| Plan Review Stops For Permit 18060620 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-17 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-17 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2018-10-18 08:18:24 | PROVISOS: | | | 1. FENESTRATION | | | 2. STAIRS | | | 3. RAILS/GUARD RAILS | | | 4. ROOFING (SUBMIT WITH SUB PERMIT) | | | 5. ELEVATION CERTIFICATE TO VERIFY SLAB POR TO D.F.E. | | | 8'-0" MINIMUM. | | | 6. FINAL CONSTRUCTION ELEVATION CERTIFICATE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-11 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-11 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2018-10-11 15:35:58 | ****CORRECTIONS**** | | | | | | PERMIT #18060620 | | | 2ND REVIEW: OCTOBER 11, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1-4. OK | | | | | | 4.(B) PROVIDE A FLOOD ELEVATION CERTIFICATE WITH DESIGN | | | FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL EQUIPMENT AS | | | APPLICABLE. | | | | | | WE ARE LOOKING FOR YOU TO PROVIDE THE FLOOD CERTIFICATE | | | IN ADDITION TO SHOWING ELEVATIONS ON THE PLANS. | | | PLEASE PROVIDE FLOOD ELEVATION CERTIFICATE AVAILABLE AT | | | WWW.FEMA.GOV (SEARCH FLOOD ELEVATION CERTIFICATE) | | | | | | 5-7. OK | | | | | | 8. DEFERED | | | | | | 9. DEFERED | | | | | | 10. OK | | | | | | 11. DEFERED | | | | | | 12. DEFERED | | | | | | 13. DEFERED | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2018-07-10 15:29:05 | | | | REVIEW BY | | | DYLAN BATTLES, BUILDING PLANS EXAMINER | | | 561 805-6718 | | | AUDITED BY | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | | | | FIRST REVIEW | | | | | | PERMIT APPLICATION #18060620 | | | | | | CODE IN EFFECT | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | NOTE THE DESIGNER OF RECORD HAS ELECTED TO DEFER THE | | | SUBMITTAL OF THE FOLLOWING PRODUCTS: | | | | | | A) WINDOWS/DOORS | | | B) STAIRS | | | C) RAILS | | | D) ROOFING | | | | | | PLEASE NOTE THE PROPERTY CONTROL NUMBER(PCN) ON | | | APPLICATION HAS BEEN CORRECTED. THE PCN FOR 120 SUMMA | | | IS 74-43-44-10-15-000-0320. | | | | | | PLEASE PROVIDE OR MAKE THE FOLLOWING CORRECTIONS: | | | | | | 1. PLEASE CORRECT THE COVER PAGE TO INDICATE THE | | | APPLICABLE CODE IN EFFECT. | | | 2. [FBC R107.2.5]PROVIDE SURVEY OF PROPERTY. SURVEY TO | | | INCLUDE EASEMENTS LOCATED ON PROPERTY. | | | 3. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. TO COMPLY | | | WITH [FBC R401.3]. THE CURRENT SHEET C1 WOULD NOT MEET | | | DRAINAGE REQUIREMENTS. WHERE DOES TRENCH DRAIN RELEASE? | | | CONSIDER HOW TO UTILIZE SCUPPERS, GUTTERS AND DRAINS TO | | | MANAGE WATER WITHIN SITE AND DRAIN TO SANITARY SEWER | | | INLETS. | | | | | | 4. THE CITY OF WPB HAS ADOPTED A 2' FREEBOARD ABV. BASE | | | FLOOD ELEVATION. THIS PROPERTY HAVE A BASE FLOOD | | | ELEVATION OF 6' NAVD88. THAT WOULD PUT YOUR LOWEST | | | FLOOR LEVEL AT 8' NAVD88. PLEASE ADJUST YOUR ELEVATIONS | | | AND EXPRESS IN NAV88, NOT NGVD ON SHEET A-0.1 & C1. | | | GARAGE CAN BE LOWER THAN 8' NAVD88 WITH THE FLOOD DRAIN | | | LOUVERS AS SPECIFIED ON SHEET A-1.0 | | | 4.(B) FBC 107.3.5.3.1 PROVIDE A FLOOD ELEVATION | | | CERTIFICATE WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY | | | MECHANICAL EQUIPMENT AS APPLICABLE. | | | 5. [FBC R903.4]PROVIDE ROOF DRAINAGE CALCULATION AND | | | SCUPPERS DETAIL TO COMPLY. | | | 6. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING | | | CAPACITY. | | | 7. [FBC R506.2.3] A 6-MIL POLYETHYLENE OR APPROVED | | | VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 | | | INCHES. UPDATE NOTE ON S-1 TO REQUIRE 6 MIL. | | | | | | 10. [FBC R301.2.1]PROVIDE METHOD USED TO DETERMINE | | | OPENING PRESSURES. SHOW PRESSURES AT EACH OPENING ON | | | ELEVATION SHEETS OR DOOR/WINDOW SCHEDULES (INCLUDE END | | | ZONES AS APPLICABLE). | | | | | | ALTHOUGH THE DESIGNER HAS ELECTED TO DEFER PRODUCT | | | APPROVALS, PLEASE NOTE THE BELOW: | | | 11. SUBMITTED N.O.A. NO.16-0808.11 IS FOR GARAGE DOORS | | | UP TO 14'-2" WIDE. PLEASE