| 2018-06-21 17:01:12 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE FOLLOWING NEEDS TO BE CORRECTED FOR THE STORM |
| | PANELS, FL11964-R4. |
| | 1A. SHUTTER SCHEDULE SPECIFIES DM - DIRECT MOUNT. |
| | DETAILS CIRCLED ON PA ARE FOR STUDDED ANGLES. |
| | 1B. SHUTTER GLASS SEPERATION ON SHUTTER SCHEDULE |
| | SPECIFIES N/A. REQUIREMENTS FOR GLASS SEPERATION ON PA |
| | IS MINIMUM 1 INCH. |
| | 1C. MINIMUM EDGE DISTANCE FOR FASTENERS ON SHUTTER |
| | SCHEDULE SPECIFIES 1 1/2 INCH. MINIMUM EDGE DISTANCE ON |
| | PA IS 3 INJCHES FOR DIRECT MOUNT SOLID SET SYSTEM. |
| | 1D. SUBSTRATE SPECIFIED ON SHUTTER SCHEDULE IS |
| | CONCRETE. BUILDING WAS BUILT IN 1950. PROVIDE |
| | DOCUMENTATION WALL IS SOLID CONCRETE NOT CMU. |
| | |
| | 2. THE FOLLWING NEEDS TO BE CORRECTED FOR THE ACCORDIAN |
| | SHUTTERS, FL1850-R14. |
| | 2A. EXPLAIN WHAT SHUTTER MOUNTING TYPE A/D IS. |
| | 2B. ON PAGE 11 OF 20 OF THE PA SELECT SCHEDULE TO BE |
| | USED. THREE SEPERATE SCHEDULES HAVE BEEN SELECTED. |
| | 2C. SEPERATION TO GLASS FOR OPPOSING CENTERMATES IS 4 |
| | INCHES. |
| | |
| | CONTRACTOR MAY REQUEST AN IN-PERSON REVIEW PRIOR TO |
| | RESUBMITTAL. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |