:41 Rev Time 0.00
Received By jleahy Date 2018-06-14 Time 16:12 Sent To  
Notes
2018-06-14 16:12:55ELEC <5K