PROVIDE PRODUCT APPROVAL FOR | | | 16' WIDE GARAGE DOOR AS SHOWN ON DOOR SCHEDULE. | | | | | | PLEASE STAMP ALL PRODUCT APPROVALS AS REVIEWED, LIST | | | NOA'S ON PLANS OR CREATE 8 1/2 X 11 REVIEW SHEET TO | | | LIST ALL NOA'S ON PROJECT. | | | | | | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-10-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-03 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-01 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2018-10-02 07:26:32 | APPROVED | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-16 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-16 |
Time |
10:13 |
Sent To |
I |
|
| Notes |
| 2018-07-16 16:56:43 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET E-3 STATES THAT ALL ELECTRICAL SHALL COMPLY | | | WITH NEC 2014, BUT THEN IN SEVERAL LOCATIONS AFTER THAT | | | THE 2008 OR 2011 NEC IS STATED AS BASIS FOR DESIGN. | | | CORRECT ALL DISCREPANCIES ON PLAN. WPB FBC 107.2.1 | | | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 3. AIC RATING OF PANELS IN PANEL SCHEDULES CONFLICTS | | | WITH WHAT IS STATED IN THE RISER DIAGRAM. CORRECT ALL | | | DISCREPANCIES ON PLAN. WPB FBC 107.2.1 | | | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 | | | 5. PROVIDE ACCURATE LOAD CALCULATION. PANEL P IS NOT | | | PERMITTED TO USE DEMAND FACTORS AS IT IS A 60 AMP | | | PANEL. PANEL B IS NOT PERMITTED TO USE DEMAND FACTORS | | | AS IT IS A 60 AMP PANEL. PANEL A SHOWS VALUES FOR | | | AC/AHU THAT CONFLICT WITH WHAT IS LISTED IN CIRCUIT | | | DESCRIPTION. NEC 215.2, 220.82, 408.30; FBC RE E3602.2 | | | 6. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE | | | OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING | | | UNIT. NEC 210.52(E)(3); FBC RE E3901.7 | | | 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC | | | 210.52; FBC RE E3901.2.1 | | | 8. BE ADVISED THAT GENERATORS AND SWIMMING POOLS ARE | | | NOT INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE | | | A BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS | | | AND PLAN SUBMITTALS FOR THESE SYSTEMS. WPB FBC 105.1, | | | 107.2.1 | | | 9. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED. | | | PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3 | | | 10. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE | | | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. | | | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 | | | 11. ALL 120 VOLT RECEPTACLE OUTLETS INSTALLED IN | | | LAUNDRY AREAS SHALL HAVE GFCI AND AFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8(A)(9), 210.12(A); FBC RE | | | E3902.9, 3902.16 | | | 12. PANEL P APPEARS TO NOT HAVE THE CLEARANCE REQUIRED | | | PER CODE. PROVIDE CORRECTION. NEC 110.26; FBC RE | | | E3405.1 | | | 13. PLAN DOES NOT SHOW THE LOCATION OF ATS SHOWN ON | | | RISER DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-10-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-12 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-12 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-07-12 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-11 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2018-07-12 08:14:09 | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | 1ST REVIEW: | | | GAS COMMENTS: | | | | | | 1. PLEASE LIST THE SIZING TABLES USED FOR SIZING THIS | | | SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | 2. SHOW THE DISTANCE FROM THE REGULATOR TO THE | | | APPLIANCE IT CAN BE A TYPICAL NOTE ON THE PLAN. PER FBC | | | FG 402 | | | 3. THE RISER LIST THE BBQ AT100,000 BTU THE TOTAL GAS | | | CONNECTED LOAD LIST THE BBQ GRILL AT 75,000BTU PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND | | | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | | SEC.G2408.1. | | | 5. ONE OF THE TANKLESS WATER HEATERS IS SHOWN INSIDE OF | | | THE GARAGE PLEASE SUBMIT A DETAIL SHOWING THE TYPE OF | | | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE | | | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER | | | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. | | | SEC.G2426 THROUGH G2439. | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR | | | 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | | | | | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-16 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-18 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-07-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-13 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-16 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-16 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2018-10-24 14:31:55 | CHANGE RESULT TO PASS, DESIGNER WILL REMOVE NOTE, | | | RETURNS DUCTED TO PLENUM. | | 2018-10-16 15:22:28 | 2ND REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | | | | PLEASE DEMONSTRATE COMPLINACE WITH M1602.3 BALANCED | | | RETURN AIR. NOTE 19 ON SHEET M-2 INDICATES RETURN DUCTS | | | TO BE 1.5 X SUPPLY TO BEDROOMS. THE PLANS DO NOT | | | INDICATE THIS. | | | | | | RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS | | | ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS | | | IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING | | | SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS | | | RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN | | | PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH | | | RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID | | | UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED | | | BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS | | | CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL | | | BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS. | | | PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING | | | SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5 | | | PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER | | | PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE. | | | | | | EXCEPTIONS: | | | | | | 1.TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR | | | SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN | | | AIR BALANCE. | | | | | | 2.TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGHTHE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | | | | 3.HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE | | | REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, | | | EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL | | | BE INCLUDED. | | | | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-10 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
P |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-09 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-09 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2019-12-09 07:48:24 | FLOOD ZONE AE | | | B.F.E. 6'-0" NAVD | | | D.F.E. 8'-0" NAVD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-10-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-12 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-12 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-07-11 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-11 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2018-07-11 14:47:54 | 1ST REVIEW: FBC 2017 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. P-2 THE SANITARY ISOMETRIC HAS MULTIPLE CODE | | | VIOLATIONS PLEASE CORRECT THE FOLLOWING | | | A) THE TOILET IN BATHROOM 1 IS NOT VENTED IT SHOULD BE | | | VENTED BY THE LAVATORY VENT STACK THE LAVATORY AND THE | | | SHOWER SHOULD CONNECT TO THE TOILET BRANCH DRAIN FOR A | | | WET VENTED BATHROOM GROUP | | | B) THE LAVATORY IN BATHROOM 1 SHALL HAVE A VENT THROUGH | | | THE ROOF OR AN AAV. | | | C) THE BBQ KITCHEN SINK SHALL CONNECT SEPARATELY TO THE | | | BUILDING DRAIN IT CANNOT CONNECT TO THE BATHROOM GROUP. | | | D) THE POWDER ROOM LAVATORY AND TOILET ARE NOT VENTED | | | THE LAVATORY SHALL CONNECT TO THE TOILET BRANCH DRAIN | | | BEFORE CONNECTING TO THE BUILDING DRAIN THE LAVATORY | | | VENT SHALL GO THROUGH THE ROOF OR HAVE A AAV. | | | E) THE DRY VENT UPSTREAM OF THE MASTER BATH TOILET IS A | | | CODE VIOLATION A DRY VENT CANNOT RUN HORIZONTALLY | | | BEFORE IT RUNS VERTICALLY ABOVE THE FLOOD LEVEL RIM OF | | | THE FIXTURE THIS VENT IS NOT REQUIRED THE TOILET IS | | | VENTED BY THE LAVATORY. | | | F) IN THE MASTER BATHROOM THE TUB SHALL CONNECT DOWN | | | STREAM OF THE LAVATORY YOU CANNOT HAVE 2 FIXTURES | | | UPSTREAM OF THE WET VENT CONNECTION. | | | G) IN BATHROOM 2 THE TOILET AND THE TUB SHOULD CONNECT | | | TO THE BRANCH FOR THE LAVATORY TO CREATE A WET VENTED | | | BATHROOM GROUP AND CONNECT TO THE BUILDING DRAIN | | | SEPARATELY FROM THE SOIL STACK FROM 2ND FLOOR AND | | | LAUNDRY SINK. | | | PER FBC PL P3101.2.1, P3108.1, | | | | | | 2. THE ENERGY CALCULATION LIST A 40 GAL ELECTRIC WATER | | | HEATER THE PLAN SHOWS 2 GAS TANKLESS PLEASE CLARIFY. | | | PER AMEND TO FBC 107.2.1 | | | | | | 3. PLEASE REVISE THE FLOOR PLAN TO REFLECT A REVISED | | | SANITARY ISOMETRIC. PER AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-07-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-10 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-10 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2018-07-10 15:08:37 | DEFERRED SUBMITTAL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-10-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-10-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-10-19 12:36:11 | ******ZONING PROVISO****** | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | LANDSCAPE INSPECTION. | | | | | | ALANA WOOTEN | | | PLANNING DIVISION | | | ASSOCIATE PLANNER | | | 561-822-1449 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-10-09 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-10-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-10-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-10-09 16:03:48 | *****************************************************ZO | | | NING REVIEW | | | FAILED********************************************** | | | | | | THE SETBACKS ON SURVEY DO NOT MATCH THE SETBACKS ON THE | | | SITE PLAN. | | | | | | THE LANDSCAPE AND IRRIGATION PLAN MUST BE SUBMITTED | | | PRIOR TO THIS PERMIT BEING APPROVED. PLEASE CONTACT ME | | | IF YOU WOULD LIKE TO APPLY FOR A CONDITIONAL LANDSCAPE | | | APPROVAL. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
awooton |
Date |
2018-06-21 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-06-20 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2018-06-21 10:11:21 | *****************************************ZONING REVIEW | | | FAILED*********************************** | | | | | | PROVIDE A SURVEY OF PROPERTY WITH PROPOSED STRUCTURE | | | AND ALL SETBACKS. | | | | | | DIMENSION THE LOT SIZE ON THE SITE PLAN. | | | | | | THE REAR SETBACK SHOULD BE 10% OF LOT DEPTH OR 15 FEET. | | | WHICHEVER IS THE LESSER NUMBER. | | | | | | LABEL THE 10 FOOT SIDE SETBACK ON THE EAST SIDE. | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. | | | | | | SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | *GROSS LOT SQUARE FOOTAGE MINUS | | | *BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | *OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | *ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | *ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | | | | DIMENSION MECHANICAL EQUIPMENT SETBACKS. | | | | | | *MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN FOUR FEET INTO A SETBACK. | | | | | | STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING | | | BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES, | | | AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER | | | THAN THREE FEET INTO ANY SETBACK. | | | | | | *DIMENSION THE BALCONY PROJECTION INTO THE SETBACK. | | | | | | POOLS, FENCE, AND DRIVEWAYS REQUIRE A SEPARATE PERMIT. | | | | | | FURTHER COMMENTS MAY FOLLOW ADDITIONAL REVIEW. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|